Lithonia Lighting LBR4 Series: 4" Open and Wallwash LED Retrofit/Remodel Downlight

Features & Specifications

Intended Use

Typical applications include corridors, lobbies, conference rooms, and private offices.

Construction

Retrofit, remodel, and new construction mounting types. See table for compatible ceiling openings and thickness range. Optional goof rings available for additional overlap trim coverage. Supports 1/2"-1-1/2" ceiling thickness. Rated for 25°C ambient temperature. IC rated up to 1000lm.

Optics

LEDs are binned to a 3-step Mac Adam Ellipse with a 55° cutoff. New construction frame accessories approved for 8 (4 in/4 out) No. 12 AWG conductors rated for 90°C through wiring. Available in 80CRI standard (90CRI optional). UGR is zero for fixtures aimed at nadir with a cut-off equal to or less than 60deg, per CIE 117-1996.

Electrical

Features adjustable lumen output with four module options; fixed lumen options also available. MVOLT (120/277V, 50/60Hz) driver supports 0-10V and 120V Phase Dimming down to 10% or 1% minimum dimming level. Complies with FCC CFR Title 47 Part 15 Class A for 277V and Class B for 120V.

Lumen Maintenance

L80 at 60,000 hours.

Listings

Certified to US and Canadian safety standards. Damp location standard (Wet Location (WL) optional, requires covered ceiling). TAA compliant. UFC (3-530-01) specification compliant for power factor and THD. GSA P100 6.2.4 compliant for power quality at full output; compliant up to 2000lm at fully dimmed output. Drivers are ROHS compliant. Title 24 compliant (90CRI, up to 1000lm).

Warranty

5-year limited warranty. For complete terms, visit www.acuitybrands.com/support/warranty/terms-and-conditions.

Note on Performance

Actual performance may differ based on end-user environment and application. All values are design or typical, measured under laboratory conditions at 25°C. Specifications are subject to change without notice.

Performance Data

Data for LBR4 AR LSS MWD and LBR4 MS MWD models.

Lumen OutputWattage30K/80CRI35K/80CRI40K/80CRI50K/80CRI
Delivered LumensLPWDelivered LumensLPWDelivered LumensLPWDelivered LumensLPW
LBR4 AR LSS MWD
AL01 (500LM)657099584101597102616105
AL01 (750LM)9903102924103946105975108
AL01 (1000LM)13126898129710013281021369104
AL02 (1000LM)131344108137511014081121451115
AL02 (1500LM)191961105200710620551082118111
AL02 (2000LM)25247199252810125881032668105
AL03 (2000LM)252542103260110426631062745109
AL03 (2500LM)3230699831409932141013314103
AL03 (3000LM)38348593356694365196376498
AL04 (4000LM)394094106417810842621104303111
AL04 (4500LM)444519103461110547031074749108
AL04 (5000LM)494915100501510251151045165105
LBR4 MS MWD
AL01 (500LM)647983490855028751789
AL01 (750LM)975885776877948981992
AL01 (1000LM)13106582108984111586115089
AL02 (1000LM)13112990115592118295121998
AL02 (1500LM)19164887168689172691177994
AL02 (2000LM)25207583212485217487224190
AL03 (2000LM)25213586218588223790230693
AL03 (2500LM)32257882263883270085278488
AL03 (3000LM)38292778299579306681316284
AL04 (4000LM)39343989351091358092361593
AL04 (4500LM)44379686387388395190398991
AL04 (5000LM)49412884421385429787433988

Notes:

  • Tested in accordance with IESNA LM-79-08.
  • Tested to current IES and NEMA standards under stabilized laboratory conditions.
  • CRI: 80 typical

Items marked with a shaded background qualify for the Design Select program and ship in 15 days or less. Visit www.acuitybrands.com/designselect for more information.

Diagram: The product is a cylindrical LED downlight fixture with a trim. Two main trim styles are shown: 'Open Trim' and 'Wallwash Trim'.

Module Ordering

Lead times will vary depending on options selected. Consult with your sales representative.

Example: LBR4 ALO2 SWW1 AR LSS MWD MVOLT UGZ 90CRI

SeriesLumensColor TemperatureReflector ColorReflector FlangeReflector FinishDistributionVoltageDriverEmergencyControl InputOptions
LBR4
4" Retrofit
Adjustable Lumen Output:
ALO1 500/750/1000lm
ALO2 1000/1500/2000lm
ALO3 2000/2500/3000lm
ALO4 4000/4500/5000lm
Fixed Lumen Output:
05LM 500lm
07LM 750lm
10LM 1000lm
15LM 1500lm
20LM 2000lm
25LM 2500lm
30LM 3000lm
40LM 4000lm
45LM 4500lm
50LM 5000lm
Switchable CCT:
SWW1 3000K-3500K-4000K-5000K
Fixed CCT:
27K 2700K
30K 3000K
35K 3500K
40K 4000K
50K 5000K
AR Clear
BR Black painted
MS Metallic Silver
WR White painted
TCPC Custom painted trim
(blank) Self-flanged
TRW White painted flange
TRBL Black painted flange
FCPC Custom painted flange
FRALTBD RAL painted flange only
LSS Semi-specularMWD Medium wide (1.0 s/mh)
WD Wide (1.2s/mh)
WW Wallwash
MVOLT 120
277
347
UGZ Universal dimming to 10% 0-10V; line voltage dimming (120V)
UGZ1 Universal dimming to 1% 0-10V; line voltage dimming (120V)
DALI DALI dimming to 1%
D1 Minimum dimming 1% driver for use with JOT
(blank) No Emergency Needed
ELR Battery pack (10W constant power) Non-T20 Compliant remote test switch
ETS Iota Emergency Transfer System
E10WCP Battery pack (10W constant power) T20 Compliant integral test switch
E10WCPR Battery pack (10W constant power) T20 Compliant remote test switch
E10WRSTAR Emergency battery pack, 10W with remote test switch and Iota STAR technology
(blank) No Control Input Needed
JOT Wireless room control with "Just One Touch" pairing
NLIGHT Embedded wired controls from nLight
NLIGHTER Embedded wired controls from nLight with UL924 listed emergency operation
NLTAIR2 nLight® Air enabled
NLTAIREM2 nLight® AIR Dimming Pack Wireless Controls. UL924 Emergency Operation, via power interrupt detection.
90CRI High CRI (90+)
AT Airtight
EC1 Extended Conduit (18")
EC6 Extended Conduit (6ft)
WL Wet Location (IP55)
QDS Quick disconnect plugs
CP Chicago Plenum
LBR4WW
4" Retrofit Wallwash
MS, WR, BRWW

Option Value Ordering Restrictions

RestrictionDetails
Adjustable Lumen Output and Switchable CCTMust be specified together (e.g., ALO1 SWW1)
Fixed Lumen Output and Fixed CCTMust be specified together (e.g., 10LM 30K)
Not available with WL, EL, E10WCP
Not available with LSS reflector finish
Not available with TRW
Not available with TRBL
RALTBD, FRALTBDFor pricing only. Replace with applicable RAL number and finish when ready to order. See the RAL BROCHURE for available color options. Not available with TCPC or FCPC.
TCPC, FCPCFor pricing only. Custom color chip needs to be sent in to your Customer Resolution specialist before order can be processed. Click HERE for more details. Not available with TRAL or FRAL.
TRW, TRBLAvailable with MS and AR reflectors only.
LSSNot available with BR or WR or MS
347VNot available with CP, QDS, ELR, E10WCP, E10WCPR, NLIGHT, NLIGHTER, NLTAIR2, or NLTAIREM2
DALINot available with fixed lumens or CCT. Max 4500 lumens.
E10WCPRNot available with EC1, EC6, AT, QDS, CP, 347V, NLIGHTER, NLTAIREM2, WL, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT.
E10WCPNot available with WW, EC1, EC6, AT, QDS, CP, 347V, NLIGHTER, NLTAIREM2, WL, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT.
E10WRSTARNot available with wet location, EC1, EC6, QDS, CP, 347V, NLIGHTER, NLTAIREM2, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT. Top access installation or 17.5" plenum clearance required for roomside installation. Not available with integral test switch
ELRNot available EC1, EC6, QDS, CP, 347V, NLIGHTER, NLTAIREM2, ALO3 & ALO4 w/DALI, OR 2000-4500 lumens w/JOT.
ETSNot available with, QDS, ELR, E10WCP, E10WCPR, 347V, JOT, NLIGHT, NLIGHTER, NLTAIR2, NLTAIREM2, DALI, or D1 driver
JOTOnly available with D1 driver. Not availabe with CP, NLIGHT, NLIGHTER, NLTAIR2, NLTAIREM2, UGZ, or DALI drivers. Max 4500 lumens. Fixed lumens and CCT only. Not available with 2000-4500lm in conjunction with emergency batterypacks.
NLIGHTMust specify UGZ1. Not available with CP, QDS, JOT, ETS, UGZ, DALI, or D1 drivers. Not available with 347V.
NLIGHTERMust specify UGZ1. Not available with CP, QDS, ELR, E10WCP, E10WCPR, DALI, or D1 drivers. Not available with 347V.
NLTAIR2Must specify UGZ1. Not available with CP, QDS, JOT, ETS, UGZ, DALI, or D1 drivers. See UL 924 Sequence of Operation table. Non-emergency luminaires with this option can be used as a normal power sensing device for nLight AIR devices and luminaires with EM emergency options. Not available with 347V.
NLTAIREM2Must specify UGZ1. Not available with CP, QDS, JOT, ETS, ELR, E10WCP, E10WCPR, DALI, D1 drivers. See UL 924 Sequence of Operation table.
WLNot available with WW, All CP is wet location, except WW (Damp). IP55 rated. Not available with E10WCP
QDSMust be specified for use with LBR_PFWQDS. Not Available with CP, emergency options, or 347V.
EC1, EC6Not Available with CP,QDS, ELR, E10WCP, or E10WCPR.
ATStandard for CP and IP55, not availabe with WW. Not available with E10WCP
CPNot available with, QDS, EC1, EC6, ELR, E10WCPR, 347V, JOT, NLTAIR2, NLTAIREM2, D1 drivers. For new construction applications, must be specified with LBR_PFWCP.

Accessories

Order as separate catalog number. Shipped separately.

  • LBRGR56**: Goof ring 5-3/4" to 6-3/4" for LBR4 (** specify BR or WR)
  • LBRCPGR56**: Chicago Plenum Goof ring 5-3/4" to 6-3/4" for LBR4
  • LBRO4 AR LSS TRIM: 4" clear, semi-specular reflector
  • LBRO4 ** TRIM: 4" reflector (** specify MS, WR, BR)
  • LBRW4 AR LSS TRIM: 4" clear, semi-specular wallwash
  • LBRW4 ** TRIM: 4" wallwash (** specify MS, WR, BR)
  • LBR46810HB FPAN U: Mounting plate 4"-10" unit pack
  • LBR46810HB FPAN J10: Mounting plate 4"-10" 10-pack
  • LBR SDT 347V 75W ASM: Field installed 347V Step-down transformer
  • SCA4: Sloped Ceiling Adapter. Degree of slope must be specified (5D, 10D, 15D, 20D, 25D, 30D). Ex: SCA4 10D.

Mounting Frame Accessory Compatibility

ModuleMounting Frame AccessoryCompatible Fixture Options
LBR4LBR4PFBase fixture only
LBR4PFWQDS, EC1, EC6, ELR, E10WCPR, E10WCP, E10WRSTAR
LBR4PFW EM
LBR4PFWQDSQDS fixture only
LBR4WWLBR4PFBase fixture only
LBR4PFWQDS, EC1, EC6, ELR, E10WCPR, E10WRSTAR
LBR4PFW EM
LBR4PFWQDSQDS fixture only

Emergency Battery Pack Options - Field Installable

Battery Model NumberWattageRuntime (Minutes)Lumen Output* @ 120 Lumens/WattOther
ILB CP07 2H A7W120840Storm Shelter / 2 Hour Runtime
ILB CP10 A10W901200
ILBLP CP10 HE SD A+10W901200Title 20, Self Diagnostic
ILBLP CP15 HE SD A+15W901800Title 20, Self Diagnostic
ILB CP20 HE A20W902400Title 20
ILB CP20 HE SD A20W902400Title 20, Self Diagnostic
ILBHI CP10 HE SD A+10W901200347-480V AC Input, Title 20, Self Diagnostic
ILBHI CP15 HE SD A+15W901800347-480V AC Input, Title 20, Self Diagnostic

*Minimum delivered lumen output to assist in product selection for increased fixture mounting height.

Please contact techsupport@iotaengineering.com for any Emergency Battery related questions.

Dimensional Data

Plenum Depth Table

Aperture Size/OutputPlenum Depth*ICNon-ICNon-IC Marked Spacing
LBR4 500-1000 Lumen3.44X
LBR4 1000-2000 Lumen3.44X
LBR4 2000-3000 Lumen-X24x24x9
LBR4 4000-5000 Lumen-X24x24x9

*Above unfinished 1/2" ceiling plane.

Ceiling Coverage Table

SeriesTrimAperture Flange ODMin ceiling openingCeiling ThicknessMax ceiling openingMax Ceiling Opening with Goof RingOverall Goof Ring OD
LBR4 ROUND4-1/4"5-7/16"4-1/2"1/2" - 1-1/2"5-1/8"5-1/8"7-1/4"
LBR45-3/4"

*All dimensions are inches (millimeters) unless otherwise noted.

Diagrams: Multiple diagrams illustrate the fixture's physical dimensions and mounting configurations. These include cross-sections showing the internal components, overall fixture dimensions, and how the mounting frame and trim attach. Specific diagrams show configurations for MVOLT UGZ, MVOLT DALI, MVOLT UGZ QDS, MVOLT UGZ EC1, and MVOLT UGZ ELR options, detailing their respective wiring and component placements. Another diagram shows the LBR4PFWCP configuration with detailed measurements.

Photometry

The following data presents photometric performance for specific configurations.

ConfigurationInput WattsDelivered LumensLPWS/MHTest No.
LBR4 SWW1 ALO2 AR LSS MWD MVOLT UGZ18.11929106.60.9820-518-01
LBR4WW SWW1 ALO2 AR LSS WW MVOLT UGZ18.11922106.20.7320-518-02

Diagrams: Photometric distribution curves are shown for two specific models (LBR4 SWW1 ALO2 AR LSS MWD MVOLT UGZ and LBR4WW SWW1 ALO2 AR LSS WW MVOLT UGZ). These plots illustrate the light intensity distribution in candelas per square meter (cd/sq.m) at various angles (0° to 90°). Zonal Lumen Summary tables break down the percentage of total lumens emitted within specific angular zones (e.g., 0°-30°, 0°-40°). Cone of Light data provides illuminance (FC) and beam diameter at different mounting heights. Average Luminance data is also presented.

Lumen Output Multipliers

CCT3000K3500K4000K5000K
Multiplier0.981.01.011.03
FinishMultiplier
Clear Semi-spec (AR LSS)1.0
Metallic Silver (MS)0.84
White Painted (WR)1.03
Black Painted (BR)0.60
CRIMultiplier
801.0
900.874

How to Estimate Delivered Lumens in Emergency Mode

Use the formula: Delivered Lumens = 1.25 x P x LPW, where P is the output power of the emergency driver (e.g., 10W for PS1055CP) and LPW is the lumen per watt rating of the luminaire.

Dimmer Compatibility

Not compatible with DALI or DMX dimmers. For specific compatible dimmers, see tables below.

Line Voltage Dimming

TypeForward PhaseALO1 (500-1000lm)ALO2 (1000-2000lm)ALO3 (2000-3000lm)ALO4 (3000-5000lm)Comment
MLVSensorswitch WPDYESYESYESYES
MLVSensorswitch CMR PDT10 ADC VLPYESYESYESYES
MLVSynergy ISD 600LVYES, 2x *YESYESYES* min 2 fixtures
INCSynergy ISD 600 IYES, 2x *YESYESYES* min 2 fixtures
MLVLutron Glyder GLV-600YESYESYESYES
INCLeviton SureSlide 6633YESYESYESYES
MLVLutron Diva DVLV-600PYESYESYESYES
MLVLutron Skylark SLV-600PYESYESYESYES
INCLutron RadioRA 2 10NDYESYESYESYES
MLVLeviton SureSlide 6613-PLWYESYESYESYES
INCLutron Diva DVCL-153PYESYESYESYES
MLVLeviton IPM06YES, 2x *YESYESYES* min 2 fixtures
INCLeviton IP106YES, 2x *YESYESYES* min 2 fixtures
INCControl4 C4-FPD 120YESYESYESYES

Reverse Phase Dimmer Bank

TypeALO1 (500-1000lm)ALO2 (1000-2000lm)ALO3 (2000-3000lm)ALO4 (3000-5000lm)
ELVLutron Nova T NTELV-600YESYESYESYES
ELVLutron Diva DVELV 600PYESYESYESYES
ELVLutron Maestro MAELV 600YESYESYESYES
ELVLeviton Vizia VPE06-1LXYESYESYESYES
ELVLeviton Illumatech IPE04YESYESYESYES
ELVControl4 C4-APD 120 REVERSE PHASEYESYESYESYES

Miscellaneous Dimmers

TypeALO1 (500-1000lm)ALO2 (1000-2000lm)ALO3 (2000-3000lm)ALO4 (3000-5000lm)
PHALutron RadioRA2 RRD-6NAYESYESYESYES
PHALutron Maestro PRO LED+ RRD-PROYESYESYESYES

Control Systems

TypeALO1 (500-1000lm)ALO2 (1000-2000lm)ALO3 (2000-3000lm)ALO4 (3000-5000lm)
MLVLutron LP-RPM-4UYESYESYESYES
PHALutron LP-RPM-4AYESYESYESYES
MLVLutron GRAPHIC EYE QSGRJ-3PYESYESYESYES
PHALutron PA Power Module PHPM-PA-120YESYESYESYES
ELVLutron nLight nSP5PCD ELVYESYESYESYES

0-10V Dimming Compatibility

ManufacturerSystem TypeDescriptionP/NALO1 (500-1000lm)ALO2 (1000-2000lm)ALO3 (2000-3000lm)ALO4 (3000-5000lm)
ACUITYWall Boxsensorswitch, dimming switch with multi-way optionSPODMRAYESYESYESYES
ACUITYWall Boxsensorswitch, wall switch sensor, occupancy controlled dimmingWSX D WHYESYESYESYES
ACUITYControl SystemnLightnPP16DYESYESYESYES
ACUITYControl SystemnLightnPS 80 EZYESYESYESYES
ACUITYControl SystemnLight AirrPP20 DYESYESYESYES
LutronOther0-10V (sink or source) PowPak wireless dimming moduleRMJ-5T-DV-BYESYESYESYES
WattStopperControl SystemDigital single relay room controller (0-10V)LMRC-211YESYESYESYES
CrestronControl SystemDIN Rail 0-10V fluorescent dimmer, 4 feeds, 4 channels (Green Light System)DIN-4DIMFLV4YESYESYESYES
LutronOtherGrafik Eye 0-10V adapterGRX-TVIYESYESYESYES
LevitonWall BoxIllumatech 0-10VIP710-DLXYESYESYESYES
LutronControl SystemMounted in the Homeworks QS panel - 0-10V dimmer (sink or source)GRX-TVM2YESYESYESYES
LutronWall BoxNova 0-10V wallbox dimmer (use with PP-120-H line voltage relay)NTFTVYESYESYESYES
LutronWall BoxNova 0-10V wallbox dimmer (use with PP-120-H line voltage relay)NTSTV-DVYESYESYESYES
LutronWall BoxNova TNFTVYESYESYESYES
LevitonWall BoxRenior II 0-10VAWSMG-7DWYESYESYESYES

Additional Data: JOT (Just One Touch)

The Sensor Switch JOT enabled solution offers a wireless, app-free approach to single room lighting control. JOT enabled products use Bluetooth® Low Energy (BLE) technology to enable wireless dimming and switching.

Diagram: Illustrates the JOT system setup: 1. Install JOT enabled fixtures and controls. 2. Pair by inserting the pairing tool into the wall switch pinhole and holding any button for 6 seconds. 3. Play: After pairing, fixtures dim to 10% brightness, and all products become fully functional.

Compatible 0-10V Wall-Mount Dimmers

MANUFACTURERPART NO.POWER BOOSTER AVAILABLE
Lutron®Diva® DVTVCN100
Diva® DVSCTVPE300
Nova T® NTFTV
Nova® NFTV
Leviton®AWSMT-7DW
AWSMG-7DW
AMRMG-7DW
Leviton Centura Fluorescent Control System
IllumaTech® IP7 Series
Synergy®ISD BC
SLD LPCS
RDMFC
Douglas Lighting ControlsDigital Equinox (DEQ BC)WPC-5721
Entertainment TechnologyTap Glide TG600FAM120 (120V)
Tap Glide Heatsink TGH1500FAM120 (120V)
Oasis 0A2000FAMU
HoneywellEL7305A1010 (optional)
EL7315A1019
EL7315A1009
HUNT DimmingPreset slide: PS-010-IV and PS-010-WH
Preset slide: PS-010-3W-IV and PS-010-3W-WH
Preset slide, controls FD-010: PS-IFC-010-IV and PS-IFC-010-WH-120/277V
Preset slide, controls FD-010: PS-IFC-010-3W-IV and PS-IFC-010-3W-WH-120/277V
Remote mounted unit: FD-010
Lehigh Electronic ProductsSolitairePBX
PDM Electrical ProductsWPC-5721
Starfield ControlsTR61 with DALI interface port
WattStopper®LS-4 used with LCD-101 and LCD-103

Control System Integration

Example Diagram: Shows a 'Group Fixture Control' application diagram for fixtures with eldoLED drivers. It illustrates wiring for nPS 80 EZ Dimming/Control Packs, nPODM 2P DX Push-Button WallPod, nCM ADCX Daylight Sensor, and nCM PDT 9 Occupancy Sensor. The description explains how this setup enables manual control of fixtures in separate rows (A and B), incorporates daylight harvesting for Row B, and uses an occupancy sensor to turn off all lights when the space is vacant.

Wiring Key: CAT-5e Cable, Line Power, Low Voltage Dimming Wires.

Choose Wall Controls: nLight offers various wall controls with different features and user experiences, including Push-Button Wallpods and Graphic Wallpods.

nLight® Wired Controls Accessories

Order as separate catalog number. Visit www.acuitybrands.com/products/controls/nlight for a complete listing.

WallPod StationsModel numberOccupancy sensorsModel Number
On/OffnPODM (Color)Small motion 360°, ceiling (PIR/dual Tech)nCM 9 / nCM PDT 9
On/Off & Raise/LowernPOD DX (Color)Large motion 360°, ceiling (PIR/dual tech)nCM 10 / nCM PDT 10
Graphic TouchscreennPOD GFX (Color)Wide View (PIR/dual tech)nWV 16 / nWV PDT 16
Photocell controlsModel NumberWall Switch w/ Raise/Lower (PIR/dual tech)nWSX LV DX / nWSX PDT LV DX
DimmingnCM ADCX
Cat-5 cables (plenum rated)Model Number
10', CAT5 10FTCAT5 10FT J1
15', CAT5 15FTCAT5 15FT J1

nLight® AIR Control Accessories

Order as separate catalog number. Visit www.acuitybrands.com/products/controls/nlightair.

Wall switchesModel number
On/Off single polerPODB [color]
On/Off two polerPODB 2P [color]
On/Off & raise/lower single polerPODB DX [color]
On/Off & raise/lower two polerPODB 2P DX [color]
On/Off & raise/lower single polerPODBZ DX WH¹

Notes:

  • ¹ Can only be ordered with the RES7Z zone control sensor version.

UL924 Sequence of Operation

For nLight AIR devices with an EM option:

  • EM devices remain at their high-end trim and ignore wireless lighting control commands unless a normal-power-sensed (NPS) broadcast is received at least every 8 seconds.
  • Using the CLAIRITY+ mobile app, EM devices must be associated with a group including a normal power sensing device to receive NPS broadcasts.
  • Only non-emergency rPP20, rLSXR, rSBOR, rSDGR, and nLight AIR luminaires with version 3.4 or later firmware can provide normal power sensing for EM devices.

nLight AIR System

nLight AIR is ideal for retrofit or new construction spaces where communication is cost-prohibitive. The integrated nLight AIR rPP20 Power Pack is part of each Lithonia LDN Luminaire, offering individually addressable controls for flexibility.

Simple Setup:

  1. Install nLight® AIR fixtures with embedded smart sensor.
  2. Install the wireless battery-powered wall switch.
  3. Use the CLAIRITY app to pair fixtures with the wall switch and customize sensor settings.

Diagram: Shows the nLight AIR setup with a fixture, a wireless wall switch (rPODB 2P DX), and a mobile device for the CLAIRITY app.

PDF preview unavailable. Download the PDF instead.

lbr4 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Macintosh)

Related Documents

Preview Lithonia Lighting LBR6 6-Inch LED Downlight - Specifications, Features, and Compatibility
Detailed specifications, performance data, ordering information, and dimmer/control system compatibility for the Lithonia Lighting LBR6 6-inch LED retrofit and remodel downlight, suitable for various commercial and residential applications.
Preview Lithonia Lighting LBR12 12-Inch LED Retrofit Downlight Specifications and Ordering
Comprehensive specifications, performance data, ordering information, and dimmer compatibility for the Lithonia Lighting LBR12 12-inch LED retrofit and remodel downlight.
Preview Lithonia Lighting LBR4 NCH: 4-Inch New Construction LED Downlight Specifications
Comprehensive specifications, features, ordering information, and compatibility for the Lithonia Lighting LBR4 NCH 4-inch New Construction LED Downlight. Includes lumen output, CCT, CRI, dimming, and control options.
Preview Lithonia Lighting LBR6 NCH 6-Inch LED New Construction Downlight - Specifications and Performance
Comprehensive details on the Lithonia Lighting LBR6 NCH 6-inch LED New Construction Downlight, including features, specifications, performance data, ordering information, dimming compatibility, control system integration (nLight, JOT), and accessories.
Preview Lithonia Lighting LBR8 8-inch LED Downlight: Features, Specifications, and Ordering Guide
Comprehensive product data for the Lithonia Lighting LBR8 8-inch LED retrofit and remodel downlight. This document details features, specifications, performance data, ordering options, accessories, dimmer compatibility, and control system integration for commercial and residential applications.
Preview Lithonia Lighting LBR8 NCH 8-Inch New Construction LED Downlight - Specifications & Ordering
Detailed specifications, performance data, ordering information, and compatibility for the Lithonia Lighting LBR8 NCH 8-inch New Construction LED Downlight. Features adjustable lumen output, multiple CCT options, and advanced control system integration.
Preview Lithonia Lighting 2BLT4R LED Relight Troffer: Features, Specifications, and Controls
The Lithonia Lighting 2BLT4R is a 2'x4' LED relight troffer designed for efficient retrofitting of existing fluorescent fixtures. It offers high lumen output, multiple diffuser options, integrated nLight and SensorSwitch controls, and optional emergency battery packs.
Preview Lithonia Lighting STACK LED Center Element Troffer: Features, Specifications, and Controls
Detailed information on the Lithonia Lighting STACK LED Center Element Troffer, covering its features, construction, installation, electrical specifications, optics, listings, warranty, ordering options, integrated controls (nLight, SensorSwitch), accessories, photometrics, and performance data for commercial and indoor applications.