Rinnai Tankless Water Heater Performance and Diagnostics

Model Series: RE199e, RE180e, RE160e, RE140e

Performance Data

To Obtain Performance Data:

  1. Press and hold the [Down] button.
  2. While holding the [Down] button for 2 seconds, press and hold the [On/Off] button (hold both buttons simultaneously).
  3. Use the [Up] and [Down] buttons to scroll to the desired performance information.

Performance Data Table

ParameterUnitDisplay Range
Water Flow Ratex0.1 gal/min0 to 999
Outgoing Temperature°F10° to 99°
Combustion Hoursx100 Hours-- to 6--
Combustion CyclesCYCLE COUNT x1000 to 99,900
Fan FrequencyHzCYCLE COUNT x10,000100,000 to 990,000
Additional Controllers ConnectedSee following informationCYCLE COUNT x1,000,0001,000,000 to 6,000,000
Water Flow Control Position0=Mid, 1=Open, 2=Closed
Inlet Temperature°F
Fan CurrentmA
Total Bath Fill Amountgallons
HEX Outlet Temperature°F
By-Pass Flow Control PositionDegrees of opening
Intake Thermistor Temperature (Indoor Units Only)°F
Freeze Protection Temperature (Outdoor Units Only)°F
Pump Hoursx100 Hours
Pump CyclesSee following information

Note on Cycle Counts:

Controller Connection Status:

Default display is 100. '_' depends on connection status of another controller.

Parameter Settings

To Adjust the Parameters:

  1. Press the [A] button for 1 second.
  2. Use the [Up] and [Down] buttons on the controller to select a setting number (See Parameter Settings Table).
  3. Once the desired setting number is selected, use the [On/Off] button on the controller to change the selection for the setting number. Example: Display will change from 01A to 01b for Maximum Temperature setting.
  4. To exit the parameters, press the [A] button on the PC board for 1 second.

Parameter Settings Table

Setting #DescriptionSelection Options
01Maximum Set Temperature120°F, 140°F
02High Altitude (Installation Location)0 - 2,000 ft (0 - 610 m), 2,001 - 5,400 ft (610 - 1,646 m), 5,401 - 7,700 ft (1,646 - 2,347 m), 7,701 - 10,200 ft (2,347 - 3,109 m)
03Service SoonDisabled, 0.5 Year, 1 Year, 2 Years
04Recirculation SettingsNo Recirculation, Recirculation (Dedicated)
05Recirculation ModeEconomy, Comfort
06Control SwitchBMS, Air Handler (AH)
07Units in Standby2, 1
10Gas Type (Factory Set)LPG, NG
12Water Heater ModelWithout Pump, With Pump
13(Factory set values and not adjustable)199/160
14Indoor / Outdoor180/140
15Low Activation ModeOn, Off
18Setting Temperature TableDefault, Alternate 1.8°F (1°C), 3.6°F (2°C), 5.4°F (3°C)
19Vent LengthLong, Short
99Adjust DHW Temperature Setting0°F (0°C)

Manifold Pressure Settings

Ensure gas pressure check under Commissioning has been completed first. The regulator is electronically controlled and factory pre-set. Adjustments are typically not required unless the unit is not operating correctly and all other possible causes have been eliminated.

Procedure:

  1. Turn off the gas supply.
  2. Turn off the 120 V power supply.
  3. Remove the front panel from the appliance.
  4. Turn on the 120 V power supply.
  5. Check the gas type using the data plate on the side of the unit and parameter setting 10 (A=LPG, b=NG).
  6. Remove sealing screw and attach the manometer to the burner test point on the manifold.
  7. Turn on the gas supply.
  8. Flow water through the water heater at the maximum flow rate obtainable (at least 3 gallons per minute recommended to prevent shut-off or damage).
  9. Press and hold the [B] button. "IF" will appear on the display.
  10. Press and hold the [A] button. "Forced Low" will appear on the display.
  11. Press and hold the [A] button again. "Forced High" will appear on the display.
  12. While in "Forced Low" or "Forced High", use the [Up] button to increase pressure and the [Down] button to decrease pressure.
  13. To exit "Forced Low" or "Forced High", press and hold the [B] button. "2L" will appear on the display.
  14. Press and hold the [B] button again. "3C" will appear on the display (Indoor models only).
  15. Press and hold the [B] button again. "4t" will appear on the display.
  16. Press and hold the [B] button again. The set temperature will appear on the display (indoor models only).
  17. Close hot water taps.
  18. Turn off the gas supply and 120 V power supply.
  19. Remove the manometer and re-install sealing screw.
  20. Turn on the gas supply and 120 V power supply.
  21. Operate the unit and check for gas leaks.
  22. Install the front panel.

Note: For additional installation and commissioning information, refer to the Installation and Operation Manual.

WARNING: This appliance must be installed, serviced and removed by a trained and qualified person. During pressure testing of the consumer piping, ensure the gas valve is turned off before the unit is shut off. Failure to do so may result in serious injury or damage.

Commissioning Gas Pressure Requirements

With all gas appliances in operation at maximum gas rate, the following inlet gas pressure at the incoming test point on the Rinnai water heater should read:

If the pressure is lower, the gas supply is inadequate. Check the gas meter regulator and pipework for correct operation/sizing and correct as required.

Model #Min./Max. Inlet PressureMaximum Gas Supply Pressure
NG (inH₂O)LPG (inH₂O)NG (inH₂O)LPG (inH₂O)
RE199e4.08.010.513.0
RE180e4.08.010.513.0
RE160e4.08.010.513.0
RE140e4.08.010.513.0
(FL) Forced Low0.621.022.524.31
(FH) Forced High0.640.992.714.23

Note: The table seems to have a slight discrepancy in how the "Forced Low" and "Forced High" values are presented relative to the model numbers. The provided text lists them separately. I will present them as they appear.

Electrical Diagnostics

Visit www.rinnai-lms.com for additional troubleshooting resources.

Note: Wiring diagram is available in the manual and on the inside front cover.

Important Safety Notes: Live tests are required. Proceed with caution to avoid contact with energized components. Only trained and qualified service technicians should attempt repair. Before checking resistance, disconnect power and isolate the component.

Component Testing

Typical Thermistor Resistance Readings

TemperatureResistance Readings
59°F11.4 - 14KΩ
86°F6.4 - 7.8KΩ
113°F3.6 - 4.5KΩ
140°F2.2 - 2.7KΩ
221°F0.6 - 0.8KΩ

Electrical Circuit Table

ComponentWire ColourVoltageResistancePCB Connector PIN
Power SupplyBlack-WhiteAC108-132VN/A
Flame RodYellow-Bodymore than 0.5VACN/ACN9
Spark ElectrodePink-Bodymore than 0.5VACN/ACN9
Combustion FanWhite-Black11-14VDC*N/ACN7
Water Flow Control DeviceYellow-Black7-8VDC*N/ACN9
Inlet TemperatureRed-Black2-14VDC*N/ACN9
Fan CurrentWhite-Black1-14VDCN/ACN9
Total Bath Fill AmountYellow-Blacklimitter On<1VDCN/ACN9
HEX Outlet TemperatureRed-Pinklimitter Off 4-6VDCN/ACN9
By-Pass Flow Control Device (RE199, RE180 model only)Blue-WhiteN/A40-60ΩCN9
Main Solenoid ValveBlack-Black8-13.5VDC40-60ΩCN7
Modulating Solenoid ValveYellow-Yellow2-17VDC*10-20ΩCN7
Solenoid Valve 1Blue-Black8-13.5VDC20-30ΩCN7
Solenoid Valve 2Yellow-Black8-13.5VDC20-30ΩCN9
Solenoid Valve 3Red-Black8-13.5VDC20-30ΩCN9
Solenoid Valve 4 (RE/REP199, RE180 model only)Orange-Black8-13.5VDC20-30ΩCN9
Outgoing Water ThermistorWhite-White59°F: 11.4-14kΩ
86°F: 6.4-7.8kΩ
113°F: 3.6-4.5kΩ
140°F: 2.2-2.7kΩ
221°F: 0.6-0.8kΩ
Disconnect connector, measure at thermistor side.CN9
Inlet ThermistorWhite-White32°F: 38k-43kΩ
50°F: 22k-26kΩ
68°F: 14k-17kΩ
Disconnect connector, measure at thermistor side.CN9
Heat Exchanger ThermistorWhite-WhiteCN9
Intake Thermistor (Indoor type only)White-WhiteCN9
Freeze Protection Thermistor (Outdoor type only)White-WhiteCN7
Overheat SwitchBlack-Blackless than 1VDCN/ACN7
Water Flow SensorYellow-Black4-7VDC*N/ACN9
Integrated PumpWhite-BlackAC108-132VN/AC101
External Pump (Except for integrated pump and RE140 model)White-BlackAC108-132V*N/ACN8
Additional Controller(s)White-White1-14VDCN/ACN4
Thermal FuseWhite-Whiteless than 1VDCN/ACN9

(* Value to be measured while unit is in operation)

Diagnostic Codes Display

To Display Diagnostic Codes:

  1. Turn off the water heater using the [On/Off] button.
  2. Press and hold the [On/Off] button for 2 seconds, then press and hold the [Up] button simultaneously.
  3. The last 9 maintenance codes will display and flash sequentially.
  4. To exit diagnostic codes and return to normal operation, press and hold the [On/Off] button for 2 seconds, then press and hold the [Up] button simultaneously.
  5. Turn on the water heater using the [On/Off] button.

Troubleshooting Diagnostic Codes

Code 1 0: Air Supply or Exhaust Blockage

Code 1 1: No Ignition (Heater Not Turning On)

Code 1 2: No Flame

Code 1 4: Thermal Fuse

Code 1 6: High Outgoing Temperature

Code 1 9: Electrical Grounding

Code 32: Outgoing Water Temperature Thermistor

Code 33: Heat Exchanger Thermistor

Code 34: Combustion Air Temperature Thermistor Fault

Code 41: Freeze Protection Thermistor

Code 51: Inlet Water Temperature Thermistor

Code 52: Modulating Solenoid Valve Signal

Code 6 1: Combustion Fan

Code 6 3: Recirculation Low Flow

Code 6 5: Water Flow Servo

Code 6 6: Bypass Flow Servo

Code 7 0: PC Board

Code 7 1: Solenoid Valve Circuit

Code 7 2: Flame Sensing Device

Code 7 9: Water Leak Detected

Code LC: Scale Build-up in Heat Exchanger (When checking maintenance code history, "00" is substituted for "LC")

Code SS: Service Soon (Flush Heat Exchanger)

NO CODE: Nothing happens when water flow is activated

Code FF: Maintenance Indicator

Parts List

Thermal Fuse Location: When replacing the heat exchanger, the thermal fuse must be properly installed and secured. The illustration shows the general placement of thermal fuses on the heat exchanger flanges.

The following table lists replacement parts for Rinnai models RE199e, RE180e, RE160e, and RE140e.

Item #DescriptionPart NumberRE199eRE180eRE160eRE140eItem #DescriptionPart NumberRE199eRE180eRE160eRE140eItem #DescriptionPart NumberRE199eRE180eRE160eRE140e
002Wall Bracket1090002811111135Flue Outlet1020000681111405Plug Band1090000181111
004Reinforcement Plate1090012482211135Flue Outlet - Small1020000691111406Ø16 Pipe Bracket1090012851111
005Heat Protection Plate1090012491111136Bellmouth1090012781111408Hot Water Outlet (3/4 NPT)1070000921111
006Front Panel1090012511111137Seal Packing10900128011409Stop Bracket1090012861111
007Front Panel Upper Packing1090012521111137Seal Packing - Small10900128111410Gas Pipe Bracket1090006351111
008Front Panel Lower Packing1090012531111138Front Panel Seal Packing1090012821111411Bracket1090012871111
009Temperature Control1050020101111143Heat Exchanger Assembly10400031311412Filter AssemblyH98-510-S1111
010Temperature Control Plate1090012551111143Heat Exchanger Assembly - Small10400031511413Cover1070000932211
013Thermistor Packing1090012571111400Water Inlet1070006141111415Hot Water Pipe Assembly10700061611
016Earth Plate1090012581111401Water Flow Servo & Sensor1050009571111415Hot and Cold Water Pipe Assembly10700061711
017Latch Hook1090012591111402RectifierM8D1-151111416Cold Water Pipe Assembly1070006201111
018Latch1090012601111403By-pass Servo Assembly10500095811417Clip10900012881111
019Clamp Fixing Plate1090012611111404Pipe Bracket1090012842222418Clip1090002441111
020Clamp1090012621111405Plug Band1090000181111460Water Flow Turbine10700062111
021Rubber Stop1090006341111406Ø16 Pipe Bracket1090012851111461Water Flow Turbine1070000881111
022Rubber Stop1090012621111408Hot Water Outlet (3/4 NPT)1070000921111478Clip1090006361111
100Gas Control Assembly1060002481111409Stop Bracket1090012861111700PC Board - Large10500095911
101Test Port Set ScrewC10D-51111410Gas Pipe Bracket1090006351111700PC Board - Small1050009601
1023/4 Gas Inlet1060001191111411Bracket1090012871111700PC Board - Small 1401050009611
103Burner Unit Assembly1060002492222412Filter AssemblyH98-510-S1111702Cover1090012921111
103Burner Unit Assembly - Small1060002502222413Cover1070000932211706Ignitor1050009631111
104Combustion Gasket1090009731111415Hot Water Pipe Assembly10700061611707High Tension Cord1050009641111
104Combustion Gasket- Small1090009741111415Hot and Cold Water Pipe Assembly10700061711708Electrode SleeveAU206-2182222
105Gas Pipe1060002512222416Cold Water Pipe Assembly1070006201111709Water Inlet Thermistor8050000811111
110Manifold Assembly - LPG1060002521111417Clip10900012881111710Heat Exchanger Thermistor1050009651111
110Manifold Assembly - NG1060002531111418Clip1090002441111711Clip1050000901111
110Manifold Assembly - LPG1060002541111460Water Flow Turbine10700062111714Fuse Holder1090012951111
110Manifold Assembly - NG1060002551111461Water Flow Turbine1070000881111715Fuse Holder1090007861111
111Manifold Upper Packing1060002561111478Clip1090006361111716Heater ClipAU124-618X013333
111Manifold Upper Packing - Small1060002571111700PC Board - Large10500095911717Heater Clip1090007952222
112Manifold Lower Packing1060002581111700PC Board - Small1050009601718Heater ClipU250-6252222
112Manifold Lower Packing - Small1060002591111700PC Board - Small 1401050009611719Gas Control Harness1050009661111
113Top Side Reinforcement1060002601111702Cover1090012921111724Sensor Harness - 210500096911
116Electrode1090012641111706Ignitor1050009631111724Sensor Harness - 410500097111
117Flame Rod1050009531111707High Tension Cord1050009641111725Fuse Harness - 110500097611
118Electrode Bracket - Right1050009541111708Electrode SleeveAU206-2182222725Fuse Harness - 210500097711
119Electrode Packing1050009551111709Water Inlet Thermistor8050000811111726Power Supply Harness - 21050009791111
120Electrode Bracket - Left1050009561111710Heat Exchanger Thermistor1050009651111728Ignitor Bracket1090012961111
123Electrode Bracket Assembly1050009571111711Clip1050000901111729Cable Clip1090012971111
124Fan Motor Assembly1050009581111714Fuse Holder1090012951111730Twin Thermistor10500098211
125Fan Motor1050009591111715Fuse Holder1090007861111731Solenoid Harness1050009831111
126Fan Casing1050009601111716Heater ClipAU124-618X013333731Solenoid Harness - Small10500098411
128Exhaust Duct Bracket1050009611111717Heater Clip1090007952222732Outside Temperature Thermistor1050009861111
129Combustion Chamber - Body Bracket1090012921111718Heater ClipU250-6252222
130Combustion Chamber Bracket1050009631111719Gas Control Harness1050009661111
131Combustion Chamber Bracket - Small1050009641111724Sensor Harness - 210500096911
135Flue Outlet1020000681111724Sensor Harness - 410500097111

Rinnai America Corporation continually updates materials, and as such, content is subject to change without notice. For further information, contact Rinnai at 1-800-621-9419 or visit www.rinnai.us.

Models: REP199EP Smart Circ Non Condensing Propane Tankless Water Heater, REP199EP, Smart Circ Non Condensing Propane Tankless Water Heater, Propane Tankless Water Heater, Tankless Water Heater

File Info : application/pdf, 2 Pages, 2.87MB

PDF preview unavailable. Download the PDF instead.

100000735 VE Non-Pump Outdoor Tech Sheet

References

Microsoft Publisher for Microsoft 365

Related Documents

Preview Rinnai Non-Condensing Cold Weather Kit Installation Instructions
Detailed installation instructions for the Rinnai Non-Condensing Cold Weather Kit, designed to protect Rinnai tankless water heaters from freezing.
Preview Rinnai SENSEI RX Series Tankless Water Heater: Ground Water Temperature & Performance Guide
Rinnai SENSEI RX Series tankless water heater guide detailing US/Canada ground water temperature zones, their impact on performance, flow rates, and simultaneous shower capacity. Includes RX160IN and RXP160IN model data.
Preview Rinnai Continuous Flow Hot Water Unit Troubleshooting Guide
A comprehensive guide to diagnosing and resolving no hot water issues with Rinnai Continuous Flow hot water units. Covers checks for power, water flow, strainers, fixtures, and gas supply.
Preview Rinnai Tankless Water Heater Installation and Operation Manual
Comprehensive guide for installing and operating Rinnai residential tankless water heaters, covering safety, model specifications, installation procedures, operation, maintenance, and troubleshooting.
Preview Rinnai RU199e, RU180e, RU160e, RU130e Outdoor Condensing Tankless Water Heater Specifications
Detailed specifications and features for Rinnai's RU199e, RU180e, RU160e, and RU130e series of outdoor condensing tankless water heaters, including technical data, dimensions, and performance curves.
Preview Rinnai RXP199i & RXP160i Condensing Tankless Water Heater Specifications and Features
Detailed overview of Rinnai's RXP199i and RXP160i high-efficiency condensing tankless water heaters, including technical specifications, installation options, warranty, and performance curves.
Preview Rinnai CX199iN Commercial Hybrid Tankless Water Heater Engineering Specifications
Detailed engineering specifications for the Rinnai CX199iN commercial hybrid tankless water heater system, including BTU input, capacity, efficiency, safety features, and warranty information.
Preview Rinnai Tankless Water Heater Error Codes and Troubleshooting Guide
A concise guide to understanding and resolving common error codes for Rinnai tankless water heaters, focusing on air supply and exhaust blockages (Error Code 10).