All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder. Applications for the copyright holder's written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. SmartGen Technology reserves the right to change the contents of this document without prior notice.

Software Version History

Date Version Note
2020-10-16 1.0 Original Release
2020-12-15 1.1 Replaced the panel drawing.
2022-08-22 1.2 Update company logo and manual format.

1. Overview

The DOUT16B-2 Digital Output Module is an expansion module featuring 16 auxiliary digital output channels. The status of the expansion module is transmitted to the DOUT16B-2 by the main control board via RS485 communication.

2. Technical Parameters

Item Contents
Working Voltage DC8.0V~DC35.0V continuous power supply
Power Consumption <6W
Aux. relay output port 1-16 10A relay for output port 1~4, 7~14. 16A relay for output port 5~6, 15~16.
Case Dimension 161.6mm x 89.7mm x 60.7mm
Installation Way 35mm guide-rail installation or screw installation
Working Temperature (-25~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-30~+80)°C
Weight 0.4kg

3. Module Address

This module features a 4-bit in-line DIP switch providing 16 coding statuses, corresponding to module addresses from 100 to 115. When a switch is turned ON, its status is 1. The module address is calculated using the formula: Module Address = 1A + 2B + 4C + 8D + 100. For example, if ABCD is 0000, the module address is 100. If ABCD is 1000, the address is 101. If ABCD is 0100, the address is 102. If ABCD is 1111, the address is 115.

Table 3 Module Addresses

A B C D Module Addresses
0000100
1000101
0100102
1100103
0010104
1010105
0110106
1110107
0001108
1001109
0101110
1101111
0011112
1011113
0111114
1111115

4. Terminal Diagram

The DOUT16B-2 module features a panel with various terminals for power, communication, and output connections. The front panel includes DIP switches (A, B, C, D) for module address configuration, a POWER indicator, and RS485 communication indicators.

The rear panel provides screw terminals for connections. The following table details each terminal:

Table 1 Description of Rear Panel Terminal Connection

No. Name Description Cable Size Remarks
1.B-DC power supply negative input1.5mm²DC power supply negative input.
2.B+DC power supply positive input1.5mm²DC power supply positive input.
3.1200Twisted shielded line is used. If the terminal needs to match 120Ω resistance, terminal 3 and 4 need to be short circuited.
4.RS485B (-)RS485 communication port0.5 mm²
5.RS485A (+)RS485 communication port0.5 mm²
6.Aux. output port 1Volt free relay N/O output1.5 mm²Capacity 250VAC/10A.
7.Aux. output port 1 (Common)1.5 mm²
8.Aux. output port 2Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
9.Aux. output port 2 (Common)1.5mm²
10.Aux. output port 3Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
11.Aux. output port 3 (Common)1.5mm²
12.Aux. output port 4Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
13.Aux. output port 4 (Common)1.5mm²
14.Aux. output port 5N/C2.5mm²Capacity 250VAC/16A.
15.Aux. output port 5N/O2.5mm²Capacity 250VAC/16A.
16.Aux. output port 5Common2.5mm²
17.Aux. output port 6N/C2.5mm²Capacity 250VAC/16A.
18.Aux. output port 6N/O2.5mm²Capacity 250VAC/16A.
19.Aux. output port 6Common2.5mm²
20.Aux. output port 7Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
21.Aux. output port 7 (Common)1.5mm²
22.Aux. output port 8Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
23.Aux. output port 8 (Common)1.5mm²
24.Aux. output port 9Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
25.Aux. output port 9 (Common)1.5mm²
26.Aux. output port 10Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
27.Aux. output port 10 (Common)1.5mm²
28.Aux. output port 11Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
29.Aux. output port 11 (Common)1.5mm²
30.Aux. output port 12Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
31.Aux. output port 12 (Common)1.5mm²
32.Aux. output port 13Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
33.Aux. output port 13 (Common)1.5mm²
34.Aux. output port 14Volt free relay N/O output1.5mm²Capacity 250VAC/10A.
35.Aux. output port 14 (Common)1.5mm²
36.Aux. output port 15Common2.5mm²Capacity 250VAC/16A.
37.Aux. output port 15N/O2.5mm²Capacity 250VAC/16A.
38.Aux. output port 15N/C2.5mm²
39.Aux. output port 16Common2.5mm²Capacity 250VAC/16A.
40.Aux. output port 16N/O2.5mm²Capacity 250VAC/16A.
41.Aux. output port 16N/C2.5mm²
POWERPower indicatorLight when power supply is normal, distinguish when abnormal.
Module AddressModule addressSelect module address by DIP switch.

5. Communication Configuration and Modbus Communication Protocol

5.1. RS485 Communication Port

The DOUT16B-2 is an expansion output module with an RS485 communication port, following the Modbus-RTU communication protocol.

Communication Parameters

5.2. Information Frame Format Example

5.2.1. Function Code 01H

Slave address is 64H (decimal 100), read 10H (decimal 16) status of starting address 64H (decimal 100).

Table 2 Function Code 01H Master Request Example
RequestBytesExample (Hex)
Slave address164 Send to slave 100
Function code101 Read status
Starting address200 Starting address is 100
64
Count number200 Read 16 status
10
CRC code275 CRC code which calculated by master
EC
Table 3 Function Code 01H Slave Response Example
ResponseBytesExample (Hex)
Slave address164 Respond slave address 100
Function code101 Read status
Read count102 16 status (total 2 bytes)
Data 1101 The content of address 07-00
Data 2100 The content of address 0F-08
CRC code2F4 CRC code which calculated by slave.
64

The value of status 07-00 is indicated as 01H in Hex, and 00000001 in binary. Status 07 is the high-order byte, 00 is the low-order byte. The state of status 07-00 is OFF-OFF-OFF-OFF-OFF-OFF-OFF-ON.

5.2.2. Function Code 03H

Slave address is 64H (decimal 100), starting address is 1 data of 64H (decimal 100) (2 bytes per data).

Table 4 Example Data Address
AddressData (Hex)
64H1
Table 5 Function Code 03H Master Request Example
RequestBytesExample (Hex)
Slave address164 Send to the slave 64H
Function code103 Read point register
Starting address200 Starting address is 64H
64
Count Number200 Read 1 data (total 2 bytes)
01
CRC code2CC CRC code which calculated by master.
20
Table 6 Function Code 03H Slave Response Example
ResponseBytesExample (Hex)
Slave address164 Respond to the slave 64H
Function code103 Read point register
Read count102 1 data (total 2 bytes)
Data 1200 The content of address 0064H
01
CRC code235 CRC code which calculated by slave.
8C

5.2.3. Function Code 05H

Slave address is 64H (decimal 100), starting address is one status of 64H (decimal 100). Set 64H unit as 1.

Table 7 Example Status Data Address
AddressData(Hex)
64H1

Illustration: Hex value FF00 forced status is 1. 0000H is forced as 0. Other values are illegal and do not affect the status.

Table 8 Function Code 05H Master Request Example
RequestBytesExample (Hex)
Slave address164 Send to the slave 64H
Function code105 Forced status
Starting address200 Starting address is 0064H
64
Data2FF Set status as 1
00
CRC code2C4 CRC code which calculated by master.
10
Table 9 Function Code 05H Slave Response Example
ResponseBytesExample (Hex)
Slave address164 Send to the slave 64H
Function code105 Forced status
Starting address200 Starting address is 0064H
64
Data2FF Set status as 1
00
CRC code2C4 CRC code which calculated by master.
10

5.2.4. Function Code 06H

Slave address is 64H (decimal 100), set one point content of starting address 64H (decimal 100) as 0001H.

Table 10 Function Code 06H Master Request Example
RequestBytesExample (Hex)
Slave address164 Send to the slave 64H
Function code106 Write single register
Starting address200 Starting address is 0064H
64
Data200 Set 1 point data (total 2 bytes)
01
CRC code200 CRC code which calculated by master.
20
Table 11 Function Code 06H Slave Response Example
ResponseBytesExample (Hex)
Slave address164 Send to the slave 64H
Function code106 Write single register
Starting address200 Starting address is 0064H
64
Data200 Set 1 point data (total 2 bytes)
01
CRC code200 CRC code which calculated by master.
20

5.3. Corresponding Address to Function Code

Table 12 Function Code 01H

AddressItemDescription
100Output Port 1 Status1 for active
101Output Port 2 Status1 for active
102Output Port 3 Status1 for active
103Output Port 4 Status1 for active
104Output Port 5 Status1 for active
105Output Port 6 Status1 for active
106Output Port 7 Status1 for active
107Output Port 8 Status1 for active
108Output Port 9 Status1 for active
109Output Port 10 Status1 for active
110Output Port 11 Status1 for active
111Output Port 12 Status1 for active
112Output Port 13 Status1 for active
113Output Port 14 Status1 for active
114Output Port 15 Status1 for active
115Output Port 16 Status1 for active

Table 13 Function Code 05H

AddressItemDescription
100Output Port 1 Status1 for active
101Output Port 2 Status1 for active
102Output Port 3 Status1 for active
103Output Port 4 Status1 for active
104Output Port 5 Status1 for active
105Output Port 6 Status1 for active
106Output Port 7 Status1 for active
107Output Port 8 Status1 for active
108Output Port 9 Status1 for active
109Output Port 10 Status1 for active
110Output Port 11 Status1 for active
111Output Port 12 Status1 for active
112Output Port 13 Status1 for active
113Output Port 14 Status1 for active
114Output Port 15 Status1 for active
115Output Port 16 Status1 for active

Table 14 Function Code 03H, 06H

AddressItemDescriptionBytes
100Output Port 1-16 StatusUnsigned2Byte

6. Installation

The module dimensions are as follows:

Unit: mm

Case Dimensions:

Models: DOUT16B-2 Digital Output Module, DOUT16B-2, Digital Output Module, Output Module, Module

File Info : application/pdf, 13 Pages, 700.07KB

PDF preview unavailable. Download the PDF instead.

DOUT16B-2 en

References

Microsoft Word 2016 Microsoft Word 2016

Related Documents

Preview SmartGen SG485-2CAN: User Manual for Communication Interface Conversion Module
User manual for the SmartGen SG485-2CAN, a communication interface conversion module that converts RS485 to CANBUS interfaces. Details specifications, wiring, electrical connections, and dimensions.
Preview SmartGen SGUE485 Communication Interface Conversion Module User Manual
User manual for the SmartGen SGUE485, a communication interface conversion module that converts USB to isolated RS485. Details features, technical parameters, terminal descriptions, applications, and installation for generator control systems.
Preview SmartGen HGM6100LT Series Genset Controller User Manual
User manual for SmartGen HGM6100LT series genset controllers (HGM6110LT/HGM6120LT), detailing features, operation, specifications, and troubleshooting for automatic control and monitoring of generators in extreme environments.
Preview SmartGen HGM7000 Series Genset Controller User Manual
This user manual provides comprehensive information on the SmartGen HGM7000 series genset controllers, covering operation, specifications, installation, and troubleshooting for automated genset control systems.
Preview SmartGen Ship Power Solutions: Marine Engine Control and Power Management Systems
Explore SmartGen's comprehensive range of marine engine control modules, power management systems (PMS), and accessories for reliable ship power solutions. Featuring HMC6000, HMC9000, and more.
Preview SmartGen AIN24-2 Analog Input Module User Manual
User manual for the SmartGen AIN24-2 Analog Input Module, detailing its features, technical specifications, wiring, and troubleshooting for K-type thermocouple, resistance, and 4-20mA current sensors.
Preview SmartGen HMC4000RM Remote Monitoring Controller User Manual
User manual for the SmartGen HMC4000RM remote monitoring controller, providing detailed information on its operation, specifications, installation, and troubleshooting for generator set applications.
Preview SmartGen ACC7200 Diesel Air Compressor Controller User Manual
Comprehensive user manual for the SmartGen ACC7200 Diesel Air Compressor Controller, detailing its operation, specifications, installation, and troubleshooting for efficient industrial air compressor management.