Rheem Technical Service Bulletin

1-800-432-8373

PowerVent with Honeywell Electronic Control

(PowerVent ESII and PowerVent ESII with Electronic Control)

Service Mode and Control Settings

Service Mode (Electronic Control Only)

Service Mode is entered by pressing down and holding all keys for 5 seconds. Alarm history of the connected appliance is displayed, alarms are indexed by "E1" for most recent alarm, "E2" for second alarm to "E9" for ninth alarm (alarm history can be scrolled by pressing "Up" and "Down" keys). Displayed alarm history can be cleared by pressing "Clear" key. If the alarm history is empty, dashes "--" are displayed instead of "E1", "E2" to "E9" and particular error numbers. Setup Mode is closed and enters User Mode after 5 minutes of user inactivity or when "Done" key is pressed.

Control Settings

SettingValueSettingValue
Set point Range90°F (32°C) to 160°F (71°C)Flame Prove Igniter Off0.5 µA
"HOT" Set point120°F (49°C)Flame Prove RUN0.7 µA
Differential15°F (9°C)Flame Lost< 0.5 µA
ECO Limit199°F (93°C)Strong Flame≥ 1.5 µA

Timings

Ignition StateTiming
Soft Lockout5 minutes; then retries for main burner
ECO Limit LockoutIndefinite
Flammable Vapor Sensor LockoutIndefinite
Hardware Error Lockout / Hard lockoutIndefinite
Pre-purge2 seconds
Trial For Ignition90 seconds
Flame Stabilization Period3 seconds
Inter-purge90 seconds
Flame Failure Response Time1.5 seconds
Post-purge30 seconds
Pressure Switch Fault Delay (failed open/closed)2 minutes

Error Code Flash Display

Display CodeGas Valve "Status" Flash CodeControl Status
NoneShort flash once every four secondsIDLE (no call for heat, no fault conditions)
None"Heartbeat", alternates bright/dimCall For Heat (no fault conditions)
12One Flash, three second pauseLow flame signal (control continues to operate)
44Two Flash, three second pausePressure switch failed closed
46Three Flash, three second pausePressure switch failed open
31Four Flash, three second pauseThermal Cut Off limit lockout
14Five Flash, three second pauseFlame out of sequence
11Six-One Flash, three second pauseFailed trial for ignition
45Six-Two Flash, three second pauseRecycle limit - PS/limit opened
13Six-Three Flash, three second pauseRecycle limit - flame lost
10Six-Five Flash, three second pauseHard Lockout; manual reset required
47Seven Flash, three second pauseFlammable vapor sensor lockout
49Eight-One Flash, three second pauseFVS fault detected
89Eight-Two Flash, three second pauseTemperature sensor fault detected
15Eight-Three Flash, three second pauseElectronics fault detected
93Eight-Four Flash, three second pauseValve fault detected

Troubleshooting: No Power or No Blower Motor

Indications: Nothing happens at all. No blower motor; no sounds.

Display: There is not a display code for this problem.

Troubleshooting Steps:

  1. Check wall plug power with a table lamp.
  2. Check that the unit is plugged in.
  3. Verify gas control switch is ON.
  4. Verify power to the gas control through the black wire (pin #1) on the gas valve Molex. Turn up thermostat on gas valve; observe blinking blue light; otherwise replace control.
  5. Turn thermostat all the way up. Verify power to the blower at the yellow wire (pin #3) on the gas valve Molex. Replace blower if there is power on the yellow wire, but no blower motor. Replace control if you have power on the black wire and not on the yellow wire.

Error Code Troubleshooting

Error 10: Hard Lockout

Indications: The control is in hard lockout.

Troubleshooting Steps:

  • Low gas supply pressure
  • Carbon buildup on electrode
  • Igniter Wire damage
  • Pilot tube restriction
  • Main burner supply tube restriction

Display:

Six-Five Flash, three second pause

Solution:

  • See Error Code history for most recent fault code (on DISPLAY models only).
  • This lockout can only be cleared by manually cycling the control power.

Error 11: Failed Trial for Ignition

Indications: Failed trial for ignition; Maximum ignition attempts. If flame is not sensed during the Trial period, the igniter turns off, the pilot valve closes, the control runs the inducer through Post-purge then turns off the inducer and enters Soft Lockout and flashes the Soft Lockout error code. The control remains in Soft Lockout for 5 minutes before responding to the demand for heat. If the control has entered Soft Lockout three times, the control will enter hard lockout.

Troubleshooting Steps:

  • Low gas supply pressure
  • Carbon buildup on electrode
  • Igniter Wire damage
  • Combustion air blockage
  • Pilot tube restriction

Display:

Six-One Flash, three second pause

Solution:

  • Verify gas pressure with rating plate on water heater.
  • Clean spark electrode and pilot hood with steel wool.
  • Verify igniter spark at electrode.
  • Verify air inlet holes on side of water heater are clean and clear.
  • Inspect pilot tube for obstructions.
  • This lockout can only be cleared by manually cycling the control power.

Error 12: Low Flame Signal

Indications: Low flame signal (control continues to operate)

Troubleshooting Steps:

  • Low gas supply pressure
  • Carbon buildup on electrode
  • Pilot tube restriction

Display:

One Flash, three second pause

Solution:

  • Verify gas pressure with rating plate on water heater.
  • Clean spark electrode and pilot hood with steel wool.
  • Inspect pilot tube for obstructions.

Error 13: Flame Lost During RUN

Indications: Flame lost during RUN: During the heating cycle, the pilot flame is lost. The control turns off the pilot and main valves, runs Inter-purge, increments the Recycle Count and, if the Recycle count limit has not been reached, begins another Trial for Ignition. If the Recycle Count Limit has been reached, the control enters soft lockout. The control remains in soft lockout for 15 minutes before responding to the Demand for Heat. This clears the Recycle Count to allow for another set of "Recycle Count Limit" recycles. A total of three such sets of ignition trials including the first ignition trial set to be attempted. If the control has entered soft lockout for the total number of ignition trials as specified above the control will enter hard lockout. This lockout can be cleared by manually cycling the control power.

Troubleshooting Steps:

  • Check pilot flame to insure flame is not lifting away from flame sense hood – when main burner ignites.
  • Check static and dynamic gas supply to insure pressure is maintained when main burner lights.
  • Check for leaking pilot supply tube.
  • Check for carbon/soot buildup on pilot grounding strap.
  • Baffle or Baffle collar is not in correct position.

Display:

Six-Three Flash, three second pause

Solution:

  • Verify gas pressure with rating plate.
  • Clean pilot supply hood to enhance flame rectification readings.
  • Reposition pilot igniter into proper position.
  • Replace pilot igniter.
  • If blower motor is hot to the touch, then inspect baffling and baffle collar.
  • Inspect baffle and baffle collar for proper positioning.

Error 14: Flame Sensed Out Of Sequence

Indications: Flame Sensed Out Of Sequence - the control only looks for pilot flame when the inducer is running. If flame is present when the pilot valve is not open, the control proceeds to Wait Flame Lost and flashes the Flame out Of Sequence error code. Blower remains on.

Troubleshooting Steps:

  • Pilot or main burner valve has failed open.

Display:

Five Flash, three second pause

Solution:

  • Recycle heater to verify error code.
  • Replace gas control valve.

Error 15: Electronics Fault Detected

Indications: Electronics fault detected - The electronic control module contains a relay for communicating with the display.

Troubleshooting Steps:

  • Panel fault.
  • Gas control fault.

Display:

Eight-Three Flash, three second pause

Solution:

  • Recycle heater to verify error code.
  • Replace display panel.
  • Replace gas control valve.

Error 31: ECO Limit Lockout

Indications: ECO limit lockout - Water temperature sensed in excess of ECO limit (199°F) - the control immediately turns off pilot and main valves and enters ECO Limit Lockout. During ECO Limit Lockout, the inducer motor runs continuously.

Troubleshooting Steps:

  • Thermal well fault (see below).
  • Gas control fault.

Display:

Four Flash, three second pause

Solution:

  • The sensed water temperature must be below 120°F.
  • Power must be cycled to remove the control from ECO limit hard lockout.

Water temperature sensor fault: Measure the OHMS resistance between pins 1 and 2; then measure the resistance between pins 3 and 2. The two numbers should be the same. See chart on last page to convert OHMS to temperature.

Diagram Description: A simple circuit diagram shows a temperature sensor with pins labeled 1, 2, 3, and ECO, connected to a multimeter measuring resistance (Ω).

Error 44: PS Failed Closed

Indications: PS Failed Closed at start of Call for Heat - the control waits four seconds then begins to flash error code (44). The control waits 2 minutes, and then turns on the inducer for 30 seconds. The inducer shuts off after 30 seconds and the control returns to waiting for the pressure switch to open. The control will attempt this sequence 5 times before entering into a hard lockout.

Troubleshooting Steps:

  • Pressure switch tube blockage.
  • Faulty pressure switch.

Display:

Two Flash, three second pause

Solution:

  • Inspect pressure switch tube for blockage.
  • Do continuity test on pressure switch. If there is continuity, replace pressure switch.
  • The hard lockout will require a manual power cycle of the control to clear the hard lockout.

Error 45: Recycle Limit - PS/Limit Opened

Indications: Recycle limit - PS/limit opened – Maximum number of retries has occurred. Unit is in hard lock-out.

Troubleshooting Steps:

  • Check venting to insure pressure switch is not momentarily opening as the appliance warms.
  • Check vent outlet for wind-gust problems.
  • Check PS wiring.
  • Check PS rubber tube for blockage.
  • Check over temp switch.
  • Faulty pressure switch.

Display:

Six-Two Flash, three second pause

Solution:

  • Correct any PVC vent issues.
  • Repair wiring or clear tube blockage.
  • Replace pressure switch.
  • The hard lockout will require a manual power cycle of the control to clear the hard lockout.

Error 46: Pressure Switch Failed Open

Indications: Pressure switch failed open (failed to close) – at the beginning of the heat cycle the control runs the inducer for 30 seconds waiting for the Pressure Switch to close. If the PS does not close in 30 seconds, the inducer turns off and the control flashes PS Failed Open error code. The control waits in this PS Failed Open mode for 2 minutes before turning on the inducer and trying for another 30 seconds to see the PS close. This cycle repeats for a maximum of five times before entering a hard lockout.

Troubleshooting Steps:

  • Vent blockage or improper installation.
  • Switch tube blockage.
  • Faulty pressure switch.
  • Blower improper operation.
  • Over temperature switch open.

Display:

Three Flash, three second pause

Solution:

  • Inspect venting run for blockage.
  • Verify over temp switch is cool to the touch.
  • Inspect pressure switch tube for blockage.
  • Check blower for proper operation.
  • Replace pressure switch.
  • The hard lockout will require a manual power cycle of the control to clear the hard lockout.

TIP: Rule out the water heater with the following process. Remove all PVC venting from the blower assy. Recycle water heater for main burner. ✓ IF the water heater goes to main burner, then the water heater is not at fault. Check venting. IF the water heater does NOT go to main burner, then we have a part problem with the water heater.

Error 47: Flammable Vapor Sensor Lockout

Indications: Flammable vapor sensor lockout - The control immediately turns off all outputs (valves closed, inducer off, ignition off). Control enters hard lockout and registers Flammable Vapor Present error code.

Troubleshooting Steps:

  • Gasoline or other flammable gas (hydrocarbons) was detected by the flammable vapor sensor.

Display:

Seven Flash, three second pause

Solution:

  • Check for flammable vapors around water heater.
  • Verify FVS sensor resistance ~ 11 KΩ -45 KΩ.
  • Replace FVS sensor if >45 KΩ.
  • Reset gas control valve. Hard lockout to be cleared when the power is manually cycled, the control dial is rotated through the HOT setting 7 times within 30 seconds and the resistance of the sensor is within the normal operation range.

Error 49: FVS Fault Detected

Indications: FVS fault detected - The control immediately turns off all outputs (valves closed, inducer off, ignition off) and enters Hardware Error Lockout and registers Flammable Vapor Device Interface/Miswiring error code.

Troubleshooting Steps:

  • Flammable vapor sensor resistance is out of range (well below or well above parameters).
  • Wiring to FV sensor is faulty (open).
  • Gas control is faulty.

Display:

Eight-One Flash, three second pause

Solution:

  • Verify FVS sensor resistance ~ 11 KΩ -45 KΩ.
  • Replace sensor and wiring harness.
  • Replace control if new sensor does not work.
  • Hard lockout will be cleared when the power is manually cycled, the control dial is rotated through the HOT setting 7 times within 30 seconds and the resistance of the sensor is within the normal operation range.

Error 89: Thermal Well Fault

Indications: Thermal well fault - Temperature Sensors not reading the same temperature within ± 5.5 °F (measure when water temperature is changing less than 1 °F/minute) - the control immediately turns off all outputs (valves closed, inducer off, ignition off) and enters Hardware Fault Lockout. Hardware Fault Lockout self clears if the fault clears for at least 15 seconds.

Troubleshooting Steps:

  • Thermal well fault.
  • Water temperature sensor fault. Measure the OHMS resistance between pins 1 and 2; then measure the resistance between pins 3 and 2. The two numbers should be the same. See chart on last page to convert OHMS to temperature.

Display:

Eight-Two Flash, three second pause

Solution:

  • Recycle power to verify error.
  • Replace thermal well.
  • Recycle power to verify error.
  • Replace thermal well.

Diagram Description: A simple circuit diagram shows a temperature sensor with pins labeled 1, 2, 3, and ECO, connected to a multimeter measuring resistance (Ω).

Error 91: Communications Error

Indications: Communications Error - when display does not detect any gas control valve. User display is periodically checking the connection to the water heater.

Troubleshooting Steps:

  • Display and gas control valve are not talking to each other.

Display:

None. Heater works without remote. This error code is for the display only.

Solution:

  • Recycle power to verify error.
  • Verify control molex correct at gas valve.

Error 93: Valve Fault Detected

Indications: Valve fault detected.

Troubleshooting Steps:

  • Gas control valve needs to be reset or has been damaged.

Display:

Eight-Four Flash, three second pause

Solution:

  • Recycle power to verify error.
  • Replace gas control.

Reset Gas Control

This will clear the current fault and force the unit to recycle for ignition.

  1. Turn temperature control knob all the way clockwise.
  2. Recycle power to the heater (both blower and gas valve).
  3. Rotate the temp knob all the way to the left, then back to the right. You must cross the midline seven (7) times to reset the gas valve.
  4. Unit should return to normal operations if all faults have been cleared and repaired. You will hear the blower motor come on.
  5. Set water temperature to a safe setting of 120°F or less.

Replacing the Gas Control

The electronic component for the gas valve is replaceable without draining the water from the tank. To replace just the electronic control portion:

  1. Turn off the blower and the gas valve. Unplug the water heater.
  2. Remove wiring harnesses from the gas valve.
  3. Remove main burner supply tube and pilot supply tube.
  4. Remove / disconnect gas supply line.
  5. Grab the bottom of the gas valve (at the main burner supply tube area) and lift up and out at the same time. There are two small plastic locking tabs that will release.
  6. The electronic component will slide up and off the thermal well still installed in the tank.
  7. Replace the control in reverse order.
  8. Reconnect fuel supply lines and tubes.
  9. Reconnect wiring harnesses.
  10. Recycle power to the water heater.
  11. Set the water temperature not to exceed 120° F.
  12. Check for safe water heater operations.

Temperature to Resistance Thermistor Chart (10kΩ Resistor)

ResistanceResistanceResistance
3232,654917,0961531,943
3434,367936,8061541,876
3632,654956,5301561,813
3731,030976,2661581,752
3929,498996,0141601,693
4128,0521005,7741621,637
4326,6861025,5461631,582
4525,3961045,3271651,530
4624,1711065,1171671,480
4823,0131084,9181691,431
5021,9131094,7271711,385
5220,8831114,5441721,340
5419,9031134,3701741,297
5518,9721154,2031761,255
5718,0901174,0421781,215
5917,2551183,8891801,177
6116,4641203,7431811,140
6315,7141223,6031831,104
6115,0001243,4691851,070
6314,3231263,3401871,037
6413,6811273,2171891,005
6613,0711293,099190974
6812,4931312,986192944
7011,9421332,878194915
7211,4181352,774196889
7310,9211362,675198861
7510,4491382,579199836
7710,0001402,488201811
799,5711422,400203787
819,1641442,315205764
828,7761452,235207742
848,4071472,157208721
868,0561492,083210700
887,7201512,011212680
907,401

Connection Diagram

The connection diagram illustrates the wiring of the PowerVent ESII with Honeywell Electronic Control. Key components and their connections are:

Wire Color Codes:

The diagram shows power inputs (120VAC, 24VAC) and how sensors (temperature, pressure) and actuators (inducer, gas valve) are wired to the electronic control.

PDF preview unavailable. Download the PDF instead.

TB 1627 Acrobat Distiller 11.0 (Windows)

Related Documents

Preview Rheem/RUUD Gas Supply Pressures and Testing Technical Service Bulletin TB-1236
Technical Service Bulletin from Rheem/RUUD (TB-1236) detailing proper gas supply pressure ranges, testing procedures, and actions required for over-pressurization events in gas water heaters and boilers.
Preview Rheem Thermal Expansion: Understanding and Preventing Water Heater Pressure Issues
Learn about thermal expansion in water heaters, the dangers of closed systems, and how Rheem's THERM-X-GUARD expansion tanks prevent dangerous pressure build-up and protect your water heater.
Preview Rheem HPWH Condensate Sensor Replacement Guide
Step-by-step instructions for replacing the condensate sensor in a Rheem Heat Pump Water Heater (HPWH), including visual descriptions.
Preview Rheem/RUUD Pilot Outage Troubleshooting Guide
Comprehensive troubleshooting guide for Rheem and RUUD water heaters experiencing pilot outage issues. Covers mechanical checks, fuel, combustion air, environmental factors, and venting.
Preview Rheem FV Sensor SP20172 Low Resistance Troubleshooting and Replacement Guide
Technical service bulletin from Rheem detailing how to diagnose and replace the FV Sensor SP20172 when experiencing low resistance issues leading to water heater valve lock-out. Includes troubleshooting steps and resistance specifications.
Preview Rheem HPWH-A108 Condensate Blocked: Troubleshooting Guide
Rheem Technical Service Bulletin for HPWH-A108 heat pump water heaters addressing the A108 condensate blocked alarm. Provides explanations, common causes, and detailed troubleshooting steps for technicians.
Preview Rheem ULN Residential Gas Atmospheric Heater Pilot Assembly Positioning Guide - TB-1443
Technical Service Bulletin TB-1443 from Rheem provides instructions on the proper positioning of the pilot assembly for ULN Residential Gas Atmospheric heaters to prevent pilot outages and ensure correct burner operation. Includes measurements and troubleshooting tips.
Preview Rheem 4 Star Gas 90L Water Heater (Model 347090) - Specifications and Features
Detailed specifications, features, and dimensions for the Rheem 4 Star Gas 90L water heater, model 347090. Includes energy efficiency, recovery rate, gas consumption, and connection sizes.