Finder Serie 72 Control Relay
Type: 72.51.0.xxx.000x Conductive Liquid Level Control Relay
The Serie 72 offers high capabilities in a single module with a wide range of accessories. It is designed for controlling liquid levels in conductive media.
Model Specifications
Model Number | Power Supply | Sensitivity Range |
---|---|---|
72.51.0.240.0000 | 110...240 V AC/DC | (5...150) kΩ |
72.51.0.240.0002 | 110...240 V AC/DC | (5...450) kΩ |
72.51.0.024.0000 | 24 V AC/DC | (5...150) kΩ |
72.51.0.024.0002 | 24 V AC/DC | (5...450) kΩ |
Key Features
- Power Supply: 24 V AC/DC or 110...240 V AC/DC.
- Adjustable Sensitivity: Selectable between 5...150 kΩ or 5...450 kΩ.
- Output Contact: 1 Changeover (CO) contact, rated 6A.
- Functions: Supports filling and emptying control with 6 available functions. This includes single level control (minimum/maximum) and level monitoring between minimum and maximum (Window function).
- Selectable Delay: Intervention delay can be set from 0.5 seconds to 7 seconds.
- Indicators: Double LED indicator for power status and output contact status.
- Double Insulation: 6 kV (1.2/50 µs) insulation between power and contacts, probes and power, and contacts and probes.
Operation Principle
Level control is performed using probes connected to the relay:
- With 2 probes: Connected to terminals B1 and B3. The liquid level is maintained at the level of the B1 probe.
- With 3 probes: Connected to terminals B1, B2, and B3. The liquid level is maintained between the minimum probe (B2) and the maximum probe (B1).
Window Function
The Window function allows simultaneous monitoring of two levels (B1 and B2). It is useful for applications requiring alerts for potential overfill or underfill conditions.
Available Functions and Delays
Function Code | Description | Delay |
---|---|---|
FL | Level control in filling | 7 s |
FS | Level control in filling | 0.5 s |
ES | Level control in emptying | 0.5 s |
EL | Level control in emptying | 7 s |
WL | Window mode | 7 s |
WS | Window mode | 0.5 s |
Admitted Liquids
- Potable water
- Well water
- Rainwater
- Seawater
- Liquids with low alcohol content
- Wine
- Milk, beer, coffee
- Sewage
- Fertilizers
Non-Admitted Liquids
- Demineralized water
- Gasoline
- Oil
- Liquids with high alcohol content
- Liquid gases
- Paraffin
- Ethylene glycol
- Paints
Available Accessories
- Type 072.41: Probe
- Type 072.51: Bipolar electrode holder
- Type 072.53: Tripolar electrode holder
- Type 072.500: Electrode (475 mm length)
- Type 072.501: Electrode fitting
- Type 072.503: Electrode separator (for tripolar electrode holder 072.53)
The PQA package is available, containing: 1x 72.51 level control relay and 2x 072.41 probes.
For more information, visit findernet.com.
Finder reserves the right to make changes to prices, features, specifications, appearance, and availability of products and services without prior notice. Finder assumes no responsibility for the presence of possible errors or insufficient information in this document. In case of discrepancies between printed and online versions, the latter prevails.