Section 5: Operation
⚠ WARNING
The advanced warning system provides optimum protection against microbiological contamination. DO NOT disregard warning signals. Have water microbiologically tested by a recognized testing agency regularly.
5.1 Basic Systems Incorporating BA-ICE-C and BA-ICE-CL Controllers
5.1.1 Lamp Life Remaining (days)
The controller tracks the lamp's days of operation. The default screen displays the total lamp life remaining (e.g., "365" days). The controller counts down until "0" days, at which point it displays "83" and sounds an intermittent audible chirp (1 second on, 5 seconds off), indicating the need for lamp change.
5.1.2 Understanding your "A3" Code
"83" (DEFERRAL) - When the "A3" or end of lamp life message is shown, the audible alarm can be deferred up to 4 times. Each deferral lasts seven days and is activated by pressing the timer reset button for 5 seconds. Once the final 7-day deferral is reached, the alarm can only be silenced by changing the UV lamp and manually resetting the controller timer (refer to Section 4.1).
5.1.3 Resetting Lamp Life
Refer to Section 4.1.
ⓘ NOTE
Even if the alarm can be deferred, address all alarm conditions as they indicate potential system problems.
5.1.4 Total Days of Operation
The controller displays the total running time in days (e.g., "1680"). Press the push-button once to view this. It remains displayed for ten seconds before reverting to the lamp life remaining screen. This value cannot be reset.
5.1.5 Lamp Failure (Blank Screen)
When the system detects UV LAMP FAILURE (no current running through the lamp), the display will be blank, and an intermittent audible tone (1 second on, 1 second off) will sound. This state persists until the condition is remedied.
5.2 Plus Systems Incorporating BA-ICE-CM Controller
5.2.1 UV Intensity (%)
The VIQUA Plus series products incorporate a UV sensor that detects the 254 nm wavelength of the UV lamp. This information is relayed to the controller as "% UV output" (default display). The system displays UV output between 50% and 99%. If the system drops below 50%, a low UV warning ("A2") flashes alternately with the actual UV level (e.g., "49") at 2-second intervals. An intermittent audible tone (2 seconds on, 2 seconds off) also sounds during low UV conditions.
UV Levels Interpretation:
- 65 to 99: System functioning within normal operating range.
- 56 to 64: UV level is still safe, but cleaning or lamp/sleeve replacement may soon be required.
- 50 to 55: UV level is nearing unsafe intensity; UV system should be immediately serviced.
- 49: UV level has reached an unsafe level. Water should not be consumed. The system/water supply should be examined. The solenoid output activates, stopping water flow if a solenoid is installed.
DEFERRAL: To temporarily defer the audible alarm and re-activate the solenoid valve (if fitted) during a low UV alarm, press and hold the timer reset button for five seconds. This mutes the alarm and activates solenoid output for 12 hours.
Over Temperature
When water temperature inside the UV reactor chamber exceeds 40 °C (104 °F), the Controller shows "Ot" on the display. This is usually caused by extended periods of no water flow. To clear, open a faucet and allow water to flow through the system.
Possible causes for low UV alarm conditions:
- The UV lamp has reached end-of-life (> 9000 hours). Replace with a new lamp of the same size and type.
- The quartz sleeve and/or sensor window are stained or dirty, possibly due to mineral deposits or sediment not detected in original water analysis. Refer to Section 4.2.
- Intermittent voltage drop in the household controller reduces lamp output. Lamp returns to normal when power is restored. (Monitoring system will not operate during power failures.)
- Influent water quality has changed and is no longer within the acceptable operational range. Perform a water analysis.
- The UV sensor is not installed correctly.
5.2.2 Lamp Life Remaining (Days)
To obtain this reading, press the timer reset button once and follow steps outlined in Section 5.1.3.
5.2.3 Total Days of Operation
To obtain this reading, press the timer reset button twice and follow steps outlined in Section 5.1.3.
5.2.4 Lamp Failure (Blank Screen)
Refer to Section 5.1.5 for explanation.
ⓘ NOTE
On VIQUA systems, the audible tone for lamp failure is a continuous alarm, unlike the intermittent tone on basic VIQUA systems.
5.2.5 Solenoid Output
The VIQUA controller provides a powered (line voltage) IEC solenoid output connector, working with the UV intensity monitor. This output is protected by a replaceable 2 amp isolated fuse. Connection to the solenoid can be done using the IEC solenoid power cable PN 260135. When the UV intensity monitor senses that water is not adequately treated (drops to 49% UV intensity or below), the internal relay opens, stopping AC power to the normally closed solenoid valve. The valve remains closed until UV level rises above 49%, then it opens, allowing water to pass. To temporarily enable solenoid output for up to 12 hours, refer to Section 5.2.1.
Solenoid Installation (Figure 7 Description): This diagram shows an optional solenoid valve installed in the water line leading to the UV system, with the VIQUA UV system itself shown vertically. The solenoid valve is positioned before the UV system.
ⓘ NOTE
During bypass, do not consume water until the system has returned to a safe condition.
5.2.6 4-20mA Output (Optional)
To transmit UV intensity data remotely via a 4-20 mA signal, an optional "Y" cable (PN 260134) is available from dealers. The "Y" cable comes with 20 meters (65') of cable for the 4-20 mA signal.
Procedure:
- Step 1: Disconnect the existing sensor cable from the controller.
- Step 2: Connect the 'Y' cable to the controller.
- Step 3: Attach the "male" end of the removed sensor cable to the "female" end of the new "Y" cable. Appropriately attach the 4-20 mA cable to the applicable equipment and ensure all connections are hand-tighten.