Isolator Barriers - Resistance Isolator

Ex i field circuit ISpac 9180/11-77-11s

Art. No.: 160499

Product Overview

The R. STAHL 9180A ISpac series resistance isolators are designed for the intrinsically safe operation of Pt100 or Pt1000 resistance temperature detectors. This two-channel device offers a compact design, requiring only 8.8 mm of space per channel, and supports two-, three-, and four-conductor connections. The measured resistance at the input is transmitted to the output and can be read by an I/O card. The auxiliary power, output, and intrinsically safe input are galvanically separated.

Key Features:

Technical Data

Explosion Protection

ParameterValue
Application range (zones)0, 1, 2, 20, 21, 22
Ex interface zoneIECEx BVS 10.0055 X
IECEx gas explosion protectionEx ec nC [ia Ga] IIC T4 Gc
IECEx dust certificateIECEx BVS 10.0055 X
IECEx dust explosion protection[Ex ia Da] IIIC
ATEX gas certificateBVS 05 ATEX E 176 X
ATEX gas explosion protectionII 3 (1) G Ex ec nC [ia Ga] IIC T4 Gc
ATEX dust certificateBVS 05 ATEX E 176 X
ATEX dust explosion protectionII (1) D [Ex ia Da] IIIC
FMUS certificateFM16US0122X
CFM certificateFM16CA0067X
Marking cFMusClass I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA nC Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 at Ta = 70°C
CertificatesSee Doc. 9180 6 031 001 1
Ship approvalATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), India (PESO), Korea (KTL), USA (FM)
Declaration of conformityCCS, EU RO MR (DNV); ATEX (EUK), China (CCC)

Safety Data

ParameterValue
Max. voltage U。/VOC6.5 V
Max. current Io/Isc16.5 mA
Max. power Po27 mW
Max. permissible external capacitance Ca/Co for IIC25 μF
Max. permissible external inductance La/Lo for IIC120 mH
Max. permissible external capacitance Ca/Co for IIB570 μF
Max. permissible external inductance La/Lo for IIB450 mH
Max. perm. ext. capacit. IIIC570 μF
Max. permis. ext. induct. IIIC450 mH
Internal capacitanceNegligible
Internal inductanceNegligible
Safety-related max. voltage253 V
Intrinsically safe limiting values inductance L/capacitance CoJointly connectable inductance L/capacitance Co
Lo [mH]Co [µF]Lo [mH]Co [µF]Lo [mH]Co [µF]Lo [mH]Co [µF]
IIC50 mH1.100 µF5 mH1.700 µF1 mH2.300 µF0.200 mH3.400 µF
IIB100 mH5.300 µF20 mH6.900 µF2 mH11 µF0.500 mH1.500 µF
IIIC100 mH5.300 µF20 mH6.900 µF2 mH11 µF0.500 mH1.500 µF

Electrical Data

ParameterValue
Number of channels1
LFD relayYes
Measuring range180 to 3910 Ω
Auxiliary Power
Auxiliary power24 V DC
Nominal voltage Vnom24 V DC
Auxiliary power voltage range18 ... 31.2 V
Voltage range residual ripple≤ 3,6 VSS
Nominal current27 mA
Power consumption0.65 W
Max. power dissipation0.6 W
Polarity reversal protectionYes
Undervoltage monitoringYes
Operation indicationGreen "PWR" LED

Galvanic Isolation

ParameterValue
Test voltage as per standardEN IEC 60079-11
Ex i input to output1.5 kV AC
Ex i input to auxiliary power1.5 KV AC
Ex i input to fault message contact1.5 KV AC
Test voltage as per standardEN 50178
Output to auxiliary power350 V AC
Output to output350 V AC
Fault message contact to auxiliary power350 V AC
Fault message contact to output350 V AC

Input

ParameterValue
Sensor adjustmentDIP switch
Medium-resolution input0.2 Ω
Input for resistance temperature detectorPt 100, Pt 1000
Connection type RTD input2-, 3- and 4-wire circuits
2-conductor adjustmentVia ADJ DIP switch
Sensor current RTD200 µA ... 0.5 mA
Max. line resistance per wire RTD50 Ω (2-wire connection), 100 Ω (3-, 4-wire connection)
Output signalEquals input signal (resistance value)
Connection type RTD output2-, 3- and 4-wire circuits
Settling time output< 10 ms
Response time output< 1 s
Sensor current range200 µA ... 0.5 mA
LF switch user adjustmentActivated/deactivated
Wire breakage error detection input> 3940 ohm
Short circuit error detection input< 160 ohm
Behaviour of output during LF> 10 kΩ
Fault indicationRed "LF" LED
Fault message contact switching capacity30 V / 100 mA
Line fault and loss of power signalizationContact (30 V/100 mA), closed against earth in case of error - pac-Bus, potential-free contact (30 V/100 mA)
Deviations / error noteInformation in % of the measuring range (20 mA) at UN, 23 °C
Average measurement fault< 0.1%
Temperature influence≤ 0.1%/10K

Ambient Conditions

ParameterValue
Ambient temperature °C-20 °C ... +70 °C (Single device), -20 °C ... +60 °C (Group assembly)
Ambient temperature °F-4°F ... +158°F (Single device), -4°F ... +140°F (Group assembly)
NoteThe installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
Storage temperature °C-40 °C ... +80 °C
Storage temperature °F-40°F ... +176°F
Max. relative humidity95%
Max. additional relative humidityNo condensation
Use at the height of< 2000 m
Overvoltage categoryII
Degree of pollution2
Electromagnetic compatibilityTested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21

Mechanical Data

ParameterValue
Degree of protection (IP)IP30
Degree of protection (IP) terminalsIP20
Fire resistance (UL 94)V0
Enclosure materialPolyamide
Connection cross-section0.2 to 2.5 mm² flexible; 0.25 to 2.5 mm² flexible with core end sleeve; 0.2 to 2.5 mm² rigid
Grid dimension17.6 mm
Width17.6 mm (0.69 in)
Height114.5 mm (4.51 in)
Length108 mm (4.25 in)
Mounting depth in inches4.51 in
Weight160 g (0.35 lb)
Mounting / Installation
Mounting typeDIN rail NS35/15, NS35/7.5
Mounting orientationVertical, Horizontal
Connection typeScrew terminal
Min. rigid conductor cross section0.2 mm²
Max. rigid conductor cross section2.5 mm²
Min. flex conductor cross section0.2 mm²
Max. flex conductor cross section2.5 mm²
Connection cross-section AWG24 ... 14

Technical Drawings

A connection diagram illustrates the isolator barrier's integration between a hazardous location (Zone 0/1, Division 1) and a non-hazardous location (Zone 2, Division 2). The diagram shows the field device connecting to the ISpac isolator, which then connects to the control system via a pac-Bus and 24 V DC auxiliary power. The diagram details terminal connections for input, output, and auxiliary power, including specific pin assignments (e.g., 1+, 2-, 3+, 4-, 7++, 8--, 9--, 10, 11, 12, 13).

Dimensional Drawings

The dimensional drawings provide a detailed view of the isolator barrier's physical dimensions in millimeters and inches. Key dimensions include:

These drawings are subject to alteration and apply to the ISpac series including models 9143, 9146, 9147, 9160, 9162, 9163, 9165, 9167, 9170, 9172, 9175, 9176, 9180, 9182, 9193, and ISbus Series 9412 with screw terminals.

Accessories

Transparent Cover

DescriptionArt. No.
For 91xx ISpac modules. Yellow, transparent. Clear identification of the device for SIL applications. (Packaging unit: 10 pieces)200914

Spare Parts

Screw terminal

DescriptionArt. No.
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: black112816
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: blue112818
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: green112817

Screw terminal with test tap

DescriptionArt. No.
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: blue113004
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: black113005

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-repetidor-aislador-resistencia-circuito-de-campo-ex-i-ispac-9180-11-77-11s-160499-en-us-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9180A Ex i Resistance Isolator for Pt100/Pt1000
Technical specifications and data for the R. STAHL 9180A Ex i resistance isolator, designed for intrinsically safe operation of Pt100 and Pt1000 resistance temperature detectors. Features include galvanic isolation, various explosion protection certifications, and detailed electrical and mechanical data.
Preview R. STAHL 9180/21-77-11s Isolator Barrier: Technical Specifications
Detailed technical specifications for the R. STAHL 9180/21-77-11s resistance isolator, including explosion protection, safety data, electrical data, and mechanical data for Ex i field circuits.
Preview R. STAHL 9180A Series Ex i Resistance Isolator - Technical Data and Specifications
Detailed technical specifications for the R. STAHL 9180A Series Ex i resistance isolator, including explosion protection, technical data, safety data, mechanical data, and accessories. Suitable for Pt100 and Pt1000 resistance temperature detectors in hazardous areas.
Preview R. STAHL 9180/11-77-11s Ex i ISpac Resistance Isolator for Field Circuits
Technical specifications and features of the R. STAHL 9180/11-77-11s Ex i ISpac resistance isolator, designed for intrinsic safety in resistance thermometer circuits.
Preview R. STAHL 9180A Series Ex i Resistance Isolator: Technical Specifications
Detailed technical specifications for the R. STAHL 9180A series Ex i field circuit resistance isolator (ISpac), including explosion protection, technical data, input/output specifications, mechanical data, and accessories.
Preview R. STAHL 9180/20-77-11k Ex i Field Circuit Isolator Barrier - Technical Data
Detailed technical specifications and data for the R. STAHL 9180/20-77-11k Ex i field circuit resistance isolator barrier, including explosion protection, safety data, electrical data, input/output specifications, mechanical data, and accessories.
Preview R. STAHL 9180/11-77-11s: Resistance Signal Conditioner for Hazardous Areas
Detailed technical specifications and features of the R. STAHL 9180/11-77-11s resistance signal conditioner, designed for intrinsically safe field circuits in Ex i applications. Learn about its explosion protection, electrical data, and mechanical properties.
Preview R. STAHL 9180/21-77-11s Resistance Temperature Detector Isolating Transducer - Technical Data
Detailed technical specifications and features of the R. STAHL 9180/21-77-11s Resistance Temperature Detector Isolating Transducer for field circuits Ex i ISpac. Includes explosion protection, safety data, electrical data, mechanical data, and accessories.