Lithonia Lighting LBR8 NCH
8" Open and Wallwash LED New Construction Downlight
Features & Specifications
- Intended Use: Typical applications include corridors, lobbies, conference rooms, and private offices.
- Construction: New Construction. Optional goof rings available for additional overlap trim coverage. Accommodates 1/2"-1-1/2" ceiling thickness. 25° ambient temperature. IC rated up to 1000lm.
- Optics: LEDs are binned to a 3-step MacAdam Ellipse. 55° cutoff. New construction frame approved for 8 (4 in/4 out) No. 12 AWG conductors rated for 90°C through wiring. 80CRI standard (90CRI optional).
- UGR: UGR is zero for fixtures aimed at nadir with a cut-off equal to or less than 60deg, per CIE 117-1996 Discomfort Glare in Interior Lighting.
- Electrical: Adjustable lumen output with four module options. Fixed lumen options also available. MVOLT 120/277V 50/60Hz driver (0-10V & 120V Phase Dimming to 10% or 1% min dimming level). FCC CFR Title 47 Part 15 Class A for 277V. FCC CFR Title 47 Part 15 Class B for 120V.
- Lumen Maintenance: L80 at 60,000 hours.
- Listings: Certified to US and Canadian safety standards. Title 24 compliant (90CRI, up to 1000lm). Damp location standard (Wet Location (WL) optional, requires covered ceiling). Some configurations are ENERGY STAR® certified. TAA compliant. UFC (3-530-01) specification compliant. GSA P100 6.2.4 compliant. Drivers are ROHS compliant.
- Warranty: 5-year limited warranty.
- Notes: Actual performance may differ based on environment. Values are design or typical, measured under laboratory conditions at 25 °C. Specifications subject to change.
Performance Data
Performance data tables detail delivered lumens and LPW (Lumens Per Watt) for various lumen outputs, color temperatures (30K, 35K, 40K, 50K), and finishes for different models. Testing is conducted in accordance with IESNA LM-79-08 and NEMA standards.
LBR8 AR LSS MWD (80CRI)
Lumen Output | Wattage | 30K/80CRI | 35K/80CRI | 40K/80CRI | 50K/80CRI | ||||
---|---|---|---|---|---|---|---|---|---|
Lumens | LPW | Lumens | LPW | Lumens | LPW | Lumens | LPW | ||
ALO1 (500LM) | 6 | 551 | 96 | 564 | 97 | 577 | 99 | 595 | 101 |
ALO1 (750LM) | 9 | 872 | 98 | 893 | 100 | 914 | 102 | 942 | 104 |
ALO1 (1000LM) | 13 | 1225 | 95 | 1253 | 96 | 1283 | 98 | 1323 | 101 |
ALO2 (1000LM) | 13 | 1298 | 105 | 1328 | 106 | 1360 | 108 | 1402 | 111 |
ALO2 (1500LM) | 19 | 1895 | 101 | 1939 | 103 | 1985 | 105 | 2047 | 107 |
ALO2 (2000LM) | 25 | 2387 | 96 | 2442 | 98 | 2500 | 99 | 2578 | 102 |
ALO3 (2000LM) | 25 | 2456 | 99 | 2513 | 101 | 2572 | 103 | 2652 | 105 |
ALO3 (2500LM) | 32 | 2965 | 94 | 3034 | 96 | 3106 | 98 | 3202 | 100 |
ALO3 (3000LM) | 38 | 3367 | 90 | 3445 | 91 | 3527 | 93 | 3636 | 95 |
ALO4 (4000LM) | 39 | 4008 | 104 | 4090 | 106 | 4172 | 108 | 4213 | 109 |
ALO4 (4500LM) | 44 | 4424 | 101 | 4514 | 103 | 4604 | 105 | 4649 | 106 |
ALO4 (5000LM) | 49 | 4811 | 98 | 4909 | 100 | 5007 | 102 | 5056 | 103 |
LBR8 MS MWD (80CRI)
Lumen Output | Wattage | 30K/80CRI | 35K/80CRI | 40K/80CRI | 50K/80CRI | ||||
---|---|---|---|---|---|---|---|---|---|
Lumens | LPW | Lumens | LPW | Lumens | LPW | Lumens | LPW | ||
ALO1 (500LM) | 6 | 463 | 80 | 474 | 82 | 485 | 84 | 500 | 86 |
ALO1 (750LM) | 9 | 733 | 82 | 750 | 84 | 767 | 86 | 791 | 88 |
ALO1 (1000LM) | 13 | 1029 | 79 | 1053 | 81 | 1078 | 83 | 1111 | 86 |
ALO2 (1000LM) | 13 | 1091 | 87 | 1116 | 89 | 1142 | 91 | 1178 | 94 |
ALO2 (1500LM) | 19 | 1592 | 84 | 1629 | 86 | 1667 | 88 | 1719 | 91 |
ALO2 (2000LM) | 25 | 2005 | 80 | 2052 | 82 | 2100 | 84 | 2165 | 87 |
ALO3 (2000LM) | 25 | 2063 | 83 | 2111 | 85 | 2161 | 87 | 2228 | 89 |
ALO3 (2500LM) | 32 | 2490 | 79 | 2548 | 81 | 2609 | 83 | 2690 | 85 |
ALO3 (3000LM) | 38 | 2828 | 75 | 2894 | 77 | 2963 | 78 | 3055 | 81 |
ALO4 (4000LM) | 39 | 3367 | 86 | 3436 | 88 | 3504 | 90 | 3539 | 91 |
ALO4 (4500LM) | 44 | 3716 | 84 | 3792 | 86 | 3867 | 88 | 3905 | 89 |
ALO4 (5000LM) | 49 | 4041 | 82 | 4124 | 84 | 4206 | 86 | 4247 | 87 |
Note: Tested in accordance with IESNA LM-79-08. Tested to current IES and NEMA standards under stabilized laboratory conditions. CRI: 80 typical.
Diagram Descriptions
- Page 1: Visuals show the Lithonia Lighting LBR8 NCH downlight fixture, with separate illustrations for 'Open Trim' and 'Wallwash Trim' options.
- Page 2: Diagram illustrates the modular ordering system, breaking down the catalog number into Series/Housing Style, Lumens, Color Temperature, Reflector Color, Reflector Flange, Reflector Finish, Distribution, Voltage Driver, Emergency Options, Control Input, and other Options. Includes an 'Option Value Ordering Restrictions' chart.
- Page 3: Illustrations show accessory items like goof rings (LBRGR910, LBRCPGR910) and various reflector trims (LBRO8, LBRW8 series). Includes a diagram of an 8" goof ring with dimensions. Also details 'Emergency Battery Pack Options - Field Installable' with model numbers, wattage, runtime, lumen output, and other specifications.
- Page 4: Features a 'Plenum Depth Table' and 'Ceiling Coverage Table'. Diagrams show the '8" New Construction Frame, 18" Conduit' and '8" New Construction Frame, QDS' with dimensions. Includes aperture size and ceiling cutout information.
- Pages 5-7: Detailed dimensional drawings and assembly views for various configurations, including LBR8 SWW1 ALOx MVOLT UGZ, LBR8 SWW1 AL03 MVOLT DALI, LBR8 SWW1 AL0x MVOLT UGZ EC1, LBR8 SWW1 AL0x MVOLT UGZ QDS, LBR8PFWCP, LBR8 SLWBWR18ASLWOxWMV1OALTLU0GxZ MCPVOLT UGZ CP, LBR8 ALOx SWW1 xx xxx 347 UGZ, and LBRx nLIGHT configurations. These diagrams illustrate wiring connections, component placement, and overall fixture dimensions.
- Page 8: Presents photometric data including distribution curves, zonal lumen summaries, cone of light data, and luminance data for different configurations. Also includes Lumen Output Multipliers tables for CCT, Finish, and CRI, and a guide on estimating delivered lumens in emergency mode.
- Pages 9-11: Detail dimmer compatibility for Line Voltage Dimming and 0-10V Dimming, listing compatible manufacturers and models. Explains the 'JOT' (Just One Touch) wireless control system with diagrams and setup steps. Shows wiring diagrams for nLight control systems (Row A/B control with occupancy and daylight sensors) and lists nLight Wired Controls Accessories.
- Page 12: Details nLight AIR Control Accessories and the UL924 Sequence of Operation for nLight AIR devices with EM options. Explains the nLight AIR system and its simple setup process (1, 2, 3).
Ordering Information
Lead times vary depending on options selected. Consult with your sales representative.
Example Part Number: LBR8 NCH ALO2 SWW1 AR LSS MWD MVOLT UGZ 90CRI
Module Ordering Components:
- Series / Housing Style: LBR8 NCH (New Construction), LBR8WW NCH (New Construction Wall Wash)
- Lumens: Adjustable (ALO1-ALO4) or Fixed Lumen Output options (e.g., 05LM, 10LM).
- Color Temperature: Switchable CCT (SWW1: 3000K-5000K) or Fixed CCT (27K, 30K, 35K, 40K, 50K).
- Reflector Color: Options include Clear (AR), Black (BR), Metallic Silver (MS), White (WR), Custom (TCPC), RAL (TRALTBD).
- Reflector Flange: Options include Self-flanged, White (TRW), Black (TRBL), Custom (FCPC), RAL (FRALTBD).
- Reflector Finish: Semi-specular (LSS).
- Distribution: Medium Wide (MWD), Wide (WD), Wallwash (WW).
- Voltage Driver: MVOLT (120/277/347V) with UGZ (0-10V dimming) or DALI driver.
- Emergency: Options include no emergency, battery pack (ELR, E10WCP, E10WCPR, E10WRSTAR), Iota Emergency Transfer System (ETS).
- Control Input: No Control Input, JOT (Wireless), nLIGHT (Wired), nLIGHTER (Wired w/EM), nLIGHT AIR (Wireless).
- Options: 90CRI, Airtight (AT), Extended Conduit (EC1, EC6), Wet Location (WL), Quick Disconnect (QDS), Chicago Plenum (CP).
Option Value Ordering Restrictions:
A comprehensive chart details compatibility between various options. Key restrictions include that Adjustable Lumens/CCT must be specified together, and Fixed Lumens/CCT must be specified together. Certain reflector finishes or colors may not be compatible with specific options like Wet Location or particular driver types. Detailed compatibility information is crucial for correct product configuration.
Accessories
- Goof Rings (LBRGR910, LBRCPGR910)
- Reflector Trims (LBRO8, LBRW8 series)
- 347V Step-down Transformer (LBR SDT 347V 75W ASM)
- Sloped Ceiling Adapter (SCA8)
Emergency Battery Pack Options - Field Installable
Battery Model Number | Wattage | Runtime (Minutes) | Lumen Output* @ 120 Lumens/Watt | Other |
---|---|---|---|---|
ILB CP07 2H A | 7W | 120 | 840 | Storm Shelter/2 Hour Runtime |
ILB CP10 A | 10W | 90 | 1200 | Title 20, Self Diagnostic |
ILBLP CP10 HE SD A+ | 10W | 90 | 1200 | Title 20, Self Diagnostic |
ILBLP CP15 HE SD A+ | 15W | 90 | 1800 | Title 20, Self Diagnostic |
ILB CP20 HE A | 20W | 90 | 2400 | Title 20 |
ILB CP20 HE SD A | 20W | 90 | 2400 | Title 20, Self Diagnostic |
ILBHI CP10 HE SD A+ | 10W | 90 | 1200 | 347-480V AC Input, Title 20, Self Diagnostic |
ILBHI CP15 HE SD A+ | 15W | 90 | 1800 | 347-480V AC Input, Title 20, Self Diagnostic |
*Minimum delivered lumen output to assist in product selection for increased fixture mounting height.
Photometry
Photometric data is provided, including distribution curves, zonal lumen summaries, cone of light data, and luminance data for various configurations. Lumen output multipliers are available for different CCTs, finishes, and CRI values. A guide is included for estimating delivered lumens in emergency mode using the formula: Delivered Lumens = 1.25 x P x LPW.
Dimmer Compatibility
The document outlines extensive dimmer compatibility for both Line Voltage Dimming (Forward Phase, Reverse Phase) and 0-10V Dimming. It lists compatible manufacturers, system types, and specific model numbers for various lumen outputs. DALI and DMX dimmers are noted as not compatible. Detailed compatibility charts are provided in the original document.
Lighting Control Systems
JOT (Just One Touch)
A wireless, app-free system using Bluetooth Low Energy (BLE) for dimming and switching. Setup involves installing fixtures and controls, pairing via a pinhole tool, and then the system operates.
nLight Wired Controls
Offers various wall control styles (Push-Button, Graphic) and accessories like occupancy sensors, photocells, and dimming modules. Example wiring diagrams demonstrate integration with sensors for manual and automatic control, including daylight harvesting and occupancy sensing.
nLight AIR
An integrated wireless solution for retrofit or new construction spaces, featuring smart sensors and individually addressable controls. Setup involves installing nLight AIR fixtures, wireless wall switches, and pairing via the CLAIRITY+ mobile app for customization.
UL924 Sequence of Operation: For nLight AIR devices with an EM option, emergency operation maintains high-end trim unless a normal-power-sensed (NPS) broadcast is received. Association with a group including a normal power sensing device is required for EM devices to receive NPS broadcasts.
Key Product Attributes
- Model: LBR8 NCH
- Brand: Lithonia Lighting
- Product Type: 8" New Construction LED Downlight
- Certifications: UL Listed, ENERGY STAR (select configurations), Title 24 Compliant
- Warranty: 5-Year Limited