Legrand DALI Light Up Multi-Sensor: Advanced 3-Zone Occupancy and Environmental Sensing
The Legrand DALI Light Up multi-sensor is an advanced device designed for lighting control and building management applications. It integrates multiple sensors to provide comprehensive environmental data and occupancy detection.
Product Overview
This multi-sensor unit offers advanced features including:
- 3-Zone DALI Lighting Control: Manages three lighting zones, supporting group dimming and ON/OFF functions.
- Occupancy and Presence Detection: Utilizes thermal imaging sensors to measure people count per zone and detect presence.
- Environmental Sensing: Includes sensors for ambient light, temperature, relative humidity, acoustic level, and VOC (Volatile Organic Compounds) for air quality assessment (eCO2 estimation).
- Connectivity: Features Bluetooth 5.0 for commissioning via the 'CLOSE UP' mobile app and a 2.4 GHz radio frequency for network management.
- Auxiliary Inputs: Supports an auxiliary input for lighting control via a wired push-button.
- DALI Output: Provides DALI bus power and control for diffuse lighting.
- Relay Output: Dedicated for powering DALI ECGs.
Key Features and Technical Specifications
- Power Supply: 230 V~, 50-60 Hz.
- Terminal Capacity: 2 x 1.5 mm² or 1 x 2.5 mm².
- Standby Consumption: 2.7 W.
- Installation Diameter: 68 mm.
- Weight: 281 g (device only).
- Ingress Protection: IP20.
- Operating Temperature: +5°C to +30°C.
- Storage Temperature: -20°C to +70°C.
- Thermal Imaging Sensor: 160° field of view, 8m x 8m coverage at 2.5m installation height, up to 40 people count.
- Daylight Sensor: Measures ambient light (5-1275 lux) for automatic lighting adjustment.
- Humidity Sensor: Measures relative humidity (20-80%), with ±5% accuracy.
- Temperature Sensor: Measures ambient temperature (0-50°C).
- Acoustic Sensor: Measures ambient noise level (38-120 dB SPL).
- VOC Sensor: Estimates air quality, measuring VOCs (0-10,000 ppb) and providing an AQI (Air Quality Index) and eCO2 value.
- Bluetooth 5.0: For device setup and configuration using the 'CLOSE UP' app.
- Radio Frequency: 2.4 GHz for network creation.
Installation and Wiring
- Mounting: Designed for recessed installation with a 68mm diameter cutout. Surface mounting is possible with accessory Art. 0 485 80.
- Safety: Installation and wiring must be performed without power. Follow safety instructions carefully.
- Wiring: The device supports DALI bus power and control. Wiring diagrams are provided for both dimmable and non-dimmable loads. The relay output is dedicated to powering DALI ECGs, with a 5-minute delay for extinguishing.
- Master/Slave Configuration: The device defaults to Master mode. It can be configured as a Slave to extend detection areas, supporting up to 5 Slave devices per Master.
Using the 'CLOSE UP' Mobile App
- Commissioning: The 'CLOSE UP' app (available for iOS and Android) is used for device setup, configuration, and advanced parameter adjustments.
- Features: The app allows for sensor calibration, zone creation (interest and exclusion zones), and monitoring of device status.
- Zone Creation: Users can define up to 6 interest zones and 6 exclusion zones. It is recommended to maintain a distance from obstacles when defining zone coordinates.
- Calibration: The device self-calibrates within 20 minutes of operation. Manual calibration can be initiated via the app.
- Advanced Settings: The app provides access to advanced sensor settings, including offsets and reset functions.
Normative Compliance
- Low Voltage Directive (LVD): Complies with 2014/35/EU and NF EN IEC 62368-1:2020.
- Electromagnetic Compatibility (EMC): Complies with 2014/53/EU, EN55035:2017, EN55032:2015, IEC61000-3-2:2019, EN61000-3-3:2014.
- Radio Equipment Directive (RED): Complies with 2014/53/EU, ETSI EN 301489-1, ETSI EN 301489-17, ETSI300 328 v2.2.2:2020, IEC62311:2020.
- RoHS: Complies with 2011/65/EU and 2015/863/EU.
- WEEE: Complies with European Directive 2002/96/CE.
Maintenance and Cleaning
- Keep the lens clean using a soft cloth.
- Avoid using acetone, stain removers, or trichloroethylene.
- The device is resistant to specific cleaning agents such as hexane, methyl alcohol, soapy water, diluted ammonia, diluted bleach (10%), and glass cleaners. Always test special cleaning products before use.