Lennox MWMD018S6-1P (RNX18ABD) For Multi-Zone Systems - Wall-Mount Unit
This document provides submittal data for the Lennox MWMD018S6-1P Wall-Mount Unit, designed for Multi-Zone Systems.
General Information
The indoor unit features a 'calm air' mode that disperses air through micro-holes on the front of the unit, preventing cold drafts on occupants when in cooling mode. The unit has integral Wi-Fi capability as standard. It requires a 208/230V power supply from the outdoor unit via a 14 AWG X 3 interconnect power cable. A built-in motion sensor is included for airflow direction control and energy-saving operation.
Construction
- The indoor unit chassis is UL94 V0 rated and includes a galvanized steel mounting bracket.
- An access panel on the bottom of the unit provides easy access for wire, pipe, and drain connections, simplifying installation and service.
Refrigerant System
- The heat exchanger features a mechanically bonded fin to copper tube design.
- Refrigerant flow is controlled by an electronic expansion valve located at the outdoor unit.
Indoor Fan
- The indoor fan is a single, antibacterial cross-flow type.
- It offers three fan speeds and an auto setting.
- Automatic motorized louvers provide vertical (up/down) and horizontal (left/right) swing.
Controls
- The indoor unit includes a rechargeable, solar-cell wireless controller with a holder. The controller can be charged via a USB C cable or the integral solar panel.
- The wireless controller features a pixel display that is visible in low light conditions.
- A built-in Wi-Fi adapter allows for control and monitoring using the Samsung SmartThings app.
- Dual set temperature support is available when connected to supported wired controllers.
- The indoor unit has a connection for condensate overflow detection devices or any normally closed contact for simple unit shutdown.
- The interconnect control wire between the outdoor and indoor unit is 16AWG X 2.
Convenience
- A 7-segment digital display on the front of the unit shows temperature and unit status.
- A washable main filter is accessible from the top of the unit.
- Unit energy consumption can be monitored via the Samsung SmartThings mobile app (conditions apply).
- AI (Artificial Intelligence) Auto Mode technology learns user patterns to automatically adjust system operation for optimal comfort and efficiency, requiring a Wi-Fi connection.
- AI Energy mode technology enhances energy saving through advanced compressor control techniques.
- Additional features include: Auto changeover, Auto Clean Function, MAX mode for rapid temperature adjustment, Good'sleep mode, Quiet mode, Dry mode, Simple ON/OFF time function (via wireless controller), and a filter cleaning reminder.
Specifications
Model | Model Number | MWMD018S6-1P |
Performance | Nominal Capacity Cooling (Btu/h) | 18,500 |
Nominal Capacity Heating (Btu/h) | 20,000 | |
Power | Voltage Ø/V/Hz | 1/208-230/60 |
Operating Current (max.) Cooling (A) | 0.5 | |
Operating Current (max.) Heating (A) | 0.5 | |
Evaporator Fan | Type | BLDC motor with cross-flow fan |
FLA Amps | 0.12 | |
Consumption | Watts | 27 |
Airflow | Air Volume (L/M/H/Turbo) Cooling (CFM) | 427/481/536/572 |
Air Volume (L/M/H/Turbo) Heating (CFM) | 447/501/556/592 | |
Refrigerant | Type | R-32 |
A2L Leak Detection | Not Included | |
Pipe Connections | Indoor & Outdoor High side (In.) | 1/4 |
Indoor & Outdoor Low side (In.) | 1/2 | |
Condensate Connection | In. | 11/16" OD |
Dimensions | W X H X D In. | 41 9/16 X 11 3/4 X 8 7/16 |
Weight lbs. | 27.30 | |
Operating Temperatures | Indoor Cooling | 64~90°F (16~32°C) |
Indoor Heating | T ≤ 86°F (30°C) | |
Sound Pressure Level | Silent / High dB(A) | 28/42 |
Safety | Certifications | UL 60335-2-40 |
Accessories
- Condensate pump: Blue Diamond MaxiBlue (X87-721), Blue Diamond MicroBlue w/slim fascia kit (X86-003)
- Wired controller (sub-PCB model VSTAT06P-1 is required): Advanced (X86-011), Touchscreen (VSTAT04P-1)
- Wired controller sub-PCB: (VSTAT02P-1)
- 24 VAC Thermostat adapter (sub-PCB model VSTAT06P-1 is required): (VSTAT06P-1)
- External temperature sensor: (VSTAT09P-1)
- External contact control interface module (sub-PCB model VSTAT06P-1 is required): (VCTRL11P-1, VSTAT10P-1)
Lennox maintains a policy of ongoing development. Specifications are subject to change without notice. Refer to www.AHRIdirectory.org for current reference numbers.
Intertek certification mark indicates compliance with relevant safety standards.