Philips Dynalite DPMI940-D Dry Contact Interface
Installation Instructions
General Safety and Installation Requirements
⚠️ Devices must be installed in an approved enclosure by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
Les appareils doivent être installés dans un lieu jugé apte, par un électricien qualifié et conformément aux règles et normes locales et nationales en matière d'électricité et de construction.
Die Geräte müssen von einem geprüften Elektriker entsprechend allen nationalen und lokalen Elektro und Bauvorschriften in einem zugelassenen Gehäuse installiert werden.
Los dispositivos se deben instalar en un recinto aprobado por un electricista cualificado de acuerdo a todos los reglamentos eléctricos y de construcción locales y nacionales pertinentes.
I dispositivi devono essere installati da un elettricista qualificato in un luogo approvato, in conformità a tutti gli standard e le norme nazionali e locali vigenti in materia di impianti elettrici e costruzioni edilizie.
Apparaten moeten door een erkende elektricien worden geïnstalleerd in een goedgekeurde behuizing in overeenstemming met alle nationale en lokale elektriciteits - en bouwvoorschriften en wetgeving.
デバイスを取り付ける際は、資格のある電気技師に依頼し、電気と建設に関する国および地域のすべての法令に従って、認可されている筐体内に取り付けてください。
根据国家/地区及当地的电气与建筑规范和法规,该设备必须由有资质的电工安装在经批准的外罩内。
يلزم تركيب الأجهزة داخل حاوية معتمدة، من قبل كهربائي مؤهل وفقًا لجميع قوانين ولوائح الكهرباء والإنشاءات الوطنية والمحلية.
Dimensions
165 mm (6.50 in)
53 mm (2.09 in)
34 mm (1.34 in)
Wiring Diagram and Connections
Diagram 1: General Wiring Setup
Illustrates the connection of the DPMI940-D to a power source and DALI devices. It shows four input terminals labeled 1, 2, 3, and 4, connected to a power distribution unit. A DALI bus is shown connecting to a DDBC120-DALI or DDBC320-DALI controller, with connections for DA+ and DA-.
Diagram 2: Electrical Specifications
Details the voltage and current requirements for the DALI and Dry Contact inputs. DALI inputs require 9.5-22.5 V with less than 9 mA. Dry Contact inputs utilize DC1, DC2, DC3, and COM terminals, with DC4 and COM for fly leads, requiring 3.3 V with less than 4 mA.
Diagram 3: Installation Example
Shows a typical installation scenario with the DPMI940-D unit mounted within a wall box, connected to a DALI bus and dry contact inputs.
Diagram 4: DALI Bus Connection Example
Depicts a connection of DALI devices, including a DDBC120-DALI or DDBC320-DALI controller, to the DALI bus. It also shows a connection to a dry contact input.
Diagram 5: Terminal Block Connection
Provides a close-up view of connecting wires to the terminal blocks on the DPMI940-D unit.
Compliance and Certifications
The device complies with IEC Pollution Degree II and IEC Overvoltage Category III standards. It operates within a temperature range of 0° C (32° F) to 40° C (104° F) and humidity up to 90%.
Certifications include CE, UKCA, cULus, and FCC.
FCC Compliance Notice: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Any modifications not approved by the manufacturer of this device could void the user's authority to operate this device.
Canadian Compliance: This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B).
⚠️ Important Safety Note: Do not connect DALI or dry contact wires to mains. DALI or dry contact wires are NOT SELV and should never be considered touch safe.