ℹ️ Document Conversion Notice:
This document has been converted from PDF and formatted to fit this screen. Diagrams and images may be available only in the original here.
Isolator Barriers - Resistance Isolator
Ex i field circuit ISpac 9180/11-77-11s
Art. No.: 160499
Product Overview
The R. STAHL 9180A ISpac series resistance isolators are designed for the intrinsically safe operation of Pt100 or Pt1000 resistance temperature detectors. This two-channel device offers a compact design, requiring only 8.8 mm of space per channel, and supports two-, three-, and four-conductor connections. The measured resistance at the input is transmitted to the output and can be read by an I/O card. The auxiliary power, output, and intrinsically safe input are galvanically separated.
Key Features:
Ex i resistance isolator 9180/.0 for Pt100 or 9180/.1 for Pt1000
World's only two-channel device requiring just 8.8 mm of space per channel
For two-, three-, and four-conductor connection
Technical Data
Explosion Protection
Parameter
Value
Application range (zones)
0, 1, 2, 20, 21, 22
Ex interface zone
IECEx BVS 10.0055 X
IECEx gas explosion protection
Ex ec nC [ia Ga] IIC T4 Gc
IECEx dust certificate
IECEx BVS 10.0055 X
IECEx dust explosion protection
[Ex ia Da] IIIC
ATEX gas certificate
BVS 05 ATEX E 176 X
ATEX gas explosion protection
II 3 (1) G Ex ec nC [ia Ga] IIC T4 Gc
ATEX dust certificate
BVS 05 ATEX E 176 X
ATEX dust explosion protection
II (1) D [Ex ia Da] IIIC
FMUS certificate
FM16US0122X
CFM certificate
FM16CA0067X
Marking cFMus
Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA nC Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 at Ta = 70°C
Certificates
See Doc. 9180 6 031 001 1
Ship approval
ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), India (PESO), Korea (KTL), USA (FM)
Declaration of conformity
CCS, EU RO MR (DNV); ATEX (EUK), China (CCC)
Safety Data
Parameter
Value
Max. voltage U。/VOC
6.5 V
Max. current Io/Isc
16.5 mA
Max. power Po
27 mW
Max. permissible external capacitance Ca/Co for IIC
25 μF
Max. permissible external inductance La/Lo for IIC
120 mH
Max. permissible external capacitance Ca/Co for IIB
570 μF
Max. permissible external inductance La/Lo for IIB
450 mH
Max. perm. ext. capacit. IIIC
570 μF
Max. permis. ext. induct. IIIC
450 mH
Internal capacitance
Negligible
Internal inductance
Negligible
Safety-related max. voltage
253 V
Intrinsically safe limiting values inductance L/capacitance Co
The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
Storage temperature °C
-40 °C ... +80 °C
Storage temperature °F
-40°F ... +176°F
Max. relative humidity
95%
Max. additional relative humidity
No condensation
Use at the height of
< 2000 m
Overvoltage category
II
Degree of pollution
2
Electromagnetic compatibility
Tested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21
Mechanical Data
Parameter
Value
Degree of protection (IP)
IP30
Degree of protection (IP) terminals
IP20
Fire resistance (UL 94)
V0
Enclosure material
Polyamide
Connection cross-section
0.2 to 2.5 mm² flexible; 0.25 to 2.5 mm² flexible with core end sleeve; 0.2 to 2.5 mm² rigid
Grid dimension
17.6 mm
Width
17.6 mm (0.69 in)
Height
114.5 mm (4.51 in)
Length
108 mm (4.25 in)
Mounting depth in inches
4.51 in
Weight
160 g (0.35 lb)
Mounting / Installation
Mounting type
DIN rail NS35/15, NS35/7.5
Mounting orientation
Vertical, Horizontal
Connection type
Screw terminal
Min. rigid conductor cross section
0.2 mm²
Max. rigid conductor cross section
2.5 mm²
Min. flex conductor cross section
0.2 mm²
Max. flex conductor cross section
2.5 mm²
Connection cross-section AWG
24 ... 14
Technical Drawings
A connection diagram illustrates the isolator barrier's integration between a hazardous location (Zone 0/1, Division 1) and a non-hazardous location (Zone 2, Division 2). The diagram shows the field device connecting to the ISpac isolator, which then connects to the control system via a pac-Bus and 24 V DC auxiliary power. The diagram details terminal connections for input, output, and auxiliary power, including specific pin assignments (e.g., 1+, 2-, 3+, 4-, 7++, 8--, 9--, 10, 11, 12, 13).
Dimensional Drawings
The dimensional drawings provide a detailed view of the isolator barrier's physical dimensions in millimeters and inches. Key dimensions include:
Overall height: 114.5 mm (4.51 in)
Overall width: 17.6 mm (0.69 in)
Overall length: 108 mm (4.25 in)
Mounting depth: 122 mm (4.80 in)
Specific internal dimensions are also detailed.
These drawings are subject to alteration and apply to the ISpac series including models 9143, 9146, 9147, 9160, 9162, 9163, 9165, 9167, 9170, 9172, 9175, 9176, 9180, 9182, 9193, and ISbus Series 9412 with screw terminals.
Accessories
Transparent Cover
Description
Art. No.
For 91xx ISpac modules. Yellow, transparent. Clear identification of the device for SIL applications. (Packaging unit: 10 pieces)
200914
Spare Parts
Screw terminal
Description
Art. No.
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: black
112816
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: blue
112818
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: green
112817
Screw terminal with test tap
Description
Art. No.
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: blue
113004
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: black
ex-ficha-tecnica-individual-repetidor-aislador-resistencia-circuito-de-campo-ex-i-ispac-9180-11-77-11s-160499-en-us-rstahl Adobe PDF Library 17.0
Related Documents
R. STAHL 9180A Ex i Resistance Isolator for Pt100/Pt1000 Technical specifications and data for the R. STAHL 9180A Ex i resistance isolator, designed for intrinsically safe operation of Pt100 and Pt1000 resistance temperature detectors. Features include galvanic isolation, various explosion protection certifications, and detailed electrical and mechanical data.
R. STAHL 9180A Series Ex i Resistance Isolator - Technical Data and Specifications Detailed technical specifications for the R. STAHL 9180A Series Ex i resistance isolator, including explosion protection, technical data, safety data, mechanical data, and accessories. Suitable for Pt100 and Pt1000 resistance temperature detectors in hazardous areas.
R. STAHL 9180A Series Ex i Resistance Isolator: Technical Specifications Detailed technical specifications for the R. STAHL 9180A series Ex i field circuit resistance isolator (ISpac), including explosion protection, technical data, input/output specifications, mechanical data, and accessories.
R. STAHL 9180/20-77-11k Ex i Field Circuit Isolator Barrier - Technical Data Detailed technical specifications and data for the R. STAHL 9180/20-77-11k Ex i field circuit resistance isolator barrier, including explosion protection, safety data, electrical data, input/output specifications, mechanical data, and accessories.
R. STAHL 9180/11-77-11s: Resistance Signal Conditioner for Hazardous Areas Detailed technical specifications and features of the R. STAHL 9180/11-77-11s resistance signal conditioner, designed for intrinsically safe field circuits in Ex i applications. Learn about its explosion protection, electrical data, and mechanical properties.