Specifying DX Dedicated Outside Air Units

White Paper

Executive Summary

Dedicated Outdoor Air Systems (DOAS) in modern HVAC configurations function to dehumidify 100-percent outdoor air to a dew point drier than the space before delivering this conditioned air (CA) to occupied spaces. This dew point is lower than the space to offset the internal latent load. DOAS units can operate either independently or in conjunction with local HVAC equipment, which is responsible for maintaining the desired space temperature through additional cooling or heating. The proper specification of DX DOAS equipment is essential for optimizing system efficiency, ensuring occupant comfort, and maintaining indoor air quality (IAQ). Specifying the correct DOAS equipment ensures that the system operates efficiently, preventing issues such as mold growth, humidity problems, and overall occupant discomfort.

Problem Statement

There has been ongoing confusion in the industry regarding the proper specification of DOAS equipment and efficiency. Historically, engineers have relied on AHRI Standard 340/360 for rating DOAS equipment. However, a relatively new standard, AHRI 920-2020, was specifically developed for DOAS applications. Despite this, there remains significant confusion around the different efficiency ratings between these standards, leading to potential misapplication and inefficiencies in system performance, particularly in part load dehumidification performance. Clarifying the appropriate use of these standards is crucial for accurate specification and optimal operation of the overall HVAC system including DOAS equipment.

Solution

To address the confusion surrounding the proper specification of DOAS equipment and efficiency, it is essential to understand the distinct functions and rating standards of DOAS compared to traditional rooftop units. The AHRI 920 standard is specifically designed for DOAS equipment, whose primary function is to remove moisture from the air, unlike typical rooftop equipment rated under AHRI 340/360, which focuses on cooling efficiency. Under AHRI 920, the full load rating for DOAS is Moisture Removal Efficiency (MRE), which measures dehumidification efficiency, rather than the Energy Efficiency Ratio (EER) used for cooling efficiency in traditional rooftop units.

A more comprehensive efficiency measure for DOAS is the Integrated Seasonal Moisture Removal Efficiency (ISMRE2), which evaluates how the unit operates throughout the year under various dynamic dehumidification conditions, with a requirement to maintain a supply air dew point at or below 55°F. In contrast, traditional rooftop equipment is rated using the Integrated Energy Efficiency Ratio (IEER), which assesses cooling efficiency across an operating envelope with static test conditions of 80°F dry bulb and 67°F wet bulb. The dynamic dehumidification capacity conditions for AHRI 920-2020 necessitate capacity modulation through modulating compressors and/or staging to handle varying humidity loads effectively.

Furthermore, since DOAS equipment is specifically designed to manage latent humidity loads, the AHRI 920 standard uniquely incorporates the impact of Hot Gas Reheat (HGRH) on overall efficiency.

By adhering to the AHRI 920 standard for DOAS equipment, engineers can ensure accurate specification, optimal performance, and efficient operation tailored to the unique dehumidification needs of their applications.

Example 1: For Part Load Performance, IEER is Scheduled Instead of ISMRE2

Issue:

IEER is based on 340/360 and is rated on different condenser capacities but the same evaporator coil conditions 80°F/67°F. This depicts how a unit would operate with a mixed air condition. This is because Standard 340/360 is intended to rate the cooling capacity and efficiency of an air-conditioner; it does not address dehumidification. During testing, there is no requirement that the evaporator achieve and maintain a dew point temperature low enough to ensure dehumidification.

Table 1. Comparison of standard rating test conditions for packaged DX units with air-cooled condensers and packaged DX DOAS units

Table 1. Comparison of standard rating test conditions for packaged DX units with air-cooled condensers and packaged DX DOAS units
Condition ACondition BCondition CCondition D
IEER rating conditions (AHRI 340/360-2022)
IEER = (0.020 x A) + (0.617 x B) + (0.238 x C) + (0.125 x D)
Evaporator entering-air conditions80°F DBT80°F DBT80°F DBT80°F DBT
Condenser entering-air conditions67°F DBT67°F DBT67°F DBT67°F DBT
ISMRE2 rating conditions (AHRI 920-2020)
ISMRE2 = (0.14 x A) + (0.34 x B) + (0.39 x C) + (0.13 x D)
Evaporator entering-air conditions95°F DBT80°F DBT70°F DBT63°F DBT
Condenser entering-air conditions78°F DBT73°F DBT66°F DBT59°F DBT

Solution:

ISMRE2: Standard 920 requires the equipment to operate at four different dry-bulb temperatures entering the air-cooled condenser: 95°F, 80°F, 70°F, and 63°F. Also, the air entering the evaporator coil matches the outdoor-air conditions, so it is different at each of these four conditions. This depicts how a 100-percent outdoor-air unit would operate as outdoor air conditions change throughout the year.

Diagram Description: This psychrometric chart illustrates the different operating conditions used for rating HVAC equipment. The horizontal axis represents Dry Bulb Temperature (°F), and the vertical axis represents Wet Bulb Temperature (°F). Lines for Dew Point Temperature (°F) and Humidity Ratio (grains/lb of dry air) are also shown. IEER Rating Conditions (AHRI 340/360-2022) are fixed for evaporator entering air at 80°F DBT and 67°F WBT. ISMRE2 Rating Conditions (AHRI 920-2020) vary to simulate year-round outdoor air conditions for DOAS units, including Condition A (95°F DBT, 78°F WBT), Condition B (80°F DBT, 73°F WBT), Condition C (70°F DBT, 66°F WBT), and Condition D (63°F DBT, 59°F WBT). The chart shows that for AHRI 920-2020, the evaporator entering air conditions are plotted, and the standard requires the unit to achieve a leaving-air dew point of no higher than 55°F at Condition A, and within +/- 0.3°F of this target at Conditions B, C, and D. This focus on dew point is critical for effective dehumidification.

Solution ++

Trane Horizon DOAS is able to provide additional performance and efficiency data at non-standard part load conditions. By providing specific application data, you are ensured peace of mind your DOAS is specifically designed to maintain the required supply-air dew point, and reheat, at all outdoor air conditions in your climate zone.

Example 2: Not Adjusting the Terminal Equipment Schedule When Designing a DOAS System

Issue:

Terminal equipment and DOAS equipment are independently designed without considering OA conditioning. Incorporating DOAS equipment into your design without integrating it into the terminal performance schedule can lead to several issues:

Condensate issues typically arise in systems that fail to decouple the space sensible and latent loads. These issues are exacerbated by the use of Dedicated Outdoor Air Systems (DOAS) units that are unable to maintain the necessary supply-air dewpoint and reheat across all outdoor air conditions. Consequently, these condensate problems are attributable to elevated relative humidity levels within the space.

Solution:

Evaluate the impact of the DOAS equipment on your terminal schedule to meet performance. Example: Elementary School Classroom

Classroom Details: 750 ft² floor area, 26 people (1 teacher + 25 students).

Classroom 101 Conditions
ZoneSpace Dry-Bulb TemperatureSpace Relative HumidityQspace SensibleQspace LatentOutdoor Airflow
Classroom 10173°F50%20,300 Btu/h4,030 Btu/h350 cfm

Designing with a conventional rooftop which can only achieve 55°F dewpoint

Example Classroom Design Space Sensible Cooling Load:

Outdoor Air (OA): 93°F DBT, 80°F WBT.

Room Air (RA) / Space Conditions: 73°F DBT, 56% RH.

Conventional Rooftop Unit (delivering 55°F DPT):

Diagram Description: This psychrometric chart compares the air conditions in an elementary school classroom scenario using a conventional rooftop unit versus a DOAS unit. The axes are Dry Bulb Temperature (°F) and Wet Bulb Temperature (°F), with Dew Point (°F) and Humidity Ratio lines. Outdoor Air (OA) is 93°F DBT, 80°F WBT. Room Air (RA) / Space Conditions are 73°F DBT, 56% RH. The conventional rooftop unit delivers Conditioned Air (CA) at 57°F DBT, 55°F DPT. Supply Air (SA) from the terminal unit is 55°F DBT, 54°F DPT. The combined SA+CA is 56°F DBT, 54°F DPT. The chart visually demonstrates how the conventional unit delivers air at 55°F DPT, which is then mixed with return air. The diagram highlights the 'space SHR' (Specific Humidity Ratio) and the target conditions.

Designing with a DOAS rated piece of equipment like Horizon with 45°F dewpoint

Example Classroom Design Space Sensible Cooling Load:

Outdoor Air (OA): 93°F DBT, 80°F WBT.

Room Air (RA) / Space Conditions: 73°F DBT, 50% RH.

DOAS Unit (delivering 45°F DPT):

Diagram Description: This psychrometric chart illustrates the same elementary school classroom scenario, but this time focusing on a DOAS unit capable of delivering a lower dew point (45°F DPT). The axes are Dry Bulb Temperature (°F) and Wet Bulb Temperature (°F), with Dew Point (°F) and Humidity Ratio lines. Outdoor Air (OA) is 93°F DBT, 80°F WBT. Room Air (RA) / Space Conditions are 73°F DBT, 50% RH. The DOAS unit delivers Conditioned Air (CA) at 47°F DBT, 45°F DPT. Supply Air (SA) from the terminal unit is 55°F DBT, 54°F DPT. The combined SA+CA is 52°F DBT, 50°F DPT. The chart shows how the DOAS delivers air at a significantly lower dew point (45°F DPT). This allows the terminal units (FCU-101) to be smaller and handle only the sensible load, as the DOAS manages the latent load effectively. The diagram visually represents the improved dehumidification capability and its impact on the supply air conditions.

Significant load reduction, both sensible and latent, can be achieved for terminal equipment by designing around a DOAS with a lower dewpoint. This approach not only provides an opportunity to right size terminal equipment, thereby saving project costs, but also addresses IAQ concerns related to moisture in the terminal equipment within the space. In this classroom example, Demand Control Ventilation (DCV) should be deployed to avoid over-cooling the space during unoccupied or part-load operation, thereby preventing the need for reheat. Alternatively, the Dedicated Outdoor Air System (DOAS) can deliver room-neutral air with a low dew point and space-neutral dry-bulb temperature instead of using DCV. Sizing a DOAS unit specifically designed to maintain the supply-air dew point to offset the space's latent load, and reheating it back to a space-neutral dry-bulb temperature, allows the terminal unit to be sized to offset the sensible space load.

Conventional Rooftop Delivering 57°F DBT, 55°F DPT

Conventional Rooftop Unit Performance
TagEntering-Air DBTEntering-Air DPTAirflowSensible CapacityLatent CapacityTotal Capacity
FCU-10173°F56°F760 cfm15,010 Btu/h3580 Btu/h18,590 Btu/h (1.55 tons)
DOAS-193°F75.6°F350 cfm14,380 Btu/h17,370 Btu/h31,750 Btu/h (2.65 tons)

DOAS Delivering 47°F DBT, 45°F DPT (44% capacity reduction)

DOAS Unit Performance
TagEntering-Air DBTEntering-Air DPTAirflowSensible CapacityLatent CapacityTotal Capacity
FCU-10173°F53°F530 cfm10,470 Btu/h0 Btu/h10,470 Btu/h (0.87 tons)
DOAS-193°F75.6°F350 cfm18,130 Btu/h22,400 Btu/h40,530 Btu/h (3.38 tons)

Consider that terminal equipment is typically sized based on design (full load) conditions. The benefit of incorporating a low dewpoint DOAS, in conjunction with terminal equipment, is enhanced part-load humidity and comfort performance throughout the year. This ensures a more efficient and comfortable environment, regardless of varying load conditions.

Example 3: Specifying DX-DOAS Equipment That Does Not Comply with AHRI 920-2020 Standard

Issue:

Prior to the 2016 version of Standard 90.1, there was no industry standard to uniformly rate the efficiency of DX DOAS equipment, so older versions of Standard 90.1 did not prescribe a minimum equipment efficiency for this class of equipment. The minimum efficiency requirements in Standard 90.1 have now been revised to coincide with the 2020 version of AHRI Standard 920.

To comply with ASHRAE 90.1 minimum efficiency rating, equipment efficiency information supplied by manufacturers shall be verified by one of the following:

Solution:

U.S. Department of Energy (DOE) has published federal regulations that govern the efficiency of DX DOAS. They align with addendum CV to Standard 90.1-2022 and went into effect on May 7, 2025. Horizon™ will be included AHRI 920-2020 certification program which will allow designers to comply with efficiency verification under part (b) above. For DOAS equipment that is not covered under the certification program (AHRI 920-2020), their efficiency ratings shall be verified by an independent laboratory - per part (c). This includes typical rooftop equipment that has been modified to claim DOAS operation.

Minimum Efficiency Standards for Direct Expansion-Dedicated Outdoor Air Systems

Diagram Description: This table, 'Minimum Efficiency Standards for Direct Expansion-Dedicated Outdoor Air Systems (Table 17 to § 431.97(g))', outlines efficiency requirements based on subcategory and supplementary heating type. Subcategories include 'Direct expansion-dedicated outdoor air systems'. Supplementary Heating Types vary, such as '(AC)—Air-cooled without ventilation energy recovery systems', '(AC w/VERS)—Air-cooled with ventilation energy recovery systems', '(ASHP)—Air-source heat pumps without ventilation energy recovery systems', '(ASHP w/VERS)—Air-source heat pumps with ventilation energy recovery systems', '(WC)—Water-cooled without ventilation energy recovery systems', '(WC w/VERS)—Water-cooled with ventilation energy recovery systems', '(WSHP)—Water-source heat pumps without ventilation energy recovery systems', and '(WSHP w/VERS)—Water-source heat pumps with ventilation energy recovery systems'. Efficiency Levels are specified using metrics like 'ISMRE2' and 'ISCOP2', with different minimum values for each subcategory and heating type combination. For example, '(AC)—Air-cooled without ventilation energy recovery systems' requires ISMRE2 = 3.8.

Table 17 to § 431.97(g): Minimum Efficiency Standards for Direct Expansion-Dedicated Outdoor Air Systems
SubcategorySupplementary heating typeEfficiency level
Direct expansion-dedicated outdoor air systems(AC)—Air-cooled without ventilation energy recovery systemsISMRE2 = 3.8
(AC w/VERS)—Air-cooled with ventilation energy recovery systemsISMRE2 = 5.0
(ASHP)—Air-source heat pumps without ventilation energy recovery systemsISMRE2 = 3.8
ISCOP2 = 2.05
(ASHP w/VERS)—Air-source heat pumps with ventilation energy recovery systemsISMRE2 = 5.0
ISCOP2 = 3.20
(WC)—Water-cooled without ventilation energy recovery systemsISMRE2 = 4.7
(WC w/VERS)—Water-cooled with ventilation energy recovery systemsISMRE2 = 5.1
(WSHP)—Water-source heat pumps without ventilation energy recovery systemsISMRE2 = 3.8
ISCOP2 = 2.13
(WSHP w/VERS)—Water-source heat pumps with ventilation energy recovery systemsISMRE2 = 4.6
ISCOP2 = 2.64

For more information, join us at trane.com/doas.

Disclaimer: Trane does not provide tax, legal, or accounting advice. This material is for informational purposes only and it should not be relied on for tax, legal, or accounting advice. Tax law is subject to continual change. All decisions are your responsibility, and you should consult your own tax, legal, and accounting advisors. Trane disclaims any responsibility for actions taken on the material presented.

Trane - by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments through a broad portfolio of heating, ventilating and air conditioning systems and controls, services, parts and supply. For more information, please visit trane.com or tranetechnologies.com.

All trademarks referenced in this document are the trademarks of their respective owners.

©2025 Trane. All Rights Reserved.

OAU-WPR001A-EN 08/14/2025

PDF preview unavailable. Download the PDF instead.

OAU-WPR001A-EN 08142025 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Macintosh)

Related Documents

Preview Trane Engineers Newsletter: AHRI 920 Standard for DX Dedicated Outdoor-Air Units
This Trane Engineers Newsletter article explains AHRI Standard 920 for rating DX Dedicated Outdoor-Air (DOA) units, comparing it with AHRI 340/360 and its impact on ASHRAE 90.1 efficiency requirements for HVAC systems.
Preview Trane Horizon Outdoor Air Units: High-Efficiency Heat Pump Solutions
Discover Trane Horizon™ Outdoor Air Units, featuring advanced Water-Source and Air-Source Heat Pump technologies for year-round humidity control, superior comfort, and significant energy savings in commercial and institutional buildings.
Preview Trane Applications Engineering Manual: Dehumidification in HVAC Systems
This Trane Applications Engineering Manual details dehumidification processes in commercial HVAC comfort-cooling systems, covering psychrometric analysis, system performance, and optimization techniques for engineers.
Preview Trane Horizon™ Outdoor Air Unit Product Catalog
Explore the Trane Horizon™ Outdoor Air Unit (OAU), a leading HVAC solution for 100% outdoor air and dew point applications, offering superior indoor air quality, energy efficiency, and advanced control capabilities for commercial environments.
Preview Trane Integrated Dehumidification Solution: Enhancing Home Health and Comfort
This white paper from Trane details the Integrated Dehumidification Solution (IDS), an innovative approach to moisture removal for improved home health, comfort, and energy efficiency in modern homes, addressing challenges like mold and mildew.
Preview Trane IntelliCore Large Split Systems: Advanced HVAC Solutions
Discover Trane's IntelliCore Large Split Systems, featuring state-of-the-art technology for efficient and reliable HVAC solutions. Learn about their advanced features, connectivity, and sustainability benefits for various applications.
Preview Trane Engineers Newsletter: Dehumidifying Constant-Volume HVAC Systems
An in-depth look at the challenges of maintaining optimal relative humidity in constant-volume HVAC systems, particularly at part-load conditions. This article from Trane explores psychrometric analyses and evaluates various design enhancements like total energy recovery, mixed-air bypass, return-air bypass, separate paths, and supply-air tempering to improve dehumidification performance.
Preview Trane Link Variable Speed Air Conditioners: Product Data, Specs & Features
Comprehensive product data, mechanical specifications, sound data, optional accessories, and model nomenclature for Trane Link Variable Speed Air Conditioners (4TTV7X24A1000A, 4TTV7X36A1000A, 4TTV7X48A1000A, 4TTV7X60A1000A). Includes rating conditions and system requirements.