Western Digital OpenFlex Data24 4000 Series Installation Guide

Regulatory Model: DCS0011
D018-000728-000
Doc. Version 04
July 2025

Table of Contents

Chapter 1. Installation

This document provides information, requirements, and procedures necessary to install and complete the initial bringup of an OpenFlex Data24 4000 Series storage platform.

1.1 Installation Equipment Requirements

This section lists everything that must be in place or available to perform the installation, including the equipment and its components.

Table 2: Included Equipment and Components
Category Item # Included
Chassis w/ 2x Power Supply Units (PSU), 2x IO Modules (IOM), and System Fans 1
Components Rail Assembly kit (includes left and right rail assemblies and rack-mounting hardware) 1
Drive Assembly Storage Devices 1-24 (depending on configuration)
Drive Blanks 0-23 (depending on configuration)
Screws T15 Torx Flat Head screws w/ washers 8
Cables 3m, C13-C14 Power Cables 2
Table 3: Additional Equipment Needed
Equipment Required or Recommended?
T15 Torx Screwdriver Required
Level Recommended
Lift Equipment Recommended
ESD Mitigation Equipment (site specific) Required
Ethernet Cable w/ RJ-45 connectors Required
Table 4: Torque Specifications for Screws
Screw Type Where Used Torque Value
T15 Torx screws Rail Assemblies 3.38-3.61 Nm / 30-32 in-lbf

1.2 Installation Safety

Safety is the number one priority for personnel responsible for installing the OpenFlex Data24 4000 Series platform. This section outlines what to consider before performing an installation.

Protect Yourself and Others

Before installing an OpenFlex Data24 4000 Series, it is important to take precautions to keep all personnel performing the installation—or individuals near the installation site—safe. Make sure all paths and floors are clean and free of obstacles. Do not wear clothing that is loose or can become tangled or catch on anything, or clothing that is too tight and may restrict movement. Read all safety labels and instructions in this manual and on the equipment being used for installation. Never lift the OpenFlex Data24 4000 Series alone; it should always be team-lifted. When installing the unit in a rack, it is highly recommended that you install it at the lowest possible U height of the rack. This is intended to prevent an imbalanced load and it keeps the center of gravity low on the rack to help prevent tipping hazards.

Protect Your Equipment

Always use the proper tooling outlined in this document during installation. This includes torque specifications and driver heads when installing screws, lifting equipment, and safety equipment, as well as the OpenFlex Data24 4000 Series itself. Always respect the ESD requirements outlined at your site. Use ESD mitigation and prevention equipment to prevent discharges that may damage equipment. During installation, do not tip the enclosure.

The following is a list of safety equipment that should be considered before proceeding:

1.3 Before You Begin

The installation process for the OpenFlex Data24 4000 Series happens in two basic phases, which are described in the following procedures:

  1. Unpacking the OpenFlex Data24 4000 Series (page 8)
  2. Installation Procedure (page 9)

1.3.1 How to Report Damage

During the installation process, there are a number of inspection steps where the installation team should be looking for damage to the product that may have occurred during shipment. If damage is found, document the items using the following process.

Before you begin: Before reporting damage to the system, please locate the system information. There is a small plastic tab located on the front of the Chassis that can be pulled out to show the vital system details such as the part number, serial number, and chassis revision number.

Step 1: Take two digital photos of the damaged packaging or component, one closeup shot showing the damage in detail and one further out so the support engineers working the case can see where the damage occurred.

Step 2: Open a web browser and go to https://portal.wdc.com/Support/s/login/. The Western Digital Business Support Center page will appear.

Step 3: Log in to your Support Portal account using an email address and password.

Step 4: Click the Cases icon.

Step 5: Click the Create Case icon.

Step 6: At a minimum, select a Case Reason, Brand, and Severity from the available drop-down menus, and provide a brief explanation of the issue in the Summary field; these fields are required.

Step 7: In addition, type the Part Number and Serial Number into the appropriate fields, and select the Product Category and Product Sub-Category that match your Product Name / Model Number.

Tip: For instructions on filling out the remaining fields, refer to the Business Support Center User Guide, available through the link on the Business Support Center page.

Step 8: Attach Photos to the Case.

a. To attach photos to the Case, click Upload Files and navigate to the location of the photos and select all that need to be added to the case. An Upload Files dialogue box will appear.

b. Click Done to close the Upload Files Dialogue box. The Photos will appear as attachments on the case.

Step 9: Click the Submit button.

1.4 Unpacking the OpenFlex Data24 4000 Series

The OpenFlex Data24 4000 Series and its components are contained in a single shipping box. The box includes the chassis which has all of its major internal components pre-installed and is wrapped in plastic. The shipping box also contains a rail kit container, mounting hardware, and power cables. It is highly recommended that the system is unpacked in an area that is ESD safe and close to the installation space.

Attention: Zero capacity and partially populated 4000 Series chassis are shipped with pre-installed drive blanks. Drive carrier assemblies are packaged separately. Do not discard this box; the assemblies are required to install SSDs.

Table 5: Packaging Contents
Category Item Quantity
Drive Assemblies Drive 24
Components (Installed) PSUs 2
IOMs 2
Fan Modules (built into the Chassis) 4
Components (Included) Rail Kit 1 (2 pc)
Power Cables 2
Screws and Washers Drive Carrier Assemblies 24
T15 Torx Screws 8
Sheet Metal Washers 8

1.5 Installation Procedure

This procedure supports the installation of the OpenFlex™ Data24 4000 Series.

Replacement Requirements
Personnel Required Average Installation Time
1 15 minutes
Tool # Needed Required vs. Optional
T15 Torx screwdriver 1 Required
Level 1 Optional

Step 1: Determine the installation location of the OpenFlex™ Data24 4000 Series. Verify that the planned installation location for the enclosure has 1000 mm (39.4 in.) of usable rack space, door to door, vertical rack rails set between 650 mm – 850 mm / 25.6 in. – 33.46 in., and 2 rack units (U) of available space.

Caution: Always install rack-mounted equipment in the lowest available U height in order to keep the rack's center of gravity low and reduce the risk of tipping.

Step 2: Install the rack mount Rail Assembly.

a. Identify a 2U location in the rack to install the Rail Assembly.

b. From the rear of the rack, set the rear of the Rail Assembly in the identified 2U location and extend it so that the pins fit into the same U holes on the front of the rack.

c. Secure the rear of the rack mount Rail Assembly to the rack using the T15 Torx screwdriver and secure the rail mount using the two washers and screws.

d. From the front of the rack, using the T15 Torx screwdriver, install the two washers and screws that secure the front of the rack mount Rail Assembly.

e. It is recommended at this point to use a level to ensure that the rails are installed in the appropriate position in the rack. Check each rail is installed level individually, and then ensure they are installed at the appropriate rack by spanning both rails. It may be necessary to insert the level used at an angle to rest inside the rack shelf space.

Step 3: Install the remaining Rail Assembly in the same way the first was installed.

Step 4: Install the Chassis onto the rack mounted rails.

a. Carefully slide the Chassis onto the rails until the rack mounts are flush with the mounts on the rails.

b. Using the T15 Torx screwdriver, tighten the two Torx captive screws to secure the Chassis to the rail. Repeat this step to secure the remaining rack mount to the remaining rail.

Step 5: Connect the Ethernet cable into the Ethernet Management port on the IOM.

Step 6: Repeat the previous step to install the remaining Ethernet cable.

Step 7: Connect the QSFP28 cable to the IOM to the QSFP the port.

Step 8: Repeat the previous step to install the remaining QSFP28 cable(s).

Step 9: Connect the power cable to the PSU.

a. Plug the power cable into the PSU power port.

b. Secure the power cable to the PSU by wrapping the hook and loop strap around the power cable.

Step 10: Repeat the previous step to install the remaining power cable.

Step 11: Verify the system has powered on using the System Power LED on the front of the system. The LED should display green.

Step 12: When using SSDs not provided as a part of a Drive Assembly, install SSDs onto a Drive Carrier. Refer to Drive Installation (page 17).

Step 13: Install the Drive Assembly into the enclosure.

a. Prepare the Drive Assembly for installation by pressing the release button on the front of the Drive Assembly. The release handle will eject outward.

b. From the front of the rack, gently slide the Drive Assembly into the Drive Assembly slot until the release handle lifts up slightly, indicating that it is engaged with the Chassis.

c. Rotate the release handle up and press it into the Drive Assembly to secure it into the slot. When it is fully installed the user will feel the handle snap and lock into place.

Result: The OpenFlex™ Data24 4000 Series has now been installed.

1.5.1 Drive Installation

This task supports the installation of an SSD onto a Drive Carrier.

Note: Use a new Drive Carrier each time you replace a drive.

Replacement Requirements
Personnel Required Avg. Replacement Time
1 5 min
Tool # Needed Required vs. Recommended
N/A

Step 1: Hold the Drive Carrier so that you can see the male alignment points on the top, bottom, and side of the drive cradle tabs.

Step 2: Locate the female alignment points on the top, bottom, and side of the drive.

Step 3: Insert the top alignment point on the carrier into the top alignment point on the drive.

Step 4: Gently snap the side alignment point on the carrier into the side alignment point on the drive.

Step 5: Repeat steps 5 and 6 on the other side of the drive and carrier.

1.5.2 Finding OOBM Port IP Addresses with DHCP

This section provides instructions for finding OOBM port IP addresses on the OpenFlex Data24 4000 Series using DHCP.

Before you begin:

If the network has been configured with a DHCP server, the enclosure's RJ45 management ports and QSFP28 data ports are assigned IP addresses using DHCP when the enclosure is initially connected to the network.

The enclosure manager configures the enclosure name using the following naming convention:

IOM management and data port naming conventions are:

Step 1: Use the pullout tab on the OpenFlex Data24 4000 Series chassis to find the serial number for the enclosure.

Step 2: Use the pullout tabs on the OpenFlex Data24 4000 Series IOMs to find the IOM MAC addresses.

Step 3: Cross-reference the IOM MAC addresses using a DHCP server to find and record the IP addresses assigned to them.

Note: If desired, make a DHCP reservation for those IPs or set them to static IPs so that the OOBM port IPs do not change.

Step 4: When a DHCP server is unavailable, use the static link-local IP assigned to the OOBM ports. For detailed instructions, refer to Finding OOBM Port IP Addresses with Non-DHCP Servers (page 22).

1.5.3 Finding OOBM Port IP Addresses with Non-DHCP Servers

This section provides instructions for finding OOBM port IP addresses on the OpenFlex Data24 4000 Series without a DHCP server.

Before you begin: Refer to Finding OOBM Port IP Addresses with DHCP (page 21) for instructions on finding IP addresses with DHCP.

Without an available DHCP server available on the network, the platform reverts to static link-local addresses in the 169.254.0.0/16 IP range for both data and management ports. The host name adds the .local suffix. Use local access through the RJ45 management port to connect directly to a host or laptop for initial configuration.

Note: The steps below provide results using a Linux server to connect to the enclosure. The steps are the same whether connecting to a high availability (42XX series) or non-high availability (41XX series) enclosure.

The enclosure manager configures the enclosure name using the following naming convention:

IOM management and data port naming conventions are:

Step 1: Plug an ethernet cable from the local server into the OpenFlex Data24 4000 Series IOM management port.

Step 2: Configure the local server's ethernet port to be on the 169.254.0.0/16 network.

Step 3: Print the ethernet interfaces available using ifconfig -a Or ip a.

Step 4: Configure the interface to connect to the OpenFlex Data24 4000 Series IOM management port.

Sample ethernet interface configuration in the etc/sysconfig/network-scripts/ifcfg-<interface> file:

BOOTPROTO="static"
IPADDR="169.254.X.X"
NETMASK="255.255.0.0"
DEVICE=<enclosure name>
HWADDR="c4:cb:el:el:b4:al"
ONBOOT=yes
PEERDNS=yes
PEERROUTES=yes
DEFROUTE=yes

Step 5: Activate the interface with ifup.

testhost # ifup <enclosure name>
Connection successfully activated <D-Bus active path: /org/freedesktop/
NetworkManager/ActiveConnection/18

Step 6: Use ifconfig -a or ip a to print the interfaces again to show the 169.254.X.X IP used in the configuration file.

testhost # ifconfig <enclosure name>
<enclosure name>: flags=4163>UP,BROADCAST,RUNNING,MULTICAST> mtu 1500
inet 10.XXX.XXX.XXX netmask 255.XXX.XXX.X broadcast
10.XXX.XXX.X
inet6 fe80::c6cb:e1ff:feel:b4a0 prefixlen 64 scopeid
0x20<link>
ether c4:cb:el:el:b4:a0 txqueuelen 1000 (Ethernet)
RX packets 2821816 bytes 514182108 (490.3 MiB)
RX errors 0 dropped 0 overruns 0 frame 0
TX packets 470144 bytes 89312796 (85.1 MiB)
TX errors 0 dropped 0 overruns 0 carrier 0 collisions 0
device interrupt 16
<enclosurename>:
flags=4099<UP, BROADCAST, MULTICAST> mtu 1500
inet 169.254.X.XX netmask 255.255.0.0 broadcast
169.254.255.255
ether c4:cb:e1:el:b4:a0 txqueuelen 1000 (Ethernet)
RX packets 113831 bytes 42065780 (40.1 MiB)
RX errors 0 dropped 0 overruns 0 frame 0
TX packets 24098 bytes 4032533 (3.8 MiB)
TX errors 0 dropped 0 overruns 0 carrier 0 collisions 0
device interrupt 17

Step 7: Use NMAP to search for IPs on the 169.254.0.0 subnet making sure to include the CIDR notation.

testhost network-scripts #2 nmap -sn 169.254.0.0/16

Step 8: Connect to the identified IP (169.254.X.XXX in this example) to verify it is the OpenFlex Data24 platform.

# wddcs http=169.254.X.XXX show
wddcs v4.3.2.0
Copyright (c) 2019-2025 Western Digital Corporation or its affiliates
Model
: OpenFlex Data24 4240
Serial
: USALPXXXXXSAXXXX
ID
: ofdata24-4240-usalpXXXXXSAXXXX
Name
: ofdata24-4240-usalpXXXXXSAXXXX
Firmware
: 3.0.0
Power state : On
LED
: Off
Slot
: 1
State
: In service
Health
: OK
Details
: None
Capacity : 368.71 TB
More data is available for the following resource types:
adapter
controller
cooling
media
port
power
sensor
clock
Enter "show=<resource>" to get more data
Example: wddcs http=1.2.3.4 show=media

1.6 Discovering and Connecting to NVMe Devices on OpenFlex Data24 4000 Series

This procedure will provide information on discovering and connecting to NVMe devices on OpenFlex Data24 4000 Series using the REST protocol over the data port. The IP address of the enclosure may be obtained using OCGUI or cURL. The IOM MAC addresses are available on the pull-out tabs on each of the IOMs at the rear of the system. Obtain the DHCP IP Address from the DHCP server and cross-reference it with the MAC addresses to determine the IP address. Examples where REST commands are required will display cURL commands.

To find the drive NQN value using OCGUI, refer to Obtaining the Drive NQN Value (page 27).

Step 1: Open a terminal and use the adapter's IPv4 or hostname address to discover all nvme devices installed on the fabric.

sudo nvme discover -t rdma -a <IP of IOM Data Port>

Note: The port defaults to rdma for RoCE, but it can be TCP also. Review the port information to determine protocol being used.

Step 2: Review the output to locate the subnqn number associated with the device that will be connected. The following example shows two devices, the In-Band management device, as well as the device (SSD) intended for connection.

Discovery Log Number of Records 2, Generation counter 0
=====Discovery Log Entry 0======
trtype: rdma
adrfam: ipv4
subtype: nvme subsystem
treq: not specified
portid: 0
trsvcid: 4420
subnqn: nqn.1992-05.com.wdc.ofdata24-4213-usalp00000aa00a:MI.AC (In-Band Management Device)
traddr: 192.168.10.51
rdma_prtype: roce-v2
rdma_qptype: connected
rdma cms: rdma-cm
rdma_pkey: 0x0000
=====Discovery Log Entry 1======
trtype: rdma
adrfam: ipv4
subtype: nvme subsystem
treq: not specified
portid: 0
trsvcid: 4420
subnqn: nqn.1992-05.com.wdc.ofdata24-4213-usalp00000aa000a:nvme.1 (subnqn for NVMe device)
traddr: 192.168.10.51
rdma_prtype: roce-v2
rdma_qptype: connected
rdma cms: rdma-cm
rdma_pkey: 0x0000

Note: This example calls out the IOM-A and RFX-C with the result AC, bolded above. The example also calls out the device number with the numeral 1 at the end of the string, bolded in the following example: nqn.1992-05.com.wdc.ofdata24-4213-usalp00000aa000a:nvme.1. The 1 indicates the device (SSD) system slot number.

Step 3: Connect to the device using the subnqn.

sudo nvme connect -t rdma -a <IP of IOM Data Port> -n nqn.1992-05.com.wdc.ofdata24-4213-usalp00000aa000a: nvme.1

Step 4: Verify the connection using nvme list -v.

root:~$ sudo nvme list -v
NVM Express Subsystems
Subsystem Subsystem-NQN Controllers
nvme-subsys0 nqn.1992-05.com.wdc.ofdata24-4213-usalp00000aa000a:nvme.1 nvme 0
NVM Express Controllers
Device SN MN Address Subsystem Namespaces FR TxPort
nvme 0 AXXXXXXX WUSXXXXXXX traddr=192.168.10.51 trsvcid=4420 nvme-subsys0 nvme0n1 R2109003 rdma
NVM Express Namespaces
Device NSID Usage Format FR TxPort Controllers
nvme0n1 1 3.84 TB / 3.84 TB 512 B + 0 B nvme 0

1.7 Obtaining the Drive NQN Value

Attention: Always confirm that the enclosure status is "Healthy" after changing settings to ensure that the system is operating properly.

Step 1: Navigate to the storage device. Refer to Navigating to a Device (page 27).

Step 2: Click the device's Media icon:

The Media information appears:

Media (24)
Name Identifier Manufacturer Model Capacity Protocol Version Number Durable Name Indicator Power State Health Details
DEVICE 1 1 Western Digital WUS5EA176ESP7E3 7.68 TB NVMe RC610007 nqn.1992-05.com.wdc.ofdata24-4213-nvme.1 OK None
DEVICE 2 2 Western Digital WUS5EA138ESP7E1 3.84 TB NVMe RC610007 nqn.1992-05.com.wdc.ofdata24-4213-nvme.2 OK None
DEVICE 3 3 Western Digital WUS5EA176ESP7E4 7.68 TB NVMe RC610007 nqn.1992-05.com.wdc.ofdata24-4213-cnvme.3 OK None
DEVICE 4 4 Western Digital WUS5EA176ESP7E3 7.68 TB NVMe RC610007 nqn.1992-05.com.wdc.ofdata24-4213-cnvme.4 OK None
DEVICE 5 5 Western Digital WUS5EA176ESP7E3 7.68 TB NVMe RC610007 nqn.1992-05.com.wdc.ofdata24-4213-nvme.5 OK None
Media (24)
Name Serial Identifier Manufacturer Model Capacity Protocol Version Number Durable Name Indicator Power State Health Details
DEVICE 1 1 Western Digital WUS5EA176ESP5E3 7.68 TB NVMe RA410000 nqn.1992-05.com.wdc.ofdata24-4113-uscosIOM-Awme.1 ON OK None
DEVICE 2 2 Western Digital WUS5EA176ESP5E3 7.68 TB NVMe RA410000 nqn.1992-05.com.wdc.ofdata24-4113-uscosIOM-Awme.2 ON OK None
DEVICE 3 3 Western Digital WUS5EA176ESP5E3 7.68 TB NVMe RA410000 nqn.1992-05.com.wdc.ofdata24-4113-uscosIOM-Awme.3 ON OK None
DEVICE 4 4 Western Digital WUS5EA176ESP5E3 7.68 TB NVMe RA410000 nqn.1992-05.com.wdc.ofdata24-4113-uscosIOM-Awme.4 ON OK None
DEVICE 5 5 Western Digital WUS5EA176ESP5E3 7.68 TB NVMe RA410000 nqn.1992-05.com.wdc.ofdata24-4113-uscosIOM-Awme.5 ON OK None
DEVICE 6 6 Western Digital WUS5EA176ESP5E3 7.68 TB NVMe RA410000 nqn.1992-05.com.wdc.ofdata24-4113-uscosIOM-Awme.6 ON OK None

Step 3: Review the Durable Name value next to the devices to view the NQN value.

Note: The NQN value for non-high availability systems contains the IOM that controls the drive. Because the high availability platform maps both IOMs to all drives, the IOM is not a part of the drive NQN value on these systems.

1.7.1 Navigating to a Device

This task provides instructions for using the OCGUI to navigate to a device's dashboard through any other fabric-connected device.

Step 1: Open a browser and enter the IP address or hostname for any fabric-connected device into the address bar. The login page for the device appears:

Step 2: Enter a valid username and password, and click the Login button:

Note: The default username/password is admin/admin.

Warning: After initial login, change the default username/password as a security best practice. Refer to Changing the Default Administrator Password (page 30) for instructions.

The system dashboard appears. In addition, the Devices section provides access to all other fabric-connected devices:

Step 3: If needed, click the Devices banner to expand the list of all connected devices:

Step 4: From the list, identify the device to which you want to navigate.

Step 5: Click the Device Actions icon:

The Device Actions window appears:

Step 6: Click the Open in a new tab/window option to open the device page in a new window.

The device's dashboard appears in a new tab/window.

1.7.2 Changing the Default Administrator Password

This procedure will provide information on changing the default administrator password using OCGUI.

Note: It is highly recommended that this is accomplished as part of the initialization process.

Attention: Always confirm that the enclosure status is "Healthy" after changing settings to ensure that the system is operating properly.

Step 1: Login to the device using the default admin credentials.

Step 2: Navigate to the storage device. Refer to Navigating to a Device (page 27).

Step 3: Click the storage device's Accounts icon:

The Accounts information appears:

Accounts (2)
User Id Identifier Role
admin admin Admin
readonly_username readonly_username ReadOnly

Step 4: Click the pencil icon next to the User Id.

The Update Account information appears in a new window:

Step 5: Type the new Administrator password into the Password and Confirmation fields.

Note: The passwords need to match in order to continue.

Step 6: Click the Update button.

The administrator password updates.

Chapter 2. Safety

This chapter provides safety information for the OpenFlex Data24 4000 Series.

2.1 Electrostatic Discharge

CAUTION Electrostatic discharge can harm delicate components inside Western Digital products. Electrostatic discharge (ESD) is a discharge of stored static electricity that can damage equipment and impair electrical circuitry. It occurs when electronic components are improperly handled and can result in complete or intermittent failures.

Wear an ESD wrist strap for installation, service and maintenance to prevent damage to components in the product. Ensure the antistatic wrist strap is attached to a chassis ground (any unpainted metal surface). If possible, keep one hand on the frame when you install or remove an ESD-sensitive part.

Before moving ESD-sensitive parts, place them in ESD static-protective bags until you are ready to install the part.

2.2 Optimizing Location

2.3 Power Connections

Be aware of the ampere limit on any power supply or extension cables being used. The total ampere rating being pulled on a circuit by all devices combined should not exceed 80% of the maximum limit for the circuit.

CAUTION The power outlet must be easily accessible and close to the unit.

Always use properly grounded, unmodified electrical outlets and cables. Ensure all outlets and cables are rated to supply the proper voltage and current.

When power cycling the unit, wait 10 seconds before re-applying power. Failure to do so may cause the enclosure to boot up in an inaccessible state. If this is encountered, remove power, wait 10 seconds, and then reapply power.

2.4 Power Cords

Use only tested and approved power cords to connect to properly grounded power outlets or insulated sockets of the rack's internal power supply.

If an AC power cord was not provided with your product, purchase one that is approved for use in your country or region.

CAUTION To avoid electrical shock or fire, check the power cord(s) that will be used with the product as follows:

2.5 Rack-Mountable Systems

CAUTION: Always install rack rails and storage enclosure according to OpenFlex™ Data24 4000 Series product documentation. Follow all cautions, warnings, labels, and instructions provided within the rackmount instructions.

Reliable grounding of rack-mounted equipment should be maintained.

If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer.

Observe the maximum rated ambient temperature, which is specified in the product documentation.

For safe operation of the equipment, installation of the equipment in a rack should be such that the amount of air flow is not impeded so that the safe operation of the equipment is not compromised.

2.6 Safety and Service

All maintenance and service actions appropriate to the end-users are described in the product documentation. All other servicing should be referred to a Western Digital-authorized service technician.

Caution: To avoid shock hazard, turn off power to the unit by unplugging both power cords before servicing the unit. Use extreme caution around the chassis because potentially harmful voltages are present.

When replacing a hot-plug power supply, unplug the power cord to the power supply being replaced before removing it from the OpenFlex™ Data24 4000 Series.

The power supply in this product contains no user-serviceable parts. Do not open the power supply. Hazardous voltage, current and energy levels are present inside the power supply. Return to manufacturer for servicing.

2.7 Safety Warnings and Cautions

Use caution when accessing part of the product that are labeled as potential shock hazards, hazardous access to moving parts such as fan blades.

To avoid personal injury or property damage, before you begin installing the product, read, observe, and adhere to all of the following safety instructions and information. The following safety symbols may be used throughout the documentation and may be marked on the product and/or the product packaging.

Models: Data24 4000 Series, Data24 4000 Series OpenFlex NVMe-oF Storage Platform, OpenFlex NVMe-oF Storage Platform, NVMe-oF Storage Platform, Storage Platform

File Info : application/pdf, 40 Pages, 17.78MB

PDF preview unavailable. Download the PDF instead.

install-guide-openflex-data24-4000

References

Apache FOP Version 2.3 oXygen PDF Chemistry Version 21.1 Build 2019-02-19T11:09:12Z

Related Documents

Preview Western Digital OpenFlex Data24 4000 Series Quick-Start Guide: Installation and Setup
A concise guide to installing and setting up the Western Digital OpenFlex Data24 4000 Series storage server, covering rail installation, cabling, power, and device discovery.
Preview Western Digital OpenFlex Data24 4000 Series User Guide
Comprehensive user guide for the Western Digital OpenFlex Data24 4000 Series, detailing its features, specifications, installation, maintenance, and safety information.
Preview Western Digital OpenFlex F3x00 and E3000 User Guide
User guide for Western Digital's OpenFlex F3x00 and E3000, detailing system architecture, components, management, safety, and regulatory information for composable infrastructure solutions leveraging NVMe-oF.
Preview WD Black NVMe SSD: High-Performance Storage for Gamers and Creators
Discover the WD Black NVMe SSD, engineered for extreme speed and reliability. Featuring PCIe Gen3 x4 interface, M.2 2280 form factor, and up to 1000GB capacity. Ideal for gaming, video editing, and demanding workloads.
Preview Western Digital WDDCS Tool User Guide
Comprehensive user guide for the Western Digital WDDCS Tool, covering installation, commands, and firmware upgrade processes for various operating systems and enclosures.
Preview WD ShareSpace™ 네트워크 스토리지 시스템 사용자 안내서: 설치, 사용 및 문제 해결 가이드
WD ShareSpace 네트워크 스토리지 시스템 사용자 안내서: 설치, 설정, 기능 사용, 백업, 원격 액세스 및 문제 해결 가이드. Western Digital의 고성능 NAS 솔루션에 대한 포괄적인 정보 제공.
Preview High-Performance NVMe Storage with Pliops XDP and Western Digital Ultrastar DC SN640 SSDs
Explore the joint solution brief detailing high-performance NVMe storage with Pliops Extreme Data Processor (XDP) and Western Digital Ultrastar DC SN640 NVMe SSDs, offering no-compromise drive failure protection and extended drive life for data-intensive workloads.
Preview Western Digital PC SN810 NVMe SSD - High-Performance PCIe Gen4 Storage
Product brief for the Western Digital PC SN810 NVMe SSD, detailing its PCIe Gen4 performance, M.2 2280 form factor, key features, and technical specifications for gaming, content creation, and demanding applications.