Midea 60Hz Dehumidifier DP Series

This document outlines the service manual for the Midea 60Hz Dehumidifier DP Series, covering models MDUDP-22AEN8-BA7, MDUDP-30AEN8-BA9, MDUDP-35AEN8-BA9, MDUDP-40AEN8-BA9, and MDUDP-50AEN8-BA9/BA9B.

1. Precaution

1.1 Safety Precaution

To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instructions will cause harm or damage. Before servicing the unit, read this service manual at first.

1.2 Warning

Installation

Caution

Operational

Warning

Caution: Risk of fire/flammable materials (Required for R32/R290 units only)

2. Display

Models: MDUDP-22AEN8-BA7, MDUDP-30AEN8-BA9, MDUDP-35AEN8-BA9, MDUDP-40AEN8-BA9, MDUDP-50AEN8-BA9, MDUDP-50AEN8-BA9B

Control panel:

3. Dimension

Diagrams showing the dimensions (W, D, H) of the dehumidifier units.

Model W(mm) D(mm) H(mm)
MDUDP-22AEN8-BA7 386 260 500
MDUDP-30AEN8-BA9
MDUDP-35AEN8-BA9
MDUDP-40AEN8-BA9 392 282 616
MDUDP-50AEN8-BA9
MDUDP-50AEN8-BA9B

4. Refrigerant Cycle Diagram

A diagram illustrating the refrigerant cycle, including the evaporator, condenser, compressor, and capillary tube. The figure describes the important components and their functions in the refrigeration system.

5. Wiring Diagram

Wiring diagram for the Midea dehumidifier models. Notes indicate that display and fan connectors must match the actual indicators, and a specific symbol indicates optional elements.

6. Features

7. Electronic function

7.1 Electric part assembly condition that use

7.2 PCB working environment

7.3 Protection function

7.4 Set humidity operation

7.5 Continually dehumidify operation

In this operation, the compressor and fan work continually unless there is water full protection or sensor fault protection. The setting humidity operation is not applied.

7.6 Smart dehumidifying mode (optional)

At smart dehumidifying mode, the unit automatically controls room humidity in a comfortable range of 45%-55% according to the room temperature. Press the up or down button to exit the smart dehumidifying mode and switch to the set dehumidify mode. The set humidity (Hs) is determined by the temperature (T): If T<18°C, Hs=55%; If 18°C≤T≤25°C, Hs=50%; If T>25°C, Hs=45%.

8. Basic test procedure

8.1 Defective compressor

Compressors are single phase, depending on the model unit. All compressor motors are permanent split capacitor type using only a running capacitor across the start and run terminal. All compressors are internally spring-mounted and externally mounted on rubber isolators.

8.1.1 Compressor wiring test

Remove the compressor terminal box cover and disconnect wires from terminals. Using an ohmmeter, check continuity across the following:

8.1.2 Ground test

Use an ohmmeter set to its highest scale. Touch one lead to the compressor body (a clean point of contact is a must) and the other probe in turn to each compressor terminal. If a reading is obtained, the compressor is grounded and must be replaced.

8.1.3 Checking the compressor efficiency

The reason for compressor inefficiency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas. This condition can be checked as follows:

  1. Install a piercing valve on the suction and discharge or liquid process tube.
  2. Attach gauges to the high and low sides of the system.
  3. Start the system and run a "cooling or heating performance test."

If the test shows: A. Below normal high side pressure, B. Above normal low side pressure, or C. Low temperature difference across the coil, the compressor valves are faulty - replace the compressor.

8.1.4 Terminal overload (external)

Some compressors are equipped with an external overload located in the compressor terminal box adjacent to the compressor body. The overload is wired in series with the common motor terminal. The overload senses both major amperage and compressor temperature. High motor temperature or amperage heats the disc, causing it to open and break the circuit to the common motor terminal.

Heat generated within the compressor shell is usually due to:

  1. High amperage.
  2. Low refrigerant charge.
  3. Frequent recycling.
  4. Dirty condenser.

8.1.5 Terminal overload – Test (compressor external type)

  1. Remove overload.
  2. Allow time for overload to reset before attempting to test.
  3. Apply ohmmeter probes to terminals on overload wires. There should be continuity through the overload.

8.1.6 Terminal overload (internal)

Some model compressors are equipped with an internal overload. The overload is embedded in the motor windings to sense the winding temperature and/or current draw. The overload is connected in series with the common motor terminal. Should the internal temperature and/or current draw become excessive, the contacts in the overload will open, turning off the compressor. The overload will automatically reset, but may require several hours before the heat is dissipated.

8.1.7 Checking the internal overload

  1. No power to the unit, remove the leads from the compressor terminals.
  2. Using an ohmmeter, test continuity between terminals C-S and C-R. If not continuous, the compressor overload is open and the compressor must be replaced.

8.2 Sealed refrigeration system repairs

8.2.1 Equipment require

8.2.2 Equipment must be capable of:

  1. Recovery CFC's as low as 5%.
  2. Evacuation from both the high side and low side of the system simultaneously.
  3. Introducing refrigerant charge into the high side of the system.
  4. Accurately weighing the refrigerant charge actually introduced into the system.
  5. Facilities for flowing nitrogen through refrigeration tubing during all brazing processes.

8.2.3 Hermetic compressor replacement.

The following procedure applies when replacing components in the sealed refrigeration circuit or repairing refrigerant leaks (Include Compressor, condenser, evaporator, capillary tube, refrigerant leaks, etc.):

  1. Recover the refrigerant from the system at the process tube located on the high side of the system by installing a line tap on the process tube. Apply gauge from process tube to EPA approved recovery system. Recover CFCs in system to at least 5%.
  2. Cut the process tube below pinch off on the suction side of the compressor.
  3. Connect the line from the nitrogen tank to the suction process tube.
  4. Drift dry nitrogen through the system and unsolder the more distant connection first (Filter drier, high side process tube, etc.).
  5. Replace inoperative component, and always install a new filter drier. Drift dry nitrogen through the system when making these connections.
  6. Pressurize system to 30 PSIG with proper refrigerant and boost refrigerant pressure to 150 PSIG with dry nitrogen.
  7. Leak test complete system with electric halogen leak detector, correcting any leaks found.
  8. Reduce the system to zero gauge pressure.
  9. Connect vacuum pump to high side and low side of system with deep vacuum hose or copper tubing. (Do not use regular hoses.)
  10. Evacuate system to maximum absolute holding pressure of 200 microns or less. NOTE: This process can be speeded up by use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns. Pressure system to 5 PSIG and leave in system a minimum of 10 minutes. Recover refrigerant, and proceed with evacuation of a pressure of 200 microns or a minimum of 10%.
  11. Break vacuum by charging system from the high side with the correct amount of refrigerant specified. This will prevent boiling the oil out of the crankcase. NOTE: If the entire charge will not enter the high side, allow the remainder to enter the low side in small increments while operating the unit.
  12. Restart unit several times after allowing pressures to stabilize. Pinch off process tubes, cut and solder the ends. Remove pinch off tool, and leak check the process tube ends.

8.2.4 Special procedure in the case of compressor motor burnout

  1. Recover all refrigerant and oil from the system.
  2. Remove compressor, capillary tube and filter drier from the system.
  3. Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent, to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary.
  4. Reassemble the system, including new drier strainer and capillary tube.
  5. Proceed with processing as outlined under hermetic component replacement.

8.2.5 Rotary compressor special troubleshooting and service

Basically, troubleshooting and servicing rotary compressors is the same as on the reciprocating compressor with only a few exceptions:

  1. Because of the spinning motion of the rotary, the mounts are critical. If vibration is present, check the mounts carefully.
  2. The electrical terminals on the rotary are in a different order than the reciprocating compressors. The terminal markings are on the cover gasket. Use your wiring diagram to ensure correct connections.

8.2.6 Refrigerant charge

  1. The refrigerant charge is extremely critical. It must be measured charge carefully - as exact as possible to the nameplate charge.
  2. The correct method for charging the rotary is to introduce liquid refrigerant into the high side of the system with the unit off. Then start compressor and enter the balance of the charge, gas only, into the low side. The introduction of liquid into the low side, without the use of a capillary tube, will cause damage to the discharge valve of the rotary compressor.

NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor.

8.3 Fan motor

A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions.

Fan motor test

  1. Determine that the capacitor is serviceable.
  2. Disconnect fan motor wires from the fan speed switch or system switch.
  3. Apply "live" test cord probes on the black wire and the common terminal of the capacitor. Motor should run at high speed.
  4. Apply "live" test cord probes on the red wire and the common terminal of the capacitor. Motor should run at low speed.
  5. Apply "live" test cord probes on each of the remaining wires from the speed switch or system switch to test intermediate speeds.

8.4 Capacitor

A run capacitor is wired across the auxiliary and main winding of a single phase permanent split capacitor motor, such as the compressor. A single capacitor can be used for each motor or a dual-rated capacitor can be used for both. The capacitor's primary function is to reduce the line current while greatly improving the torque characteristics of a motor. The capacitor also reduces the line current to the motor by improving the power factor of the load. The run capacitor hook-up line side of the capacitor is marked with a red dot and is wired to the line side of the circuit.

Capacitor test:

  1. Remove capacitor from unit.
  2. Check for visual damage such as bulges, cracks, or leaks.
  3. For dual rated, apply an ohmmeter lead to the common (C) terminal and the other probe to the compressor (HERM) terminal. A satisfactory capacitor will cause a deflection on the pointer, and then gradually move back to infinity.
  4. Reverse the leads of the probe and momentarily touch the capacitor terminals. The deflection of the pointer should be two times that of the first check if the capacitor is good.
  5. Repeat steps 3 and 4 to check the fan motor capacitor.

NOTE: A shorted capacitor will indicate a low resistance and the pointer will move to the "0" end of the scale and remain there as long as the probes are connected. An open capacitor will show no movement of the pointer when placed across the terminals of the capacitor.

9. Characteristic of temperature sensor

Indoor room temperature sensor (T1) and Evaporator coil temperature sensor (T2) resistance values at different temperatures are provided in tables.

10. Troubleshooting

10.1. Error codes:

LED displayStand for
ASIndoor room temperature sensor (T1) error
ESEvaporator coil temperature sensor (T2) error
P2Bucket is full or bucket is removed or not in right position (only available for the unit with no pump)
EbBucket is full (only available for the unit with pump)
ECBucket is removed or not in right position (only available for the unit with pump)
E0EEPROM parameter error

NOTE: When more than one error occurs, the priority of the code display order is: E0—P2—EC—AS—ES (No pump) or E0—Eb—EC—P2—AS—ES (pump).

10.2 Troubleshooting

1. P2-Bucket is full or bucket is not in right position diagnosis and solution

Description: Bucket is full or bucket is not in right position (only available for the unit with no pump). Bucket is full (only available for the unit with pump).

Troubleshooting and repair:

Flowchart: Is there a water pump? YES -> Empty the bucket. NO -> Empty the bucket and replace it in the right position.

2. Eb- Bucket is removed or not in right position diagnosis and solution

Description: Bucket is removed or not in right position (only available for the unit with pump).

Troubleshooting and repair:

Flowchart: Eb display -> Replace the bucket in the right position.

3. AS/ES: Open circuit or short circuit of temperature sensor diagnosis and solution

Description: If the sampling voltage is lower than 0.05V or higher than 4.95V, the LED displays the failure code.

Possible causes:

Troubleshooting and repair:

Flowchart: Check the connection between temperature sensor and PCB. Is it properly wired? YES -> Measure the resistance value of the sensor. Is it within acceptable parameters? YES -> Replace the main PCB. NO -> Replace the sensor. NO -> Ensure proper connections.

4. E0: EEPROM parameter error diagnosis and solution

Description: Main chip does not receive feedback from EEPROM chip.

Possible causes:

Troubleshooting and repair:

Flowchart: Shut off the power supply and turn it on 2 minutes later. Is it still displaying the error code? YES -> Replace the main PCB. NO -> The unit is operating normally.

5. EC: Refrigerant Leakage Detection diagnosis and solution

Description: When the number of abnormality B accumulates 4 times, the refrigerant leakage failure will be reported. The specific steps are as follows: 1) When the compressor is turned on, check the difference between T1-T2 every 5 minutes. If T1-T2≥7°C does not keep continuous 5 seconds, the refrigeration system is considered to be abnormal, and one abnormal A is accumulated; 2) If an abnormality A occurs 11 times in total, the compressor will be forced to stop, and an abnormality B will be accumulated once; 3) When the cumulative number of abnormal B reaches 4 times, the LED displays the failure code and the unit turns off.

Possible causes:

Refrigerant leakage, faulty fan, faulty compressor, faulty fan capacitor, etc. cause refrigeration system failure.

Troubleshooting and repair:

Flowchart: Power off, then restart the unit 2 minutes later. Does a problem remain? YES -> The compressor does not operate / The compressor operates several minutes then ceases / The compressor is operating constantly. Replace the capacitor of compressor / Replace the capacitor of fan motor / Check system for leakages. NO -> Does a problem remain? NO -> Does a problem remain? NO -> Are any leakages present? YES -> Repair the leakage and recharge the refrigerant. NO -> Check System for blockages and clear blockages if present. NO -> Replace the compressor / Replace the fan.

6. In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application, and the other is called the Structure Damage.

ProblemWhat to check
Unit does not start•Make sure the dehumidifier's plug is pushed completely into the outlet.
•Check the house fuse/circuit breaker box.
•Dehumidifier has reached its pre-set level or bucket is full.
•Water bucket is not in the proper position
Dehumidifier does not dry the air as it should•Did not allow enough time to remove the moisture.
•Make sure there are no curtains, blinds or furniture blocking the front or back of the dehumidifier.
•The humidity control may not be set low enough.
•Check that all doors, windows and other openings are securely closed.
•Room temperature is too low, below 5°C (41°F).
•There is a kerosene heater or something giving off water vapor in the room.
The unit makes a loud noise when operating•The air filter is clogged.
•The unit is tilted instead of upright as it should be.
•The floor surface is not level.
Frost appears on the coils•This is normal. The dehumidifier has Auto defrost feature.
Water on floor•Hose to connector or hose connection may be loose.
•Intend to use the bucket to collect water, but the back drain plug is removed.
E0, ES, AS, Eb, EC or P2 appear in the display•These are error codes.
The pump operation on light blinks at 1Hz•Clean the filter of the pump.
•Check the pump hose does not link or block.
•Empty the water of the bucket.

PDF preview unavailable. Download the PDF instead.

235303 UseandCareManual Microsoft Word 2016 Microsoft Word 2016

Related Documents

Preview Midea 60Hz Dehumidifier DP Series Service Manual
This document provides comprehensive service information for the Midea 60Hz Dehumidifier DP Series, including safety precautions, operational guidelines, electronic functions, troubleshooting, and component testing.
Preview Midea 60Hz Dehumidifier DP Series Manual
This manual provides detailed information on the Midea 60Hz Dehumidifier DP Series, including safety precautions, operational guidelines, electronic functions, troubleshooting, and maintenance. It covers model numbers MDUDP-22AEN1-BA7, MDUDP-30AEN1-BA9, MDUDP-35AEN1-BA9, MDUDP-40AEN1-BA9, MDUDP-50AEN1-BA9, and MDUDP-50AEN1-BA9B.
Preview Midea Dehumidifier Report: Technical Specifications and Model Differences
Comprehensive report detailing Midea dehumidifier models, including product specifications, model variations, safety markings, and installation guidelines. Covers US and Canadian requirements.
Preview Midea MAD Series Dehumidifier User Manual - Setup, Operation, and Troubleshooting
Comprehensive user manual for Midea MAD series dehumidifiers (MAD20S1QWT, MAD35S1QWT, MAD50S1QWT, MAD50PS1QWT, MAD50PS1QGR). Includes safety precautions, setup, installation, operation, care, troubleshooting, app instructions, and warranty information.
Preview Midea Dehumidifier MDP User Manual - Specifications, Operation & Troubleshooting
Comprehensive user manual for Midea MDP Series Dehumidifiers (MDP30SR71, MDP50SR71, MDP70SR71, MDP70PR71). Find operating instructions, installation guides, care and cleaning tips, and troubleshooting solutions.
Preview Midea Dehumidifier MAD Series User Manual
User manual for Midea MAD series dehumidifiers, covering installation, operation, cleaning, maintenance, troubleshooting, and app instructions. Includes safety warnings and specifications.
Preview Midea Compact Series Refrigerator Service Manual
Comprehensive service manual for Midea Compact Series refrigerators, covering installation, operation, troubleshooting, and repair procedures for models like HS-164LN and UR-BC126CM-ST.
Preview Midea Dehumidifier User Manual: MDP Series Operation Guide
User manual for Midea MDP series dehumidifiers (MDP30SR71, MDP50SR71, MDP70SR71, MDP70PR71). Covers operation, installation, care, and troubleshooting for optimal home comfort.