R. STAHL Isolator Barriers: Resistance Isolator

Product Series: Ex i field circuit ISpac

Model: 9180/21-77-11s

Article Number: 160502

Product Overview

The R. STAHL 9180 series Ex i resistance isolators are designed for the intrinsically safe operation of Pt100 (9180/.0) or Pt1000 (9180/.1) resistance temperature detectors. These isolators measure resistance at the input and transmit it to the output, allowing it to be read by an I/O card. The auxiliary power, output, and intrinsically safe input are galvanically separated. Key features include world's only two-channel device requiring just 8.8 mm of space per channel and suitability for two-, three-, and four-conductor connections.

Technical Data

Explosion Protection

Application range (zones) 0, 1, 2, 20, 21, 22
Ex interface zone IECEx BVS 10.0055 X
IECEx gas explosion protection Ex ec nC [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx BVS 10.0055 X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate BVS 05 ATEX E 176 X
ATEX gas explosion protection II 3 (1) G Ex ec nC [ia Ga] IIC T4 Gc
ATEX dust certificate BVS 05 ATEX E 176 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FMus certificate FM16US0122X
CFM certificate FM16CA0067X
Marking cFMus Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA nC Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 at Ta = 70°C
Certificates See Doc. 9180 6 031 001 1
Ship approval ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), India (PESO), Korea (KTL), USA (FM)
Declaration of conformity CCS, EU RO MR (DNV)
Safety Data ATEX (EUK), China (CCC)
Max. voltage U。/V 6.5 V
Max. current Io/Isc 16.5 mA
Max. power Po 27 mW
Max. permissible external capacitance C/C for IIC 25 μF
Max. permissible external inductance L/La for IIC 120 mH
Max. permissible external capacitance C/C for IIB 570 μF
Max. permissible external inductance L/La for IIB 450 mH
Max. perm. ext. capacit. IIIC 570 μF
Max. permis. ext. induct. IIIC 450 mH
Internal capacitance Negligible
Internal inductance Negligible
Safety-related max. voltage 253 V

Intrinsically safe limiting values

Jointly connectable inductance L/capacitance C₀
L. [mH] C₀ [µF] L. [mH] C₀ [µF] L. [mH] C₀ [µF] L. [mH] C₀ [µF]
IIC 50 mH 1.100 μF 5 mH 1.700 μF 1 mH 2.300 μF 0.200 mH 3.400 μF
IIB 100 mH 5.300 μF 20 mH 6.900 μF 2 mH 11 μF 0.500 mH 1.500 μF
IIIC 100 mH 5.300 μF 20 mH 6.900 μF 2 mH 11 μF 0.500 mH 1.500 μF

Electrical Data

Number of channels 2
LFD relay Yes
Measuring range 180 to 3910 Ω
Auxiliary Power 24 V DC
Nominal voltage Vnom 24 V DC
Auxiliary power voltage range 18 ... 31.2 V
Voltage range residual ripple ≤ 3,6 VSS
Nominal current 37 mA
Power consumption 0.89 W
Max. power dissipation 0.72 W
Polarity reversal protection Yes
Undervoltage monitoring Yes
Operation indication Green "PWR" LED

Galvanic Isolation

Test voltage as per standard EN IEC 60079-11
Ex i input to output 1.5 kV AC
Ex i input to auxiliary power 1.5 KV AC
Ex i input to fault message contact 1.5 KV AC
Test voltage as per standard EN 50178
Output to auxiliary power 350 V AC
Output to output 350 V AC
Fault message contact to auxiliary power 350 V AC
Fault message contact to output 350 V AC

Input Specifications

Sensor adjustment DIP switch
Medium-resolution input 0.2 Ω
Input for resistance temperature detector Pt 100 or Pt 1000
Connection type RTD input 2-, 3- and 4-wire circuits
2-conductor adjustment Via ADJ DIP switch
Sensor current RTD 200 µA ... 0.5 mA
Max. line resistance per wire RTD 50 Ω (2-wire connection)
Max. line resistance per wire RTD 100 Ω (3-, 4-wire connection)

Output Specifications

Output signal Equal to input signal (resistance value)
Connection type RTD output 2-, 3- and 4-wire circuits
Settling time output < 10 ms
Response time output < 1 s
Sensor current range 200 µA ... 0.5 mA
LF switch user adjustment Activated/deactivated
Wire breakage error detection input > 3940 ohm
Short circuit error detection input < 160 ohm
Behaviour of output during LF > 10 KΩ
Line fault indication Red "LF" LED
Fault message contact switching capacity 30 V / 100 mA
Line fault and loss of power signalization Contact (30 V/100 mA), closed against earth in case of error
Deviations / error note Information in % of the measuring range (20 mA) at UN, 23 °C
Average measurement fault < 0,1%
Temperature influence ≤ 0,1%/10K

Ambient Conditions

Ambient temperature °C -20 °C ... +70 °C (Single device)
-20 °C ... +60 °C (Group assembly)
Ambient temperature °F -4°F ... +158°F (Single device)
-4°F ... +140°F (Group assembly)
Note The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
Storage temperature °C -40 °C ... +80 °C
Storage temperature °F -40°F ... +176°F
Max. relative humidity 95%
Max. additional relative humidity No condensation
Use at the height of < 2000 m
Overvoltage category II
Degree of pollution 2
Electromagnetic compatibility Tested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21

Mechanical Data

Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Connection cross-section 0.2 to 2.5 mm² flexible
0.25 to 2.5 mm² flexible with core end sleeve
0.2 to 2.5 mm² rigid
Grid dimension 17.6 mm
Width 17.6 mm
Width, inches 0.69 in
Height 114.5 mm
Length 108 mm
Length in inches 4.25 in
Mounting depth in inches 4.51 in
Weight 180 g
Weight 0.4 lb

Mounting / Installation

Mounting type DIN rail NS35/15, NS35/7.5
Mounting orientation Vertical
Horizontal
Connection type Screw terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings

Hazardous Location:

Nonhazardous Location:

Field Device:

Control System:

Connection diagram: 9180/21-77-11

Dimensional Drawings

Dimensions in mm [inches]:

ISpac Series compatibility: 9143, 9146, 9147, 9160, 9162, 9163, 9165, 9167, 9170, 9172, 9175, 9176, 9180, 9182, 9193, ISbus Series 9412 with screw terminal.

Accessories

Item: Transparent cover Description: For 91xx ISpac modules, Yellow, transparent. Clear identification of the device for SIL applications. (Packaging unit: 10 pieces) Art. No.: 200914

Spare Parts

Screw terminal

Description: 3-pole plug, screw connector Thread: M3 Stripping length: 7 mm Color: black Art. No.: 112816
Description: 3-pole plug, screw connector Thread: M3 Stripping length: 7 mm Color: blue Art. No.: 112818
Description: 3-pole plug, screw connector Thread: M3 Stripping length: 7 mm Color: green Art. No.: 112817

Screw terminal with test tap

Description: 3-pole plug with test tap, screw connector Thread: M3 Stripping length: 7 mm Colour: blue Art. No.: 113004
Description: 3-pole plug with test tap, screw connector Thread: M3 Stripping length: 7 mm Colour: black Art. No.: 113005

General Information

R. STAHL, INC. | 13259 N. Promenade Blvd. | Stafford, TX 77477 | Tel. +1 800 782 4357

Email US: sales.us@r-stahl.com | Email CAN: sales.ca@r-stahl.com | rstahl.com

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-repetidor-aislador-resistencia-circuito-de-campo-ex-i-ispac-9180-21-77-11s-160502-en-us-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9180A Series Ex i Resistance Isolator - Technical Data and Specifications
Detailed technical specifications for the R. STAHL 9180A Series Ex i resistance isolator, including explosion protection, technical data, safety data, mechanical data, and accessories. Suitable for Pt100 and Pt1000 resistance temperature detectors in hazardous areas.
Preview R. STAHL 9180A ISpac Resistance Isolator Datasheet
Technical datasheet for the R. STAHL 9180A ISpac resistance isolator, designed for Ex i field circuits. Includes detailed specifications, explosion protection data, electrical and mechanical characteristics, and safety information.
Preview R. STAHL 9180A Ex i Resistance Isolator for Pt100/Pt1000
Technical specifications and data for the R. STAHL 9180A Ex i resistance isolator, designed for intrinsically safe operation of Pt100 and Pt1000 resistance temperature detectors. Features include galvanic isolation, various explosion protection certifications, and detailed electrical and mechanical data.
Preview R. STAHL 9180A Series Ex i Resistance Isolator: Technical Specifications
Detailed technical specifications for the R. STAHL 9180A series Ex i field circuit resistance isolator (ISpac), including explosion protection, technical data, input/output specifications, mechanical data, and accessories.
Preview R. STAHL 9180/21-77-11s Resistance Temperature Detector Isolating Transducer - Technical Data
Detailed technical specifications and features of the R. STAHL 9180/21-77-11s Resistance Temperature Detector Isolating Transducer for field circuits Ex i ISpac. Includes explosion protection, safety data, electrical data, mechanical data, and accessories.
Preview R. STAHL 9180/20-77-11k Ex i Field Circuit Isolator Barrier - Technical Data
Detailed technical specifications and data for the R. STAHL 9180/20-77-11k Ex i field circuit resistance isolator barrier, including explosion protection, safety data, electrical data, input/output specifications, mechanical data, and accessories.
Preview R. STAHL 9180/11-77-11s Ex i ISpac Resistance Isolator for Field Circuits
Technical specifications and features of the R. STAHL 9180/11-77-11s Ex i ISpac resistance isolator, designed for intrinsic safety in resistance thermometer circuits.
Preview R. STAHL ISpac 9180/21-77-11k Resistance Signal Conditioner for Ex i Circuits
Technical specifications and data for the R. STAHL ISpac 9180/21-77-11k, a resistance isolator repeater for Ex i field circuits, designed for operation with Pt100 or Pt1000 resistance temperature detectors.