Lennox MWMD018S6-1P (RNX18ABD) For Multi-Zone Systems - Wall-Mount Unit

This document provides submittal data for the Lennox MWMD018S6-1P Wall-Mount Unit, designed for Multi-Zone Systems.

General Information

The indoor unit features a 'calm air' mode that disperses air through micro-holes on the front of the unit, preventing cold drafts on occupants when in cooling mode. The unit has integral Wi-Fi capability as standard. It requires a 208/230V power supply from the outdoor unit via a 14 AWG X 3 interconnect power cable. A built-in motion sensor is included for airflow direction control and energy-saving operation.

Construction

  • The indoor unit chassis is UL94 V0 rated and includes a galvanized steel mounting bracket.
  • An access panel on the bottom of the unit provides easy access for wire, pipe, and drain connections, simplifying installation and service.

Refrigerant System

  • The heat exchanger features a mechanically bonded fin to copper tube design.
  • Refrigerant flow is controlled by an electronic expansion valve located at the outdoor unit.

Indoor Fan

  • The indoor fan is a single, antibacterial cross-flow type.
  • It offers three fan speeds and an auto setting.
  • Automatic motorized louvers provide vertical (up/down) and horizontal (left/right) swing.

Controls

  • The indoor unit includes a rechargeable, solar-cell wireless controller with a holder. The controller can be charged via a USB C cable or the integral solar panel.
  • The wireless controller features a pixel display that is visible in low light conditions.
  • A built-in Wi-Fi adapter allows for control and monitoring using the Samsung SmartThings app.
  • Dual set temperature support is available when connected to supported wired controllers.
  • The indoor unit has a connection for condensate overflow detection devices or any normally closed contact for simple unit shutdown.
  • The interconnect control wire between the outdoor and indoor unit is 16AWG X 2.

Convenience

  • A 7-segment digital display on the front of the unit shows temperature and unit status.
  • A washable main filter is accessible from the top of the unit.
  • Unit energy consumption can be monitored via the Samsung SmartThings mobile app (conditions apply).
  • AI (Artificial Intelligence) Auto Mode technology learns user patterns to automatically adjust system operation for optimal comfort and efficiency, requiring a Wi-Fi connection.
  • AI Energy mode technology enhances energy saving through advanced compressor control techniques.
  • Additional features include: Auto changeover, Auto Clean Function, MAX mode for rapid temperature adjustment, Good'sleep mode, Quiet mode, Dry mode, Simple ON/OFF time function (via wireless controller), and a filter cleaning reminder.

Specifications

ModelModel NumberMWMD018S6-1P
PerformanceNominal Capacity Cooling (Btu/h)18,500
Nominal Capacity Heating (Btu/h)20,000
PowerVoltage Ø/V/Hz1/208-230/60
Operating Current (max.) Cooling (A)0.5
Operating Current (max.) Heating (A)0.5
Evaporator FanTypeBLDC motor with cross-flow fan
FLA Amps0.12
ConsumptionWatts27
AirflowAir Volume (L/M/H/Turbo) Cooling (CFM)427/481/536/572
Air Volume (L/M/H/Turbo) Heating (CFM)447/501/556/592
RefrigerantTypeR-32
A2L Leak DetectionNot Included
Pipe ConnectionsIndoor & Outdoor High side (In.)1/4
Indoor & Outdoor Low side (In.)1/2
Condensate ConnectionIn.11/16" OD
DimensionsW X H X D In.41 9/16 X 11 3/4 X 8 7/16
Weight lbs.27.30
Operating TemperaturesIndoor Cooling64~90°F (16~32°C)
Indoor HeatingT ≤ 86°F (30°C)
Sound Pressure LevelSilent / High dB(A)28/42
SafetyCertificationsUL 60335-2-40

Accessories

  • Condensate pump: Blue Diamond MaxiBlue (X87-721), Blue Diamond MicroBlue w/slim fascia kit (X86-003)
  • Wired controller (sub-PCB model VSTAT06P-1 is required): Advanced (X86-011), Touchscreen (VSTAT04P-1)
  • Wired controller sub-PCB: (VSTAT02P-1)
  • 24 VAC Thermostat adapter (sub-PCB model VSTAT06P-1 is required): (VSTAT06P-1)
  • External temperature sensor: (VSTAT09P-1)
  • External contact control interface module (sub-PCB model VSTAT06P-1 is required): (VCTRL11P-1, VSTAT10P-1)

Lennox maintains a policy of ongoing development. Specifications are subject to change without notice. Refer to www.AHRIdirectory.org for current reference numbers.

Intertek certification mark indicates compliance with relevant safety standards.

PDF preview unavailable. Download the PDF instead.

sbmtl mwmd018s6-1p 2506 Adobe PDF Library 17.0 Adobe InDesign 20.4 (Windows)

Related Documents

Preview Lennox Mini-Split Installation Manual
Comprehensive installation manual for Lennox Mini-Split systems, model series MM*D***S6M-1P. Includes safety precautions, step-by-step installation procedures, and troubleshooting for optimal performance.
Preview Lennox MMDD018S6-1P Medium Static Ducted Unit Submittal Data
Submittal data for the Lennox MMDD018S6-1P Medium Static Ducted Unit, featuring detailed specifications, general information, construction details, refrigerant system information, indoor fan capabilities, controls, external heat control, and convenience features. Includes dimensional drawings and accessory options.
Preview Lennox MPC018S4S-1P / MMA018SM4-1P Single Zone Mini-Split Heat Pump Submittal Data
Submittal data for the Lennox MPC018S4S-1P outdoor unit and MMA018SM4-1P indoor unit, a single zone mini-split heat pump system. Includes features, specifications, dimensions, and warranty information.
Preview Lennox M22D018S6-1P 4-Way Cassette Unit Submittal Data
Detailed submittal data for the Lennox M22D018S6-1P 4-Way (2x2) Cassette Unit for multi-zone systems. Includes general information, construction details, refrigerant system specifications, fan capabilities, control options, external heat control features, and convenience functions like Emergency Temperature Output (ETO). Also provides performance specifications, dimensions, and available accessories.
Preview Lennox Mini-Split Installation Manual for MM*D***S6S-1P Systems
Comprehensive installation manual for Lennox mini-split air conditioning systems, model series MM*D***S6S-1P. Includes safety guidelines, installation procedures, troubleshooting, and maintenance information.
Preview Lennox M22D009S6-1P (CNG09NDD) 4-Way Cassette Unit Submittal Data
Submittal data for the Lennox M22D009S6-1P (CNG09NDD) multi-zone 4-way cassette air conditioning unit, including specifications, features, and dimensional drawings.
Preview Lennox Mini-Split Installation Manual for MWHD/MWLD/MWPD Outdoor and MWHD/MWMD Indoor Units
This installation manual provides detailed instructions and safety guidelines for installing Lennox Mini-Split systems, including MWHD/MWLD/MWPD outdoor and MWHD/MWMD indoor units. It covers preparation, unit installation, inspection, testing, and option settings.
Preview Lennox MMDD012S6-1P (CNG12LDD) Medium Static Ducted Unit Submittal Data
Submittal data for the Lennox MMDD012S6-1P (CNG12LDD) Medium Static Ducted Unit, detailing its specifications, features, and accessories. This unit offers high heating capacity, comfort humidity control, and Wi-Fi connectivity.