Reznor Heat Exchanger Gasket Kit Installation

Reznor Heat Exchanger Gasket Kit Installation

Revision: UB-UD-HX (02-25) 1037154-C

Supersedes: UB-UD-HX (11-24) 1037154-B

FOR GAS-FIRED UNIT HEATERS

MODELS UBX, UBXC, UBZ, UDX, UDXC, AND UDZ

⚠️ DANGER ⚠️

  • Improper installation could result in death, serious injury, and/or property damage. The qualified agency performing this work assumes responsibility for this installation.
  • Proper installation and sealing of the heat exchanger to the heater is necessary for reliable and safe operation. Failure to properly install could result in property damage, personal injury, and/or death.
  • The replacement heat exchanger should be installed by a qualified service agency in compliance with all codes and requirements of authorities having jurisdiction.
  • To prevent damage during shipping or storage, gasket kits for replacement heat exchangers are shipped in a parts bag.
  • Refer to the installation manual provided with the heater for important safety information.

KIT COMPONENTS

Gasket kits should be attached to the replacement heat exchanger at the time of installation. All gaskets are self-adhesive and are cut to size.

Ensure that all components listed in Table 1 are available before beginning installation.

Table 1. Kit Components

Item No.* Component Size Unit Size (MBTUh)
30, 45 60, 75 100, 125 150, 175, 200 225, 250 300, 350, 400
1036360 1036361 1036362 201670 201671 201672
1 Top/bottom header panel gasket 5/8 x 21-3/8
1 x 35-23/64
1033925 (2) 1033925 (2) 1033925 (2)
194533 (2) 194533 (2) 194533 (2)
2 Front/rear header panel gasket 5/8 x 12-5/8
5/8 x 15-5/8
5/8 x 23-5/8
1 x 20-3/16
1 x 26-3/16
1 x 34-3/16
1033922 (2) 1033923 (2) 1033924 (2)
195986 (2) 195987 (2) 195988 (2)
3 Tube support gasket 1 x 89-7/32
1 x 95-7/32
1 x 103-7/32
201424 (1) 201425 (1) 201426 (1)

*See Figure 1.

INSTALLATION

NOTE: Unit sizes 30–125 require the installation of four (4) gasket strips. Unit sizes 150–400 require the installation of five (5) gasket strips.

Install the heat exchanger gasket kit as follows (item numbers refer to Table 1 and are shown in Figure 1):

Figure 1. Heat Exchanger Gasket Locations (Refer to Table 1)

This figure shows two diagrams illustrating the placement of heat exchanger gasket kits on Reznor unit heaters. The left diagram, labeled 'UNIT SIZES 030-125', shows a heat exchanger assembly with two types of header panel gaskets indicated by labels '1' and '2'. The right diagram, labeled 'UNIT SIZES 150-400', shows a similar heat exchanger assembly with header panel gaskets labeled '1' and '2', and a tube support gasket labeled '3'.

  1. Install header panel gaskets:

    NOTE: The header panel gaskets are sealing gaskets and must cover the full length of the surface.

    • Position top/bottom (1) and front/rear (2) gaskets on outer edges of header panel and align holes—ignore large holes in bottom gasket.
    • To apply gasket(s), start at end and gradually peel backing from gasket as it is adhered. Repeat with each strip.
  2. Install tube support gasket (unit sizes 150–400):

    NOTE: The tube support gasket is required to prevent vibration but is not a sealing gasket.

    • Position tube support gasket (3) across top, rear, and bottom of tube support.
    • To apply gasket, start at end and gradually peel backing from gasket as it is adhered.
  3. Complete replacement heat exchanger installation (refer to installation manual provided with heater):

    • Inspect and clean cabinet, burner, and vent system.
    • Replace any components that are not structurally sound.
  4. When installation of replacement heat exchanger is complete, start up heater (refer to installation manual provided with heater):

    • Follow instructions on lighting instruction plate to restart heater.
    • Check all safety features for proper operation.
Models: UBX, UBXC, UBZ, UDX, UDXC, UDZ, UBX Gas Fired Unit Heaters, UBX, Gas Fired Unit Heaters, Unit Heaters, Heaters

File Info : application/pdf, 4 Pages, 1.44MB

PDF preview unavailable. Download the PDF instead.

UB-UD-HX (02-25) 1037154-C

References

Adobe InDesign 20.1 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Reznor Vertical Louver Kit Installation Guide for Gas-Fired Unit Heaters (OPT-CD1)
Installation instructions for the Reznor OPT-CD1 Vertical Louver Kit, designed for gas-fired unit heaters (models UBX, UBXC, UBZ, UDX, UDXC, UDZ, UEZ). Includes component list and step-by-step assembly guide.
Preview Reznor Gas Conversion Kit Installation for Gas-Fired Unit Heaters
This document provides installation instructions for Reznor gas conversion kits for various gas-fired unit heater models, including UBX, UBXC, UBZ, UDX, UDXC, UDZ, UDAP, UDAS, UDBP, and UDBS. It details component selection, safety precautions, and installation steps for converting between natural gas and propane, as well as for high-elevation installations.
Preview Reznor Relay Kit Installation Guide for Multiple Unit Control (CL31/CL32)
Comprehensive installation guide for Reznor CL31 and CL32 relay kits, enabling multiple unit control for various Reznor electric and gas-fired heaters. Includes component lists, detailed installation steps, and wiring specifications.
Preview Reznor Downturn Nozzle Kit Installation Guide for Unit Heaters
Installation instructions and component lists for Reznor downturn nozzle kits (OPT-CD2,3,4,5) for UBX, UBXC, UBZ, UDX, UDXC, UDZ, UEZ, and UWS unit heaters.
Preview Reznor Downturn Nozzle Kit Installation Guide
This guide provides detailed instructions for installing Reznor downturn nozzle kits (CD2, CD3, CD4, CD5) on various Reznor unit heater models including UBX, UBXC, UBZ, UDX, UDXC, UDZ, UEZ, and UWS. It covers kit components and step-by-step installation procedures for both gas-fired and hydronic units.
Preview Reznor Vertical Louver Kit Installation Guide for Unit Heaters
Comprehensive installation guide for the Reznor Vertical Louver Kit (Option CD1) for gas-fired and hydronic unit heaters. Includes part lists, step-by-step instructions, and safety information.
Preview Reznor Stepdown Transformer Kit Installation Guide for Gas-Fired Unit Heaters
Detailed installation instructions for Reznor stepdown transformer kits (CG1, CG2, CG4) for UDAP, UDAS, UDX, UDZ, UDBP, UDBS, UBX, and UBZ gas-fired unit heaters. Includes component lists, wiring guidance, and safety precautions.
Preview Reznor Unit Heater Venting Instructions for UBX and UDX Models
Comprehensive venting instructions for Reznor UBX (Standard Power Vent Blower Type) and UDX (Standard Power Vent Fan Type) unit heaters. Covers general information, safety precautions, venting requirements, condensation mitigation, vent terminal specifications, and installation procedures for both commercial/industrial and residential applications.