Lennox Elite Series 6- to 20-Ton Split Systems
Quick Reference Guide
6- to 20-Ton Elite Series® Air Conditioners
Size (tons) | 6 | 6 | 7.5 | 7.5 | 10 | 10 | 12.5 | 12.5 | 15 | 15 | 15 | 15 | 20 | 20 | 20 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Outdoor Unit | EL072XCSST* | EL072XCSST* | EL090XCSST* | EL090XCSST* | EL120XCSST* | EL120XCSDT* | EL150XCSDT* | EL150XCSDT* | EL180XCSDT* | EL180XCSDT* | EL180XCSDT* (2) | EL090XCSST* | EL240XCSDT* | EL240XCSDT* (2) | EL120XCSST* |
Compressor Type | Scroll | Scroll | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage | Two-Stage |
Refrigerant Circuits (Qty) | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Indoor Unit | EL072XASS* | EL090XASD* | EL090XASD* | EL120XASD* | EL120XASD* | EL120XASD* | EL150XASD* | EL180XASD* | EL180XASD* | EL180XASD* | EL180XASD* (2) | EL090XASD* | EL240XASD* | EL240XASD* (2) | EL120XASD* |
Refrigerant Circuits (Qty) | Single | Single | Single | Single | Single | Dual | Dual | Dual | Dual | Dual | Dual | (2) Single | Dual | Dual | Dual |
Blower Type | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV | MSAV |
Net Cooling Capacity (btuh) | 71,000 | 73,000 | 89,000 | 90,000 | 115,000 | 115,000 | 136,000 | 142,000 | 176,000 | 196,000 | 180,000 | 170,000 | 228,000 | 232,000 | 232,000 |
EER | 12.0 | 11.2 | 11.2 | 11.2 | 11.2 | 11.2 | 11.0 | 11.0 | 11.0 | 11.0 | 11.0 | 11.0 | 11.0 | 11.0 | 11.0 |
IEER | 16.0 | 14.8 | 14.8 | 14.8 | 14.8 | 14.8 | 14.2 | 14.2 | 14.2 | 14.2 | 14.2 | 14.2 | 14.2 | 14.2 | 14.4 |
Stages of Cooling | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 3 | 3 | 3 | 2 | 3 | 3 | 2 |
Weight Shipping (ODU) | 338 | 338 | 365 | 365 | 477 | 511 | 560 | 560 | 809 | 809 | 809 | 730 | 889 | 889 | 1022 |
Weight Shipping (IDU) | 438 | 460 | 460 | 528 | 528 | 528 | 542 | 769 | 769 | 841 | 920 | 769 | 841 | 1056 | 841 |
Sound Rating ODU (dBA) | 81 | 81 | 81 | 81 | 86 | 85 | 86 | 86 | 88 | 88 | 88 | N/A | 89 | 89 | N/A |
6- to 15-Ton Elite Series® Heat Pumps
Size (tons) | 6 | 7.5 | 10 | 15 |
---|---|---|---|---|
Outdoor Unit | EL072XPSST* | EL090XPSST* | EL120XPSST* | (2) EL090XPSST* |
Compressor Type | Two-Stage Scroll | Two-Stage Scroll | Two-Stage Scroll | Two-Stage Scroll |
Refrigerant Circuits (Qty) | 1 | 1 | 1 | 1 |
Indoor Unit | EL090XASD* | EL090XASD* | EL120XASD* | EL240XASD* |
Refrigerant Circuits (Qty) | Single | Single | Single | Dual |
Blower Type | MSAV | MSAV | MSAV | MSAV |
Net Cooling Capacity (btuh) | 69,000 | 88,000 | 115,000 | 178,000 |
EER | 11.3 | 11.0 | 11.0 | 10.6 |
IEER | 14.1 | 14.1 | 14.1 | 13.5 |
High Heat COP @ 47°F | 3.4 | 3.4 | 3.4 | 3.4 |
Low Heat COP @ 17°F | 2.25 | 2.25 | 2.25 | 2.25 |
Stages of Cooling | 2 | 2 | 2 | 2 |
Weight Shipping (ODU) | 450 | 450 | 527 | 900 |
Weight Shipping (IDU) | 460 | 460 | 528 | 841 |
Sound Rating (dBA) | 85 | 85 | 86 | 85 |
Elite Series® Residential Matches
The following details provide potential residential matches for Elite Series outdoor units:
-
Outdoor Unit: EL072XPSST*
- Refrigerant Circuits: 1
- Indoor Coil or Air Handler: (2) CX35-60D
- Furnace Matchups: (2) EL296UH135XE60D
- Net Cooling Capacity (btuh): 92,000
- EER: 11.2
- IEER: 14.8
- Stages of Cooling: 2
- Expansion Device: Factory TXV
-
Outdoor Unit: EL090XPSST*
- Refrigerant Circuits: 1
- Indoor Coil or Air Handler: (2) CX35-60C
- Furnace Matchups: (2) EL280UH110E60C, (2) EL280UH110XE60C, (2) EL296UH110XE60C or (2) EL280UH110E48C
- Net Cooling Capacity (btuh): 95,000
- EER: 11.2
- IEER: 14.8
- Stages of Cooling: 2
- Expansion Device: Factory TXV
-
Outdoor Unit: EL120XPSST*
- Refrigerant Circuits: 1
- Indoor Coil or Air Handler: (2) CH23-68
- Furnace Matchups: (2) EL280UH110XE60C, (2) EL296UH110XE60C or (2) EL280UH110E60C
- Net Cooling Capacity (btuh): 110,000
- EER: 11.2
- IEER: 14.8
- Stages of Cooling: 2
- Expansion Device: 12J20 (Order 2)
-
Outdoor Unit: (2) EL090XPSST*
- Refrigerant Circuits: 1
- Indoor Coil or Air Handler: (2) CX35-60C
- Furnace Matchups: (2) EL280UH110XE60C, (2) EL296UH135XE60D or (2) EL280UH110E60C
- Net Cooling Capacity (btuh): 110,000
- EER: 11.2
- IEER: 14.8
- Stages of Cooling: 2
- Expansion Device: Factory TXV
Factory- and Field-Installed Options
OPTION | FACTORY | FIELD |
---|---|---|
CABINET | ||
Combined Coil/Hail Guards | ||
Corrosion Protection | ||
Drain Pan Overflow Switch | ||
CONTROLS | ||
BACnet® Module | ||
BACnet® Sensor with Display | ||
BACnet® Sensor without Display | ||
Low Ambient Control (0°F) | ||
Furnace Twinning Panel (072-120 XC) | ||
BLOWER | ||
Blower Motor and Drive Kits | ||
ECONOMIZER | ||
Standard Economizers (Not for Title 24) | ||
High Performance Economizers | ||
Single Sensible/Enthalpy Control | ||
ELECTRICAL | ||
Voltage (208/230V, 460V, or 575V-3ph, 60Hz) | ||
Electric Heat 10kW-50kW | ||
GFI Service Outlet | ||
INDOOR AIR QUALITY | ||
Healthy Climate® Air Filters (16 x 25 x 4) | ||
4-Inch Filter Mounting Kits | ||
REFRIGERANT SYSTEM | ||
R-410a | ||
Heat Pump Check Valve Kit |
Model No. Nomenclature Comparison
Manufacturer Comparison
Lennox | Carrier | Trane | York/JCI | |
---|---|---|---|---|
Manufacturer | Lennox | Carrier | Trane | N/A |
Product Name | Elite® Series | Gemini® | Odyssey™ | N/A |
Air Handler | EL***XA | 40RU(A/Q) | TWE | NC/ND |
Air Conditioner | EL***XC | 38AU(Z/D) | TTA | Y(C/D/E) |
Heat Pump | EL***XP | 38AUQ | TWA | P(C/D/E) |
Dimensional Comparison
LENGTH L | WIDTH W | HEIGHT H | SUPPLY AIR SL | SUPPLY AIR SW | RETURN AIR RL | RETURN AIR RW | |
---|---|---|---|---|---|---|---|
Tonnage | |||||||
072 to 090 | 45-1/4 | 37-5/8 | 46-1/8 | 18-5/8 | 25-3/4 | 23-1/4 | 45-1/2 |
120 to 150 | 45-1/4 | 57-7/8 | 41-3/8 | 18-5/8 | 25-3/4 | 23-1/4 | 61-1/2 |
180 to 240 | 45-1/4 | 57-7/8 | 86-1/2 | 18-5/8 | 51-5/8 | 23-1/4 | 92 |
Key Features
PURE COMFORT™: Featuring smart design features and high-quality components, the Pure Comfort™ system offers superior comfort and energy savings.
ADVANCED CONDENSATE MANAGEMENT™: The Advanced Condensate Management™ System uses quality engineering and innovative design to control condensation and keep moisture where it belongs.
SIMPLE SERVICE™: The Simple Service™ system helps ensure ease of installation and maintenance to make every service call easier.
Product Images
Images of Lennox Elite Series outdoor HVAC units are presented in the original document.