Rheem HPWH-A108: Understanding and Resolving Condensate Blocked Alarms

This technical service bulletin from Rheem addresses the common A108 alarm for the HPWH-A108 Heat Pump Water Heater, which indicates a condensate blockage.

Contact Rheem Technical Service: 1-800-432-8373

What is the A108 Alarm?

The A108 alarm signifies that the condensate rope sensor has become wet. This typically occurs when condensation, generated during the heat pump's operation, cannot drain properly due to a blockage in the condensate drain line or pan. This leads to water backing up and triggering the sensor.

Common Causes Identified

Troubleshooting Overview

This bulletin outlines essential troubleshooting steps to diagnose and resolve the A108 alarm. Key actions include:

Necessary tools for these procedures include a flathead and a Philips head screwdriver.

PDF preview unavailable. Download the PDF instead.

TB 1332 - Possible Causes A108 TB Microsoft Word 2016 Microsoft Word 2016

Related Documents

Preview Rheem A108 Water Heater: Troubleshooting Blocked Condensate Line and Sensor Replacement
Technical service bulletin from Rheem Water Heating providing instructions for troubleshooting blocked condensate lines in A108 water heaters and guidance on replacing the condensate sensor.
Preview Rheem HPWH Condensate Sensor Replacement Guide
Step-by-step instructions for replacing the condensate sensor in a Rheem Heat Pump Water Heater (HPWH), including visual descriptions.
Preview Rheem Expansion Tank Installation Guide and Sizing
Comprehensive guide for installing Rheem expansion tanks, detailing pre-installation checks, step-by-step installation procedures, system diagram descriptions, and essential sizing tables. Includes important safety cautions for proper setup.
Preview Rheem/RUUD Pilot Outage Troubleshooting Guide
Comprehensive troubleshooting guide for Rheem and RUUD water heaters experiencing pilot outage issues. Covers mechanical checks, fuel, combustion air, environmental factors, and venting.
Preview Rheem FV Sensor SP20172 Low Resistance Troubleshooting and Replacement Guide
Technical service bulletin from Rheem detailing how to diagnose and replace the FV Sensor SP20172 when experiencing low resistance issues leading to water heater valve lock-out. Includes troubleshooting steps and resistance specifications.
Preview Rheem ULN Residential Gas Atmospheric Heater Pilot Assembly Positioning Guide - TB-1443
Technical Service Bulletin TB-1443 from Rheem provides instructions on the proper positioning of the pilot assembly for ULN Residential Gas Atmospheric heaters to prevent pilot outages and ensure correct burner operation. Includes measurements and troubleshooting tips.
Preview Rheem Commercial W2W Heat Pump Water Heater: Owners Guide and Installation Instructions
Comprehensive guide for Rheem Commercial Water to Water (W2W) Heat Pump Water Heater, detailing installation, operation, maintenance, troubleshooting, and warranty. Includes model WMKA21549 and other Rheem W2W models.
Preview Rheem Commercial Air to Water Heat Pump Water Heater Owners Guide and Installation Instructions WMKA21549
Official owners guide and installation instructions for the Rheem WMKA21549 commercial air-to-water heat pump water heater. Covers installation, operation, maintenance, safety, and troubleshooting for optimal performance.