Ceiling Cassette Type: 2-Way Airflow
PLFY-P VLMD-E (R410A)
Technologies and Functions
- [Fan Speed]
- [Swing]
- [Dual Function]
- [Auto Mode]
- [Dry Mode]
- [Auto-Restart]
- [Drain Pump]
- [Lift Up Filter]
- [Filter Indicator]
- (Refer to P.160 for details)
Slim Body Design
Slim body (depth 634 mm) for up to P100.
Recommended for corridors or long and narrow rooms.
The in-take port features a stylish design instead of a traditional grille, allowing for visually attractive installation in harmony with ceilings and lighting.
Standard Drain Pump
The drain pump is a standard feature, allowing the drain to be positioned anywhere up to 583 mm (22-15/16 in.) from the ceiling surface. This provides greater flexibility with long cross-piping and more versatile piping layouts.
Diagram illustrating the drain pump feature, showing the main unit height from the ceiling surface and the maximum drain height.
Compact Height
Slim body - only 290 mm (11-7/16 in.) high
The slimline body is highly suited for installation in narrow ceiling spaces and for replacing obsolete air-conditioning equipment in older buildings. The main unit height is only 290 mm (11-7/16 in.).
Diagram showing the compact height of the main unit.
Vane Control
Vane angle can be selected from 7 types, including "Horizontal fix" and "Swing," to set the air blow according to preference. Note: Airflow direction cannot be changed individually.
Airflow Modes:
Air blow Swing: The air stream feels good.
Windbreak Horizontal airflow: Cold air doesn't blow directly at me.
Illustrations of vane control options: 'Air blow Swing' showing comfortable airflow, and 'Windbreak Horizontal airflow' showing protection from direct drafts.
Specifications
PLFY-P20-P40VLMD-E Series | PLFY-P50-P125VLMD-E Series | ||||||||
---|---|---|---|---|---|---|---|---|---|
PLFY-P20VLMD-E | PLFY-P25VLMD-E | PLFY-P32VLMD-E | PLFY-P40VLMD-E | PLFY-P50VLMD-E | PLFY-P63VLMD-E | PLFY-P80VLMD-E | PLFY-P100VLMD-E | PLFY-P125VLMD-E | |
Power source | 1-phase 220-240V 50Hz / 1-phase 220-230V 60Hz | ||||||||
Cooling capacity *1 kW | 2.2 | 2.5 | 2.8 | 3.6 | 5.6 | 6.3 | 8.0 | 10.0 | 14.0 |
Cooling capacity *1 BTU/h | 7,500 | 8,500 | 9,600 | 12,300 | 19,100 | 21,500 | 27,300 | 34,100 | 47,800 |
Heating capacity *1 kW | 2.5 | 3.2 | 4.0 | 4.5 | 6.3 | 7.1 | 10.0 | 11.2 | 16.0 |
Heating capacity *1 BTU/h | 8,500 | 10,900 | 13,600 | 15,400 | 21,500 | 24,200 | 34,100 | 38,200 | 54,600 |
Power consumption Cooling kW | 0.072/0.075 | 0.072/0.075 | 0.072/0.075 | 0.081/0.085 | 0.082/0.086 | 0.075/0.080 | 0.101/0.105 | 0.147/0.156 | 0.157/0.186 |
Power consumption Heating kW | 0.065/0.069 | 0.065/0.069 | 0.065/0.069 | 0.074/0.079 | 0.075/0.080 | 0.094/0.099 | 0.140/0.150 | 0.150/0.180 | 0.150/0.180 |
Current Cooling A | 0.36/0.37 | 0.36/0.37 | 0.36/0.37 | 0.40/0.42 | 0.41/0.43 | 0.35/0.38 | 0.49/0.51 | 0.72/0.74 | 0.75/0.88 |
Current Heating A | 0.30/0.32 | 0.30/0.32 | 0.30/0.32 | 0.34/0.37 | 0.35/0.38 | 0.43/0.46 | 0.66/0.69 | 0.69/0.83 | 1.33/1.33 |
External finish Unit (Munsell No.) | Galvanized steel plate | ||||||||
External finish Panel (Munsell No.) | Pure white (6.4Y 8.9/0.4) | ||||||||
Dimension Unit HxWxD mm(in.) | 290 x 776 x 634 (11-7/16 x 30-9/16 x 25) | 290 x 946 x 634 (11-7/16 x 37-1/4 x 25) | |||||||
Dimension Panel HxWxD mm(in.) | 20 x 1080 x 710 (13/16 x 42-9/16 x 28) | 20 x 1250 x 710 (13/16 x 49-1/4 x 28) | |||||||
Net weight Unit kg(lbs.) | 23 (51) | 27 (60) | |||||||
Net weight Panel kg(lbs.) | 6.5 (15) | 7.5 (17) | |||||||
Heat exchanger | Cross fin | ||||||||
FAN Type x Quantity | Turbo fan x 1 | Turbo fan x 2 | |||||||
Airflow rate *2 m³/min (Lo-Mid-Hi) | 6.5-8.0-9.5 | 7.0-8.5-10.5 | 9.0-11.0-12.5 | 11.0-13.0-15.5 | 15.5-18.5-22.0 | 17.5-21.0-25.0 | 24.0-27.0-30.0-33.0 | ||
Airflow rate *2 L/s | 108-133-158 | 117-142-175 | 150-183-208 | 167-217-258 | 258-308-367 | 292-350-417 | 400-450-500-550 | ||
Airflow rate *2 cfm | 230-283-335 | 247-300-371 | 318-388-441 | 353-459-547 | 547-653-777 | 618-742-883 | 848-953-1,059-1,165 | ||
External static press. Pa | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Motor Type | 1-phase induction motor | 1-phase induction motor | |||||||
Motor Output kW | 0.015 (at 240V) | 0.015 (at 240V) | 0.015 (at 240V) | 0.015 (at 240V) | 0.020 (at 240V) | 0.020 x 2 (at 240V) | 0.030 x 2 (at 240V) | 0.078 x 2 (at 240V) | 0.078 x 2 (at 240V) |
Air filter | PP honeycomb fabric (long life type) | ||||||||
Refrigerant pipe diameter Liquid(Flare) mm(in.) | Ø12.7 (Ø1/2) | Ø12.7 (Ø1/2) | |||||||
Refrigerant pipe diameter Gas(Flare) mm(in.) | Ø6.35 (Ø1/4) | Ø6.35 (Ø1/4) | |||||||
Field drain pipe diameter mm(in.) | O.D.32 (1-1/4) | O.D.32 (1-1/4) | |||||||
Sound pressure level 220V,240V dB<A> (Lo-Mid-Hi) | 27-30-33 | 28-31-34 | 29-33-36 | 30-34-37 | 31-34-37 | 32-35-38 | 33-38-40 | 37-41-43 | 40-42-44-46 |
Sound pressure level 230V dB<A> (Lo-Mid-Hi) | 28-31-34 | 30-34-37 | 32-37-39 | 33-38-40 | 33-36-39 | 34-37-40 | 36-39-42 | 37-41-43 | 40-42-44-46 |
Notes:
- *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition. Cooling: Indoor 27°C (81°F)DB/19°C (66°F)WB, Outdoor 35°C(95°F)DB. Heating: Indoor 20°C (68°F)DB, Outdoor 7°C (45°F) DB/6°C (43°F)WB.
- *2 Airflow rate/Sound pressure level are in (low-middle-high) or (low-middle2-middle1-high).
- *3 It is measured in an anechoic room.
Optional Parts
- Decoration panel
Models: CMP-40VLW-C (P20-P40), CMP-63VLW-C (P50-P63), CMP-100VLW-C (P80-P100), CMP-125VLW-C (P125) - OA duct flange
Model: PAC-KH11OF (Applicable for P20-P125)