Danfoss ERC 213 Electronic Refrigeration Control
Installation Guide
1. Technical Highlights
- Ease of use: Four buttons, easy menu structure, pre-installed application solutions ensure superior usability.
- Simple installation: High performance 16 A relay enables direct connection of heavy loads, such as 2 hp compressors, without use of intermediate relays. A wide range of compatible types of sensors and screw connection terminals ensure high flexibility in installation.
- Unit protection: Special software features like compressor protection from fluctuation in power supply or from high condensing temperature ensure the safety operation of the unit.
- Energy efficiency: Defrost on demand, day/night mode and smart evaporator fan management ensure energy efficiency.
2. User Interface
Key Function
- Scroll up: Short press (less than 1 second).
- Main switch ON/OFF: Press and hold (~ 3 seconds).
- Factory reset: Press and hold at Power up.
- Scroll down: Short press (less than 1 sec.).
- Defrost Start/Stop: Press and hold (~3 secs.).
- Back function: Short press (less than 1 sec.).
- Pull down start / stop: Press and hold (~3 secs.).
- Set point change or OK: Short press (less than 1 sec.).
- Enter Menu: Press and hold (~ 3 secs.).
Display Icons
- (?) Night mode (Energy saving)
- ? Fan running
- ⚙️ Compressor running (Flashes in pull-down mode)
- ❗ Active alarm
- ❄️ Defrost
- °C Unit (°C or °F)
3. Dimensions (mm) and mounting
[Diagram showing dimensions and mounting instructions, including drilling template and rear mounting clip mechanism.]
4. Electrical connections
[Diagram showing electrical connections for power supply, sensors, and digital inputs/outputs.]
Note: 2L and 3L must be connected to the same phase.
Power connectors: wire size = 0.5 - 1.5 mm², max. tightening torque = 0.4 Nm
Low voltage signal connectors: wire size = 0.15 – 1.5 mm², max. tightening torque = 0.2 Nm
5. Quick configuration at power up
- STEP 1: power on
- STEP 2: select the quick configuration menu: Within 30 seconds of power on, press "<" BACK for 3 seconds. The main switch "r12" is automatically set to OFF.
- STEP 3: select pre-installed application: The display automatically shows the application selection parameter "061". Press SET to select the pre-installed application. The display shows the default value (e.g., "APO" flashing). Choose the application type by pressing UP/DOWN and press SET to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters.
- STEP 4: select sensor type: The display automatically shows sensor selection parameter "006". Press SET to select the sensor type. The display shows the default value (e.g., "n10" flashing). Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm. Note: All sensors must be the same type.
- STEP 5: configure DO2 output: The display automatically shows the "o71" parameter to configure "DO2" output. Select required configuration (DEF or Lig or ALA) as per the application and press SET to confirm. The display returns to normal display mode and the control is started.
6. Quick Configuration via "cFg" Menu
- Press "SET" button for 3 seconds to access the parameter menu (display will show "cFg").
- Enter "CFg" menu by pressing "SET" button (display will show first parameter "r12" main switch).
- Select "r12" by pressing "SET" button again and set the main switch to "OFF" (r12=0).
- Press back button ("<") to come back to 'CFg" menu.
- Press DOWN button to scroll through the "cFg" menu parameter list.
- Open the "061 application mode" and select needed application mode (Press SET).
- Open the "007 Cooling/Heating" and select needed function and press "SET" (applicable only for APO and AP5).
- Open the "006 Sensor type" and select the temperature sensor type used (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000)- (Press "SET").
- Open the "071 DO2 configuration" and select the function associated to DO2 output and press "SET".
- Open the "002 DI1 Configuration" and select the function associated to digital input 1 (Press "SET").
- Open the "037 DI2 Configuration" and select the function associated to digital input 2 (Press "SET").
- Navigate back to parameter "r12 Main switch" and set it in "ON" position to start control.
- Go through other parameters default settings and change wherever needed.
7. Technical specifications
Features | Description |
---|---|
Purpose of control | Operating temperature sensing control suitable for incorporation into commercial air conditioning and refrigeration applications |
Construction of control | Incorporated control |
Power supply | 115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply |
Rated power | Less than 0.7 W |
Inputs | Sensor inputs, Digital inputs, Programming key. Connected to SELV limited energy <15 W |
Allowed sensors types | NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C - EKS 211) NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C - EKS 221) PTC 990 Ohm at 25 °C, (EKS 111) Pt1000, (AKS 11, AKS 12, AKS 21) |
Sensors included in Kit Solution | NTC 10000 Ohm at 25 °C, cable length: 1.5 m |
Accuracy | Measuring range: -40 – 105 °C (-40 – 221 °F) Controller accuracy: ±1 K below -35 °C, ±0.5 K between -35 – 25 °C, ±1 K above 25 °C |
Type of action | 1B (relay) |
Output DO1 - Relay 1 | 16 A, 16 (16) A, EN 60730 10 FLA/60 LRA at 230 V, UL60730 16 FLA/72 LRA at 115 V, UL60730 |
Output DO2 - Relay 2 | 8 A, 2 FLA/12 LRA, UL60730 8 A, 2 (2 A), EN60730 |
Output DO3 - Relay 3 | 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1 |
Display | LED display, 3 digits, decimal point and multi function icons, °C + °F scale |
Operating conditions | -10 – +55 °C (14 – 131 °F), 90% Rh |
Storage conditions | -40 – +70 °C (-40 – +158 °F), 90% Rh |
Protection | Front: IP65 (Gasket integrated) Rear: IP00 |
Environmental | Pollution degree II, non-condensing |
Overvoltage category | II - 230 V supply version - (CE, UL recognized) III - 115 V supply version - (UL recognized) |
Resistance to heat and fire | UL94-V0 |
Temperature for ball pressure test statement | According to Annex G (EN 60730-1) |
EMC category | Emission: IEC/EN 61000 6-3 Immunity: IEC/EN 61000 6-2 |
Approvals | UL recognition (US & Canada) (UL 60730-1) CQC CE (LVD & EMC Directive) EAC NSF ROHS2.0 HACCP temperature monitoring in compliance with EN13485 Class I, when used with AKS 12 sensor |
8. Parameter List
[Table detailing various parameters, their codes, ranges, and default settings for different applications (AP0-AP7). This includes configuration, alarm settings, defrost, fan control, compressor settings, and other miscellaneous parameters.]
Safety Standards: Check if the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: Use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation.
Disposal of the Product: The appliance (or the product) must be disposed in accordance with the local waste disposal legislation.
EU design registration: 002566703-0001