Mitsubishi Electric Ceiling Cassette Air Conditioner Specifications (R32 & R410A Series)

Mitsubishi Electric Ceiling Cassette Air Conditioner Specifications

This document provides detailed technical specifications for Mitsubishi Electric's 4-way airflow ceiling cassette air conditioning units, covering both R32 and R410A refrigerant series.

R32 Series: PLFY-M VEM-E Ceiling Cassette Units

Specifications for models PLFY-M20VEM-E through PLFY-M63VEM-E.

SpecificationPLFY-M20VEM-EPLFY-M25VEM-EPLFY-M32VEM-EPLFY-M40VEM-EPLFY-M50VEM-EPLFY-M63VEM-E
Power source1-phase 220–240V 50Hz, 1-phase 220V 60Hz
Cooling capacity (Nominal)*12.2 kW (7,500 BTU/h)2.8 kW (9,600 BTU/h)3.6 kW (12,300 BTU/h)4.5 kW (15,400 BTU/h)5.6 kW (19,100 BTU/h)7.1 kW (24,200 BTU/h)
Power input (Cooling)0.03 kW0.03 kW0.03 kW0.03 kW0.03 kW0.03 kW
Current input (Cooling)0.31 A0.31 A0.32 A0.32 A0.32 A0.36 A
Heating capacity (Nominal)*22.5 kW (8,500 BTU/h)3.2 kW (10,900 BTU/h)4.0 kW (13,600 BTU/h)5.0 kW (17,100 BTU/h)6.3 kW (21,500 BTU/h)8.0 kW (27,300 BTU/h)
Power input (Heating)0.03 kW0.03 kW0.03 kW0.03 kW0.03 kW0.03 kW
Current input (Heating)0.24 A0.24 A0.25 A0.25 A0.25 A0.29 A
External finish (Unit)Galvanized steel sheet
External dimension (Unit) HxWxD258 x 840 x 840 mm (10-3/16 x 33-3/32 x 33-3/32 in.)
Net weight (Unit)19 kg (42 lbs)19 kg (42 lbs)19 kg (42 lbs)19 kg (42 lbs)19 kg (42 lbs)21 kg (46 lbs)
Grille modelPLP-6EA
External finish (Grille)MUNSELL (1.0Y 9.2/0.2)
Dimension (Grille) H x W x D40 x 950 x 950 mm (1-9/16 x 37-13/32 x 37-13/32 in.)
Net weight (Grille)5 kg (11 lbs)
Heat exchangerCross fin (Aluminum fin and copper tube)
FAN Type x QuantityTurbo fan x 1
External static press.0 Pa (0 mmH2O)
Motor TypeDC motor
Motor output0.050 kW
Driving mechanismDirect-drive
Air flow rate (Low-Mid2-Mid1-High)12 - 13 - 14 - 15 m³/min
200 - 217 - 233 - 250 L/s
424 - 459 - 494 - 530 cfm
12 - 13 - 14 - 15 m³/min
200 - 217 - 233 - 250 L/s
424 - 459 - 494 - 530 cfm
13 - 14 - 15 - 16 m³/min
217 - 233 - 250 - 267 L/s
459 - 494 - 530 - 565 cfm
13 - 14 - 15 - 17 m³/min
217 - 233 - 250 - 283 L/s
459 - 494 - 530 - 600 cfm
13 - 14 - 16 - 18 m³/min
217 - 233 - 267 -300 L/s
459 - 494 - 565 - 636 cfm
14 - 15 - 16 - 18 m³/min
233 - 250 - 267 -300 L/s
494 - 530 - 565 - 636 cfm
Sound pressure level (Low-Mid2-Mid1-High)24 - 26 - 27 - 29 dB<A>24 - 26 - 27 - 29 dB<A>26 - 27 - 29 - 31 dB<A>26 - 27 - 29 - 31 dB<A>26 - 27 - 29 - 31 dB<A>28 - 29 - 30 - 32 dB<A>
Air filterPP honeycomb
Refrigerant piping diameter (Liquid)Ø6.35 (Ø1/4) FlareØ9.52 (Ø3/8) Flare
Refrigerant piping diameter (Gas)Ø12.7 (Ø1/2) FlareØ15.88 (Ø5/8) Flare
Field drain pipe sizeO.D. Ø32 (1-1/4) (VP-25)

*1 Nominal cooling conditions: Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB). Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.).

*2 Nominal heating conditions: Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB). Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.).

*3 Nominal conditions *1 and *2 are subject to JIS B8615-1.

R32 is flammable, and certain restrictions apply to the installation of units. For detail, refer to the section in the Databook on installation restrictions.

When connecting the indoor units of M20 or M25, the maximum connectable number of indoor units is limited. Please refer to the table for details.

Outdoor unitConnectable indoor units (Not including M20 or M25)Connectable indoor units (Including M20 or M25)
(E)M2001–201–8
(E)M2501–251–10
(E)M3001–301–12

R410A Series: PLFY-P VFM-E1 Ceiling Cassette Units

Specifications for models PLFY-P15VFM-E1 through PLFY-P50VFM-E1.

SpecificationPLFY-P15VFM-E1PLFY-P20VFM-E1PLFY-P25VFM-E1PLFY-P32VFM-E1PLFY-P40VFM-E1PLFY-P50VFM-E1
Power source1-phase 220-240V 50Hz / 220V 60Hz
Cooling capacity (Nominal)*11.7 kW (5,800 BTU/h)2.2 kW (7,500 BTU/h)2.8 kW (9,600 BTU/h)3.6 kW (12,300 BTU/h)4.5 kW (15,400 BTU/h)5.6 kW (19,100 BTU/h)
Heating capacity (Nominal)*11.9 kW (6,500 BTU/h)2.5 kW (8,500 BTU/h)3.2 kW (10,900 BTU/h)4.0 kW (13,600 BTU/h)5.0 kW (17,100 BTU/h)6.3 kW (21,500 BTU/h)
Power consumption (Cooling)0.02 kW0.02 kW0.02 kW0.02 kW0.03 kW0.04 kW
Power consumption (Heating)0.02 kW0.02 kW0.02 kW0.02 kW0.03 kW0.04 kW
Current (Cooling)0.19 A0.21 A0.22 A0.23 A0.28 A0.40 A
Current (Heating)0.14 A0.16 A0.17 A0.18 A0.23 A0.35 A
External finish (Unit)Galvanized steel sheet
External finish (Panel)MUNSELL (1.0Y 9.2/0.2)
Dimension (Unit) HxWxD208 x 570 x 570 mm (8-1/4 x 22-1/2 x 22-1/2 in.)
Dimension (Panel) HxWxD10 x 625 x 625 mm (3/8 x 24-5/8 x 24-5/8 in.)
Net weight (Unit)14 kg (31 lbs)15 kg (33 lbs)15 kg (33 lbs)15 kg (33 lbs)15 kg (33 lbs)15 kg (33 lbs)
Net weight (Panel)3 kg (7 lbs)
Heat exchangerCross fin (Aluminum fin and copper tube)
FAN Type x QuantityTurbo fan x 1
Airflow rate (Lo-Mid-Hi)6.5-7.5-8.0 m³/min
108-125-133 L/s
230-265-282 cfm
6.5-7.5-8.5 m³/min
108-125-142 L/s
230-265-300 cfm
6.5-8.0-9.0 m³/min
108-133-150 L/s
230-282-318 cfm
7.0-8.0-9.5 m³/min
117-133-158 L/s
247-282-335 cfm
7.5-9.0-11.0 m³/min
125-150-183 L/s
265-318-388 cfm
9.0-11.0-13.0 m³/min
150-183-217 L/s
318-388-459 cfm
External static press.0 Pa
Motor TypeDC motor
Motor output0.05 kW
Air filterPP Honeycomb fabric (long life type)
Refrigerant piping diameter (Liquid)Ø6.35 (Ø1/4) Flare
Refrigerant piping diameter (Gas)Ø12.7 (Ø1/2) Flare
Field drain pipe diameterO.D. Ø32 (1-1/4) (PVC pipe VP-25 connectable)
Sound pressure level (Lo-Mid-Hi)*226-28-30 dB<A>26-29-31 dB<A>26-30-33 dB<A>26-30-34 dB<A>28-33-39 dB<A>33-39-43 dB<A>

*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.

Cooling: Indoor 27°C(81°F)DB/19°C(66°F)WB, Outdoor 35°C(95°F)DB

Heating: Indoor 20°C(68°F)DB, Outdoor 7°C(45°F)DB/6°C(43°F)WB

*2 It is measured in anechoic room at power source 230V.

Optional Parts

DescriptionModelApplicable models
i-see Sensor corner panelPAC-SF1ME-EP15, 20, 25, 32, 40, 50
Wireless signal receiverPAR-SF9FA-E
Anti-allergy enzyme filterPAC-SK46KF-E

Panel & Corner panel Options

With signal ReceiverWith 3D i-see SensorWith New Wireless Remote Controller
PanelSLP-2FASLP-2FALSLP-2FAE
SLP-2FALESLP-2FALM2SLP-2FALME2
Corner panelPAR-SF9FA-EPAC-SF1ME-E

PDF preview unavailable. Download the PDF instead.

PLFY chetiristruina-kaseta GPL Ghostscript 9.55.0

Related Documents

Preview Mitsubishi Electric PLFY-P VLMD-E Ceiling Cassette Air Conditioner Specifications
Detailed specifications and features for the Mitsubishi Electric PLFY-P VLMD-E 2-way airflow ceiling cassette air conditioner, including dimensions, capacity, power consumption, and optional parts.
Preview Mitsubishi Electric PLFY Series Ceiling Cassette Technical & Service Manual
Comprehensive technical and service manual for Mitsubishi Electric PLFY Series Ceiling Cassette Split-Type Heat Pump Air Conditioners (R410A). Includes specifications, parts, troubleshooting, wiring diagrams, and disassembly procedures for models like PLFY-P32VEM to PLFY-P140VEM.
Preview Mitsubishi Electric CITY MULTI Ceiling Cassette Parts Catalog
Comprehensive parts catalog for Mitsubishi Electric CITY MULTI Series Ceiling Cassette indoor units, detailing service parts, optional components, and model compatibility for VRF systems.
Preview Mitsubishi Electric Ceiling Cassette 4-Way Airflow Air Conditioners: Features and Specifications
Comprehensive overview of Mitsubishi Electric's 4-way airflow ceiling cassette air conditioners, detailing features such as the 3D i-see Sensor, versatile airflow patterns, high and low ceiling modes, automatic air-speed adjustment, and horizontal airflow. Includes detailed technical specifications and optional parts for PLFY-M VEM-E, PLFY-M VEM6-E, and PLFY-P VFM-E1 series.
Preview Mitsubishi Electric R32 Hybrid Pipe Connections Quick Reference Guide
This guide provides essential pipe connection specifications for Mitsubishi Electric's R32 Hybrid air conditioning indoor units, covering various models including PLFY, PEFY, PFFY, and PKFY series for ceiling, floor, and wall mounting.
Preview Mitsubishi Electric PLFY-WL63VEM-E Embodied Carbon Calculation | TM65ANZ Specification
This document provides the embodied carbon calculation for the Mitsubishi Electric PLFY-WL63VEM-E 4-way Cassette Indoor Unit, based on the TM65 ANZ methodology. It details the total carbon footprint, breakdown by life cycle stages, product specifications, and calculation assumptions.
Preview Mitsubishi Electric PLFY-WL25VFM-E R32 Hybrid Indoor Unit Embodied Carbon Calculation
Embodied carbon calculation for the Mitsubishi Electric PLFY-WL25VFM-E R32 Hybrid 4-way Cassette Indoor Unit, based on TM65 ANZ methodology. Details product information, results breakdown, and calculation assumptions.
Preview Mitsubishi Electric R32 Hybrid Catalogue: Next Generation VRF Heat Recovery Systems
Discover the Mitsubishi Electric City Multi R32 Hybrid Systems, featuring advanced 2-pipe VRF heat recovery technology with low GWP R32 refrigerant. These systems offer simultaneous heating and cooling, enhanced safety with water-based indoor units, reduced leak detection, and significant energy and cost efficiencies for commercial buildings.