Lithonia Lighting LBR4 Series: 4" Open and Wallwash LED Retrofit/Remodel Downlight
Features & Specifications
Intended Use
Typical applications include corridors, lobbies, conference rooms, and private offices.
Construction
Retrofit, remodel, and new construction mounting types. See table for compatible ceiling openings and thickness range. Optional goof rings available for additional overlap trim coverage. Supports 1/2"-1-1/2" ceiling thickness. Rated for 25°C ambient temperature. IC rated up to 1000lm.
Optics
LEDs are binned to a 3-step Mac Adam Ellipse with a 55° cutoff. New construction frame accessories approved for 8 (4 in/4 out) No. 12 AWG conductors rated for 90°C through wiring. Available in 80CRI standard (90CRI optional). UGR is zero for fixtures aimed at nadir with a cut-off equal to or less than 60deg, per CIE 117-1996.
Electrical
Features adjustable lumen output with four module options; fixed lumen options also available. MVOLT (120/277V, 50/60Hz) driver supports 0-10V and 120V Phase Dimming down to 10% or 1% minimum dimming level. Complies with FCC CFR Title 47 Part 15 Class A for 277V and Class B for 120V.
Lumen Maintenance
L80 at 60,000 hours.
Listings
Certified to US and Canadian safety standards. Damp location standard (Wet Location (WL) optional, requires covered ceiling). TAA compliant. UFC (3-530-01) specification compliant for power factor and THD. GSA P100 6.2.4 compliant for power quality at full output; compliant up to 2000lm at fully dimmed output. Drivers are ROHS compliant. Title 24 compliant (90CRI, up to 1000lm).
Warranty
5-year limited warranty. For complete terms, visit www.acuitybrands.com/support/warranty/terms-and-conditions.
Note on Performance
Actual performance may differ based on end-user environment and application. All values are design or typical, measured under laboratory conditions at 25°C. Specifications are subject to change without notice.
Performance Data
Data for LBR4 AR LSS MWD and LBR4 MS MWD models.
Lumen Output | Wattage | 30K/80CRI | 35K/80CRI | 40K/80CRI | 50K/80CRI | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Delivered Lumens | LPW | Delivered Lumens | LPW | Delivered Lumens | LPW | Delivered Lumens | LPW | ||||||||||
LBR4 AR LSS MWD | |||||||||||||||||
AL01 (500LM) | 6 | 570 | 99 | 584 | 101 | 597 | 102 | 616 | 105 | ||||||||
AL01 (750LM) | 9 | 903 | 102 | 924 | 103 | 946 | 105 | 975 | 108 | ||||||||
AL01 (1000LM) | 13 | 1268 | 98 | 1297 | 100 | 1328 | 102 | 1369 | 104 | ||||||||
AL02 (1000LM) | 13 | 1344 | 108 | 1375 | 110 | 1408 | 112 | 1451 | 115 | ||||||||
AL02 (1500LM) | 19 | 1961 | 105 | 2007 | 106 | 2055 | 108 | 2118 | 111 | ||||||||
AL02 (2000LM) | 25 | 2471 | 99 | 2528 | 101 | 2588 | 103 | 2668 | 105 | ||||||||
AL03 (2000LM) | 25 | 2542 | 103 | 2601 | 104 | 2663 | 106 | 2745 | 109 | ||||||||
AL03 (2500LM) | 32 | 3069 | 98 | 3140 | 99 | 3214 | 101 | 3314 | 103 | ||||||||
AL03 (3000LM) | 38 | 3485 | 93 | 3566 | 94 | 3651 | 96 | 3764 | 98 | ||||||||
AL04 (4000LM) | 39 | 4094 | 106 | 4178 | 108 | 4262 | 110 | 4303 | 111 | ||||||||
AL04 (4500LM) | 44 | 4519 | 103 | 4611 | 105 | 4703 | 107 | 4749 | 108 | ||||||||
AL04 (5000LM) | 49 | 4915 | 100 | 5015 | 102 | 5115 | 104 | 5165 | 105 | ||||||||
LBR4 MS MWD | |||||||||||||||||
AL01 (500LM) | 6 | 479 | 83 | 490 | 85 | 502 | 87 | 517 | 89 | ||||||||
AL01 (750LM) | 9 | 758 | 85 | 776 | 87 | 794 | 89 | 819 | 92 | ||||||||
AL01 (1000LM) | 13 | 1065 | 82 | 1089 | 84 | 1115 | 86 | 1150 | 89 | ||||||||
AL02 (1000LM) | 13 | 1129 | 90 | 1155 | 92 | 1182 | 95 | 1219 | 98 | ||||||||
AL02 (1500LM) | 19 | 1648 | 87 | 1686 | 89 | 1726 | 91 | 1779 | 94 | ||||||||
AL02 (2000LM) | 25 | 2075 | 83 | 2124 | 85 | 2174 | 87 | 2241 | 90 | ||||||||
AL03 (2000LM) | 25 | 2135 | 86 | 2185 | 88 | 2237 | 90 | 2306 | 93 | ||||||||
AL03 (2500LM) | 32 | 2578 | 82 | 2638 | 83 | 2700 | 85 | 2784 | 88 | ||||||||
AL03 (3000LM) | 38 | 2927 | 78 | 2995 | 79 | 3066 | 81 | 3162 | 84 | ||||||||
AL04 (4000LM) | 39 | 3439 | 89 | 3510 | 91 | 3580 | 92 | 3615 | 93 | ||||||||
AL04 (4500LM) | 44 | 3796 | 86 | 3873 | 88 | 3951 | 90 | 3989 | 91 | ||||||||
AL04 (5000LM) | 49 | 4128 | 84 | 4213 | 85 | 4297 | 87 | 4339 | 88 |
Notes:
- Tested in accordance with IESNA LM-79-08.
- Tested to current IES and NEMA standards under stabilized laboratory conditions.
- CRI: 80 typical
Items marked with a shaded background qualify for the Design Select program and ship in 15 days or less. Visit www.acuitybrands.com/designselect for more information.
Diagram: The product is a cylindrical LED downlight fixture with a trim. Two main trim styles are shown: 'Open Trim' and 'Wallwash Trim'.
Module Ordering
Lead times will vary depending on options selected. Consult with your sales representative.
Example: LBR4 ALO2 SWW1 AR LSS MWD MVOLT UGZ 90CRI
Series | Lumens | Color Temperature | Reflector Color | Reflector Flange | Reflector Finish | Distribution | Voltage | Driver | Emergency | Control Input | Options |
---|---|---|---|---|---|---|---|---|---|---|---|
LBR4 4" Retrofit | Adjustable Lumen Output: ALO1 500/750/1000lm ALO2 1000/1500/2000lm ALO3 2000/2500/3000lm ALO4 4000/4500/5000lm Fixed Lumen Output: 05LM 500lm 07LM 750lm 10LM 1000lm 15LM 1500lm 20LM 2000lm 25LM 2500lm 30LM 3000lm 40LM 4000lm 45LM 4500lm 50LM 5000lm | Switchable CCT: SWW1 3000K-3500K-4000K-5000K Fixed CCT: 27K 2700K 30K 3000K 35K 3500K 40K 4000K 50K 5000K | AR Clear BR Black painted MS Metallic Silver WR White painted TCPC Custom painted trim | (blank) Self-flanged TRW White painted flange TRBL Black painted flange FCPC Custom painted flange FRALTBD RAL painted flange only | LSS Semi-specular | MWD Medium wide (1.0 s/mh) WD Wide (1.2s/mh) WW Wallwash | MVOLT 120 277 347 | UGZ Universal dimming to 10% 0-10V; line voltage dimming (120V) UGZ1 Universal dimming to 1% 0-10V; line voltage dimming (120V) DALI DALI dimming to 1% D1 Minimum dimming 1% driver for use with JOT | (blank) No Emergency Needed ELR Battery pack (10W constant power) Non-T20 Compliant remote test switch ETS Iota Emergency Transfer System E10WCP Battery pack (10W constant power) T20 Compliant integral test switch E10WCPR Battery pack (10W constant power) T20 Compliant remote test switch E10WRSTAR Emergency battery pack, 10W with remote test switch and Iota STAR technology | (blank) No Control Input Needed JOT Wireless room control with "Just One Touch" pairing NLIGHT Embedded wired controls from nLight NLIGHTER Embedded wired controls from nLight with UL924 listed emergency operation NLTAIR2 nLight® Air enabled NLTAIREM2 nLight® AIR Dimming Pack Wireless Controls. UL924 Emergency Operation, via power interrupt detection. | 90CRI High CRI (90+) AT Airtight EC1 Extended Conduit (18") EC6 Extended Conduit (6ft) WL Wet Location (IP55) QDS Quick disconnect plugs CP Chicago Plenum |
LBR4WW 4" Retrofit Wallwash | MS, WR, BR | WW |
Option Value Ordering Restrictions
Restriction | Details |
---|---|
Adjustable Lumen Output and Switchable CCT | Must be specified together (e.g., ALO1 SWW1) |
Fixed Lumen Output and Fixed CCT | Must be specified together (e.g., 10LM 30K) |
Not available with WL, EL, E10WCP | |
Not available with LSS reflector finish | |
Not available with TRW | |
Not available with TRBL | |
RALTBD, FRALTBD | For pricing only. Replace with applicable RAL number and finish when ready to order. See the RAL BROCHURE for available color options. Not available with TCPC or FCPC. |
TCPC, FCPC | For pricing only. Custom color chip needs to be sent in to your Customer Resolution specialist before order can be processed. Click HERE for more details. Not available with TRAL or FRAL. |
TRW, TRBL | Available with MS and AR reflectors only. |
LSS | Not available with BR or WR or MS |
347V | Not available with CP, QDS, ELR, E10WCP, E10WCPR, NLIGHT, NLIGHTER, NLTAIR2, or NLTAIREM2 |
DALI | Not available with fixed lumens or CCT. Max 4500 lumens. |
E10WCPR | Not available with EC1, EC6, AT, QDS, CP, 347V, NLIGHTER, NLTAIREM2, WL, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT. |
E10WCP | Not available with WW, EC1, EC6, AT, QDS, CP, 347V, NLIGHTER, NLTAIREM2, WL, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT. |
E10WRSTAR | Not available with wet location, EC1, EC6, QDS, CP, 347V, NLIGHTER, NLTAIREM2, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT. Top access installation or 17.5" plenum clearance required for roomside installation. Not available with integral test switch |
ELR | Not available EC1, EC6, QDS, CP, 347V, NLIGHTER, NLTAIREM2, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT. |
ETS | Not available with, QDS, ELR, E10WCP, E10WCPR, 347V, JOT, NLIGHT, NLIGHTER, NLTAIR2, NLTAIREM2, DALI, or D1 driver |
JOT | Only available with D1 driver. Not availabe with CP, NLIGHT, NLIGHTER, NLTAIR2, NLTAIREM2, UGZ, or DALI drivers. Max 4500 lumens. Fixed lumens and CCT only. Not available with 2000-4500lm in conjunction with emergency batterypacks. |
NLIGHT | Must specify UGZ1. Not available with CP, QDS, JOT, ETS, UGZ, DALI, or D1 drivers. Not available with 347V. |
NLIGHTER | Must specify UGZ1. Not available with CP, QDS, ELR, E10WCP, E10WCPR, DALI, or D1 drivers. Not available with 347V. |
NLTAIR2 | Must specify UGZ1. Not available with CP, QDS, JOT, ETS, UGZ, DALI, or D1 drivers. See UL 924 Sequence of Operation table. Non-emergency luminaires with this option can be used as a normal power sensing device for nLight AIR devices and luminaires with EM emergency options. Not available with 347V. |
NLTAIREM2 | Must specify UGZ1. Not available with CP, QDS, JOT, ETS, ELR, E10WCP, E10WCPR, DALI, D1 drivers. See UL 924 Sequence of Operation table. |
WL | Not available with WW, All CP is wet location, except WW (Damp). IP55 rated. Not available with E10WCP |
QDS | Must be specified for use with LBR_PFWQDS. Not Available with CP, emergency options, or 347V. |
EC1, EC6 | Not Available with CP,QDS, ELR, E10WCP, or E10WCPR. |
AT | Standard for CP and IP55, not availabe with WW. Not available with E10WCP |
CP | Not available with, QDS, EC1, EC6, ELR, E10WCPR, 347V, JOT, NLTAIR2, NLTAIREM2, D1 drivers. For new construction applications, must be specified with LBR_PFWCP. |
Accessories
Order as separate catalog number. Shipped separately.
- LBRGR56**: Goof ring 5-3/4" to 6-3/4" for LBR4 (** specify BR or WR)
- LBRCPGR56**: Chicago Plenum Goof ring 5-3/4" to 6-3/4" for LBR4
- LBRO4 AR LSS TRIM: 4" clear, semi-specular reflector
- LBRO4 ** TRIM: 4" reflector (** specify MS, WR, BR)
- LBRW4 AR LSS TRIM: 4" clear, semi-specular wallwash
- LBRW4 ** TRIM: 4" wallwash (** specify MS, WR, BR)
- LBR46810HB FPAN U: Mounting plate 4"-10" unit pack
- LBR46810HB FPAN J10: Mounting plate 4"-10" 10-pack
- LBR SDT 347V 75W ASM: Field installed 347V Step-down transformer
- SCA4: Sloped Ceiling Adapter. Degree of slope must be specified (5D, 10D, 15D, 20D, 25D, 30D). Ex: SCA4 10D.
Mounting Frame Accessory Compatibility
Module | Mounting Frame Accessory | Compatible Fixture Options |
---|---|---|
LBR4 | LBR4PF | Base fixture only |
LBR4PFW | QDS, EC1, EC6, ELR, E10WCPR, E10WCP, E10WRSTAR | |
LBR4PFW EM | ||
LBR4PFWQDS | QDS fixture only | |
LBR4WW | LBR4PF | Base fixture only |
LBR4PFW | QDS, EC1, EC6, ELR, E10WCPR, E10WRSTAR | |
LBR4PFW EM | ||
LBR4PFWQDS | QDS fixture only |
Emergency Battery Pack Options - Field Installable
Battery Model Number | Wattage | Runtime (Minutes) | Lumen Output* @ 120 Lumens/Watt | Other |
---|---|---|---|---|
ILB CP07 2H A | 7W | 120 | 840 | Storm Shelter / 2 Hour Runtime |
ILB CP10 A | 10W | 90 | 1200 | |
ILBLP CP10 HE SD A+ | 10W | 90 | 1200 | Title 20, Self Diagnostic |
ILBLP CP15 HE SD A+ | 15W | 90 | 1800 | Title 20, Self Diagnostic |
ILB CP20 HE A | 20W | 90 | 2400 | Title 20 |
ILB CP20 HE SD A | 20W | 90 | 2400 | Title 20, Self Diagnostic |
ILBHI CP10 HE SD A+ | 10W | 90 | 1200 | 347-480V AC Input, Title 20, Self Diagnostic |
ILBHI CP15 HE SD A+ | 15W | 90 | 1800 | 347-480V AC Input, Title 20, Self Diagnostic |
*Minimum delivered lumen output to assist in product selection for increased fixture mounting height.
Please contact techsupport@iotaengineering.com for any Emergency Battery related questions.
Dimensional Data
Plenum Depth Table
Aperture Size/Output | Plenum Depth* | IC | Non-IC | Non-IC Marked Spacing |
---|---|---|---|---|
LBR4 500-1000 Lumen | 3.44 | X | ||
LBR4 1000-2000 Lumen | 3.44 | X | ||
LBR4 2000-3000 Lumen | - | X | 24x24x9 | |
LBR4 4000-5000 Lumen | - | X | 24x24x9 |
*Above unfinished 1/2" ceiling plane.
Ceiling Coverage Table
Series | Trim | Aperture Flange OD | Min ceiling opening | Ceiling Thickness | Max ceiling opening | Max Ceiling Opening with Goof Ring | Overall Goof Ring OD |
---|---|---|---|---|---|---|---|
LBR4 ROUND | 4-1/4" | 5-7/16" | 4-1/2" | 1/2" - 1-1/2" | 5-1/8" | 5-1/8" | 7-1/4" |
LBR4 | 5-3/4" |
*All dimensions are inches (millimeters) unless otherwise noted.
Diagrams: Multiple diagrams illustrate the fixture's physical dimensions and mounting configurations. These include cross-sections showing the internal components, overall fixture dimensions, and how the mounting frame and trim attach. Specific diagrams show configurations for MVOLT UGZ, MVOLT DALI, MVOLT UGZ QDS, MVOLT UGZ EC1, and MVOLT UGZ ELR options, detailing their respective wiring and component placements. Another diagram shows the LBR4PFWCP configuration with detailed measurements.
Photometry
The following data presents photometric performance for specific configurations.
Configuration | Input Watts | Delivered Lumens | LPW | S/MH | Test No. |
---|---|---|---|---|---|
LBR4 SWW1 ALO2 AR LSS MWD MVOLT UGZ | 18.1 | 1929 | 106.6 | 0.98 | 20-518-01 |
LBR4WW SWW1 ALO2 AR LSS WW MVOLT UGZ | 18.1 | 1922 | 106.2 | 0.73 | 20-518-02 |
Diagrams: Photometric distribution curves are shown for two specific models (LBR4 SWW1 ALO2 AR LSS MWD MVOLT UGZ and LBR4WW SWW1 ALO2 AR LSS WW MVOLT UGZ). These plots illustrate the light intensity distribution in candelas per square meter (cd/sq.m) at various angles (0° to 90°). Zonal Lumen Summary tables break down the percentage of total lumens emitted within specific angular zones (e.g., 0°-30°, 0°-40°). Cone of Light data provides illuminance (FC) and beam diameter at different mounting heights. Average Luminance data is also presented.
Lumen Output Multipliers
CCT | 3000K | 3500K | 4000K | 5000K |
---|---|---|---|---|
Multiplier | 0.98 | 1.0 | 1.01 | 1.03 |
Finish | Multiplier |
---|---|
Clear Semi-spec (AR LSS) | 1.0 |
Metallic Silver (MS) | 0.84 |
White Painted (WR) | 1.03 |
Black Painted (BR) | 0.60 |
CRI | Multiplier |
---|---|
80 | 1.0 |
90 | 0.874 |
How to Estimate Delivered Lumens in Emergency Mode
Use the formula: Delivered Lumens = 1.25 x P x LPW, where P is the output power of the emergency driver (e.g., 10W for PS1055CP) and LPW is the lumen per watt rating of the luminaire.
Dimmer Compatibility
Not compatible with DALI or DMX dimmers. For specific compatible dimmers, see tables below.
Line Voltage Dimming
Type | Forward Phase | ALO1 (500-1000lm) | ALO2 (1000-2000lm) | ALO3 (2000-3000lm) | ALO4 (3000-5000lm) | Comment |
---|---|---|---|---|---|---|
MLV | Sensorswitch WPD | YES | YES | YES | YES | |
MLV | Sensorswitch CMR PDT10 ADC VLP | YES | YES | YES | YES | |
MLV | Synergy ISD 600LV | YES, 2x * | YES | YES | YES | * min 2 fixtures |
INC | Synergy ISD 600 I | YES, 2x * | YES | YES | YES | * min 2 fixtures |
MLV | Lutron Glyder GLV-600 | YES | YES | YES | YES | |
INC | Leviton SureSlide 6633 | YES | YES | YES | YES | |
MLV | Lutron Diva DVLV-600P | YES | YES | YES | YES | |
MLV | Lutron Skylark SLV-600P | YES | YES | YES | YES | |
INC | Lutron RadioRA 2 10ND | YES | YES | YES | YES | |
MLV | Leviton SureSlide 6613-PLW | YES | YES | YES | YES | |
INC | Lutron Diva DVCL-153P | YES | YES | YES | YES | |
MLV | Leviton IPM06 | YES, 2x * | YES | YES | YES | * min 2 fixtures |
INC | Leviton IP106 | YES, 2x * | YES | YES | YES | * min 2 fixtures |
INC | Control4 C4-FPD 120 | YES | YES | YES | YES |
Reverse Phase Dimmer Bank
Type | ALO1 (500-1000lm) | ALO2 (1000-2000lm) | ALO3 (2000-3000lm) | ALO4 (3000-5000lm) | |
---|---|---|---|---|---|
ELV | Lutron Nova T NTELV-600 | YES | YES | YES | YES |
ELV | Lutron Diva DVELV 600P | YES | YES | YES | YES |
ELV | Lutron Maestro MAELV 600 | YES | YES | YES | YES |
ELV | Leviton Vizia VPE06-1LX | YES | YES | YES | YES |
ELV | Leviton Illumatech IPE04 | YES | YES | YES | YES |
ELV | Control4 C4-APD 120 REVERSE PHASE | YES | YES | YES | YES |
Miscellaneous Dimmers
Type | ALO1 (500-1000lm) | ALO2 (1000-2000lm) | ALO3 (2000-3000lm) | ALO4 (3000-5000lm) | |
---|---|---|---|---|---|
PHA | Lutron RadioRA2 RRD-6NA | YES | YES | YES | YES |
PHA | Lutron Maestro PRO LED+ RRD-PRO | YES | YES | YES | YES |
Control Systems
Type | ALO1 (500-1000lm) | ALO2 (1000-2000lm) | ALO3 (2000-3000lm) | ALO4 (3000-5000lm) | |
---|---|---|---|---|---|
MLV | Lutron LP-RPM-4U | YES | YES | YES | YES |
PHA | Lutron LP-RPM-4A | YES | YES | YES | YES |
MLV | Lutron GRAPHIC EYE QSGRJ-3P | YES | YES | YES | YES |
PHA | Lutron PA Power Module PHPM-PA-120 | YES | YES | YES | YES |
ELV | Lutron nLight nSP5PCD ELV | YES | YES | YES | YES |
0-10V Dimming Compatibility
Manufacturer | System Type | Description | P/N | ALO1 (500-1000lm) | ALO2 (1000-2000lm) | ALO3 (2000-3000lm) | ALO4 (3000-5000lm) |
---|---|---|---|---|---|---|---|
ACUITY | Wall Box | sensorswitch, dimming switch with multi-way option | SPODMRA | YES | YES | YES | YES |
ACUITY | Wall Box | sensorswitch, wall switch sensor, occupancy controlled dimming | WSX D WH | YES | YES | YES | YES |
ACUITY | Control System | nLight | nPP16D | YES | YES | YES | YES |
ACUITY | Control System | nLight | nPS 80 EZ | YES | YES | YES | YES |
ACUITY | Control System | nLight Air | rPP20 D | YES | YES | YES | YES |
Lutron | Other | 0-10V (sink or source) PowPak wireless dimming module | RMJ-5T-DV-B | YES | YES | YES | YES |
WattStopper | Control System | Digital single relay room controller (0-10V) | LMRC-211 | YES | YES | YES | YES |
Crestron | Control System | DIN Rail 0-10V fluorescent dimmer, 4 feeds, 4 channels (Green Light System) | DIN-4DIMFLV4 | YES | YES | YES | YES |
Lutron | Other | Grafik Eye 0-10V adapter | GRX-TVI | YES | YES | YES | YES |
Leviton | Wall Box | Illumatech 0-10V | IP710-DLX | YES | YES | YES | YES |
Lutron | Control System | Mounted in the Homeworks QS panel - 0-10V dimmer (sink or source) | GRX-TVM2 | YES | YES | YES | YES |
Lutron | Wall Box | Nova 0-10V wallbox dimmer (use with PP-120-H line voltage relay) | NTFTV | YES | YES | YES | YES |
Lutron | Wall Box | Nova 0-10V wallbox dimmer (use with PP-120-H line voltage relay) | NTSTV-DV | YES | YES | YES | YES |
Lutron | Wall Box | Nova T | NFTV | YES | YES | YES | YES |
Leviton | Wall Box | Renior II 0-10V | AWSMG-7DW | YES | YES | YES | YES |
Additional Data: JOT (Just One Touch)
The Sensor Switch JOT enabled solution offers a wireless, app-free approach to single room lighting control. JOT enabled products use Bluetooth® Low Energy (BLE) technology to enable wireless dimming and switching.
Diagram: Illustrates the JOT system setup: 1. Install JOT enabled fixtures and controls. 2. Pair by inserting the pairing tool into the wall switch pinhole and holding any button for 6 seconds. 3. Play: After pairing, fixtures dim to 10% brightness, and all products become fully functional.
Compatible 0-10V Wall-Mount Dimmers
MANUFACTURER | PART NO. | POWER BOOSTER AVAILABLE | |
---|---|---|---|
Lutron® | Diva® DVTV | CN100 | |
Diva® DVSCTV | PE300 | ||
Nova T® NTFTV | |||
Nova® NFTV | |||
Leviton® | AWSMT-7DW | ||
AWSMG-7DW | |||
AMRMG-7DW | |||
Leviton Centura Fluorescent Control System | |||
IllumaTech® IP7 Series | |||
Synergy® | ISD BC | ||
SLD LPCS | |||
RDMFC | |||
Douglas Lighting Controls | Digital Equinox (DEQ BC) | WPC-5721 | |
Entertainment Technology | Tap Glide TG600FAM120 (120V) | ||
Tap Glide Heatsink TGH1500FAM120 (120V) | |||
Oasis 0A2000FAMU | |||
Honeywell | EL7305A1010 (optional) | ||
EL7315A1019 | |||
EL7315A1009 | |||
HUNT Dimming | Preset slide: PS-010-IV and PS-010-WH | ||
Preset slide: PS-010-3W-IV and PS-010-3W-WH | |||
Preset slide, controls FD-010: PS-IFC-010-IV and PS-IFC-010-WH-120/277V | |||
Preset slide, controls FD-010: PS-IFC-010-3W-IV and PS-IFC-010-3W-WH-120/277V | |||
Remote mounted unit: FD-010 | |||
Lehigh Electronic Products | Solitaire | PBX | |
PDM Electrical Products | WPC-5721 | ||
Starfield Controls | TR61 with DALI interface port | ||
WattStopper® | LS-4 used with LCD-101 and LCD-103 |
Control System Integration
Example Diagram: Shows a 'Group Fixture Control' application diagram for fixtures with eldoLED drivers. It illustrates wiring for nPS 80 EZ Dimming/Control Packs, nPODM 2P DX Push-Button WallPod, nCM ADCX Daylight Sensor, and nCM PDT 9 Occupancy Sensor. The description explains how this setup enables manual control of fixtures in separate rows (A and B), incorporates daylight harvesting for Row B, and uses an occupancy sensor to turn off all lights when the space is vacant.
Wiring Key: CAT-5e Cable, Line Power, Low Voltage Dimming Wires.
Choose Wall Controls: nLight offers various wall controls with different features and user experiences, including Push-Button Wallpods and Graphic Wallpods.
nLight® Wired Controls Accessories
Order as separate catalog number. Visit www.acuitybrands.com/products/controls/nlight for a complete listing.
WallPod Stations | Model number | Occupancy sensors | Model Number |
---|---|---|---|
On/Off | nPODM (Color) | Small motion 360°, ceiling (PIR/dual Tech) | nCM 9 / nCM PDT 9 |
On/Off & Raise/Lower | nPOD DX (Color) | Large motion 360°, ceiling (PIR/dual tech) | nCM 10 / nCM PDT 10 |
Graphic Touchscreen | nPOD GFX (Color) | Wide View (PIR/dual tech) | nWV 16 / nWV PDT 16 |
Photocell controls | Model Number | Wall Switch w/ Raise/Lower (PIR/dual tech) | nWSX LV DX / nWSX PDT LV DX |
Dimming | nCM ADCX | ||
Cat-5 cables (plenum rated) | Model Number | ||
10', CAT5 10FT | CAT5 10FT J1 | ||
15', CAT5 15FT | CAT5 15FT J1 |
nLight® AIR Control Accessories
Order as separate catalog number. Visit www.acuitybrands.com/products/controls/nlightair.
Wall switches | Model number |
---|---|
On/Off single pole | rPODB [color] |
On/Off two pole | rPODB 2P [color] |
On/Off & raise/lower single pole | rPODB DX [color] |
On/Off & raise/lower two pole | rPODB 2P DX [color] |
On/Off & raise/lower single pole | rPODBZ DX WH¹ |
Notes:
- ¹ Can only be ordered with the RES7Z zone control sensor version.
UL924 Sequence of Operation
For nLight AIR devices with an EM option:
- EM devices remain at their high-end trim and ignore wireless lighting control commands unless a normal-power-sensed (NPS) broadcast is received at least every 8 seconds.
- Using the CLAIRITY+ mobile app, EM devices must be associated with a group including a normal power sensing device to receive NPS broadcasts.
- Only non-emergency rPP20, rLSXR, rSBOR, rSDGR, and nLight AIR luminaires with version 3.4 or later firmware can provide normal power sensing for EM devices.
nLight AIR System
nLight AIR is ideal for retrofit or new construction spaces where communication is cost-prohibitive. The integrated nLight AIR rPP20 Power Pack is part of each Lithonia LDN Luminaire, offering individually addressable controls for flexibility.
Simple Setup:
- Install nLight® AIR fixtures with embedded smart sensor.
- Install the wireless battery-powered wall switch.
- Use the CLAIRITY app to pair fixtures with the wall switch and customize sensor settings.
Diagram: Shows the nLight AIR setup with a fixture, a wireless wall switch (rPODB 2P DX), and a mobile device for the CLAIRITY app.