Resideo Q314U Universal Pilot Burner Installation Guide

Q314U Universal Pilot Burner Installation Guide

Document Number: 69-2754ES-02

Important Notes

This pilot burner replaces only Resideo standard hood-style standing pilot burners. It will not replace batwing style pilot burners or intermittent pilot burners. For standard hood-style intermittent pilot burners, see the Q345U or Q3451U. For batwing-style intermittent pilot burners, see the Q348U.

The specifications provided do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. This product is tested and calibrated under closely controlled conditions; some minor differences in performance should be expected if those conditions are changed.

WHEN INSTALLING THIS PRODUCT:

  1. Read these instructions carefully. Failure to follow instructions can damage equipment or cause a hazardous condition.
  2. Check the cross-reference in the installation guide or box to verify the pilot is suitable for your application.
  3. The installer must be a trained, experienced service technician.
  4. After completing installation, use these instructions to check out product operation.

General Warnings

FIRE OR EXPLOSION HAZARD. CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.

  • Disconnect power supply before wiring to prevent electrical shock or equipment damage.
  • To avoid dangerous accumulation of fuel gas, turn off the gas supply at the appliance service valve before starting installation and perform a Gas Leak Test after completion.
  • Do not bend pilot tubing within 3 inches of the gas control or pilot burner after the compression nut has been tightened, as this can result in gas leakage at the connection.

Follow the appliance manufacturer instructions, if available; otherwise, use the instructions provided.

Cross Reference

Use only as a replacement for these Resideo pilots.

Old Part # Use Hood Set Hood Use Orifice Compression Fitting Bracket
Q314A3471ASLAs Shipped1/8 in.No
Q314A3513ASFAs Shipped1/4 in.Yes
Q314A3547ASLAs Shipped1/4 in.Yes
Q314A3679ASLAs Shipped1/4 in.No
Q314A3687ASFAs Shipped1/4 in.No
Q314A3703ASLGreen Bag1/4 in.No
Q314A3729ASRAs Shipped1/4 in.No
Q314A3737ASFAs Shipped1/4 in.No
Q314A3802ASFGreen Bag1/4 in.No
Q314A3828ASFGreen Bag1/4 in.No
Q314A4586ASF*1/4 in.*
Q314A6094ASL*1/4 in.*
Q314A6102ASR*1/4 in.*
Q314A6557ASFAs Shipped1/4 in.No
Q314A6631ASFAs Shipped1/8 in.No
Q314A6862ASF**No
Q314A6946ASLAs Shipped1/4 in.No
Q314A6953ASLGreen Bag1/4 in.No
Q314A6961ASRAs Shipped1/4 in.No
Q314A9015ASRAs Shipped1/4 in.Yes
Q314AFAASF**Yes
Q314AFBASF**No
Q314AFKASF**No
Q314AKAASR**Yes
Q314AKBASR**No
Q314ALAASL**Yes
Q314ALBASL**No
Q314U1001*****
Q350A1065LBFPink Bag1/4 in.No
Q350A1222LBLPink Bag1/4 in.No
Q350A1271LBRLight Blue Bag1/4 in.No
Q350A1305LBRPink Bag1/4 in.No
Q350A1321LBLPink Bag1/4 in.No
Q350A1545LBLPink Bag1/4 in.Yes
Q350A1644LBLPink Bag1/8 in.No
Q350A1677LBLPink Bag1/8 in.No
Q350A1859LBRYellow Bag1/4 in.No
Q350A1867LBLYellow Bag1/4 in.Yes
Q350A2097LBFLight Blue Bag1/4 in.No
Q350A2212LBFPink Bag1/4 in.No
Q350A2287LBD**Yes
Q350AFBLBF**No
Q350AFKLBF**No
Q350AKALBD**Yes
Q350AKBLBD**No
Q350AKKLBD**No
Q350ALALBL**Yes
Q350ALBLBL**No
Q350ALKLBL**No

Key

Use Hood: AS = As Shipped, LB = Low-BTU Hood (in bag)

Set Hood To: L = Left, F = Front, R = Right

Colors refer to the color of the label on the bag.

Use Orifice

As Shipped = BCR-18 (0.018 in.) Natural gas

Green Bag = BBR-10 (0.010 in.) LP gas

Pink Bag = CAR-12 (0.012 in.) Natural gas

Light Blue Bag = CAR-13 (0.013 in.) Natural gas

Yellow Bag = BBF-8 (0.008 in.) LP gas

* Check Application

Installation Steps

  1. 1. Remove the Old Pilot Burner

    A. Make sure gas is shut off.

    B. Remove old Pilot Burner, including the old compression fitting.

    C. Match the old model number to the Cross Reference.

    D. Use the information in the Cross Reference to install the Pilot Burner.

  2. 2. Set the Hood

    See Cross Reference for position and hood selection.

    NOTE: Choose between standard (installed) or Low BTU Hood (in bag).

    [Diagram: Shows three positions for setting the hood: Right, Left, Front]

    FIRE OR EXPLOSION HAZARD. CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. Pilot flame must be positioned in the exact same position with respect to the main burner. The screw must be installed through the pilot hood and into the spud, so the head of the screw is flush with the adapter. Failure to properly orient the pilot flame and/or secure the pilot hood may create an explosion hazard.

  3. 3. Mount Pilot Burner

    Use the included screws to mount the Pilot Burner. Use the Auxiliary Mounting Bracket if needed.

    Position the Pilot Burner so the pilot flame is aimed at the main burner exactly the same way as the original pilot burner flame.

    [Diagram: Shows correct and incorrect pilot flame alignment to the main burner, labeled "ORIGINAL LOCATION", "TOO LOW", "TOO HIGH"]

    FIRE OR EXPLOSION HAZARD. CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. Pilot burner flame alignment to the main burner is critical to safe appliance operation. Carefully read all installation instructions. Replace only those pilots listed in the literature.

  4. 4. Install the Correct Orifice and Compression Fitting

    See Cross Reference for orifice and sizes.

    NOTE: The Low BTU Hood must be used with one of the orifices packed with it. The standard BTU Hood can only be used with the BBR-10 orifice (Green bag) or the BCR-18 orifice that was initially installed.

    [Diagram: Shows an orifice and a compression fitting]

    Cut off the old compression fitting and replace with the new compression fitting provided with the new pilot burner. Never use the old compression fitting because it might not provide a gas-tight seal.

    FIRE OR EXPLOSION HAZARD. CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. Orifice must be the same size as the original orifice.

  5. 5. Install the Thermocouple or Thermopile

    See Cross Reference for position and size.

    [Diagram: Shows a thermocouple or thermopile being installed]

  6. 6. Gas Leak Test and Checkout

    Gas Leak Test:

    A. Make sure warning card has been removed from the pilot.

    B. Turn on gas supply.

    C. Use a gas sniffer* or paint the pipe connections upstream of the pilot burner with a rich soap and water solution to check for leaks. Bubbles indicate a gas leak.

    D. If a leak is detected, tighten the pipe connections.

    E. Stand clear of the main burner while lighting to prevent injury from hidden leaks, which can cause flashback in the appliance vestibule.

    F. Set the thermostat to call for heat to light the main burner.

    G. With the main burner in operation, paint the pipe joints (including the adapters) and gas control inlet and outlet with rich soap and water solution or use a gas sniffer* to check for leaks.

    H. If another leak is detected, tighten the adapter screws, joints, and pipe connections.

    I. Replace the part if the leak cannot be stopped.

    J. Do not proceed until all gas leaks are eliminated.

    * See AHRI video for proper use and considerations when using an electronic gas sniffer.

    Checkout:

    Cycle the furnace through several cycles to ensure proper smooth light off.

    FIRE OR EXPLOSION HAZARD. CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. Check for gas leaks any time work is done on a gas system.

  7. 7. Adjust Pilot Flame

    Ignite Pilot Burner:

    A. Turn the thermostat to its lowest setting. Wait for unburned gas to vent.

    NOTE: LP gas is heavier than air and will not vent upward. Smell for LP gas next to floor. If you smell gas, shut off the main valve in the gas piping or, on LP systems, at the tank. Perform Gas Leak Test to recheck the connections.

    B. Light the pilot burner according to the appliance manufacturer instructions.

    Adjust Pilot Flame:

    The pilot flame should envelop 3/8 to 1/2 in. (10 to 13 mm) of the igniter-sensor tip.

    A. Remove the pilot adjustment cover screw from the gas control.

    B. Turn the inner pilot adjustment screw clockwise to decrease or counterclockwise to increase the pilot flame.

    C. Replace the pilot adjustment cover screw and tighten firmly after completing adjustment to ensure proper operation.

    NOTE: If Pilot flame is too small and cannot be adjusted large enough, a larger orifice may be needed. Check application requirements. If Pilot flame is too large and cannot be adjusted smaller, a smaller orifice may be needed. Check application requirements.

    FIRE OR EXPLOSION HAZARD. CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH. Using the incorrect orifice or pilot hood can cause an unstable pilot, too large or too small of a pilot, pilot outage, reduced pilot life, improper lightoff, or gas buildup.

Models: Q314U Universal Pilot Burner, Q314U, Universal Pilot Burner

File Info : application/pdf, 2 Pages, 1,018.80KB

PDF preview unavailable. Download the PDF instead.

69-2754ES Adobe PDF Library 15.0

Related Documents

Preview Resideo V400 & V800 Combination Gas Controls Installation Guide
Comprehensive installation and operation manual for Resideo V400 and V800 Combination Gas Controls, detailing application, installation, wiring, safety checks, and troubleshooting for gas-fired appliances.
Preview Resideo S8610U Universal Intermittent Pilot Gas Ignition Control Quick Reference Guide
A technician's quick reference guide for the Resideo S8610U Universal Intermittent Pilot Gas Ignition Control, covering wiring, settings, adjustments, and troubleshooting.
Preview Resideo SV9401/SV9402/SV9403, SV9501/SV9502/SV9503, SV9601/SV9602 SmartValve™ Installation Instructions
Comprehensive installation instructions, specifications, and troubleshooting guide for Resideo SV9401, SV9402, SV9403, SV9501, SV9502, SV9503, SV9601, and SV9602 SmartValve™ ignition system controls. Covers application, safety warnings, installation procedures, wiring diagrams, and maintenance.
Preview Resideo Application Selection and Cross-Reference Guide
A comprehensive guide from Resideo for selecting and cross-referencing HVAC components, including gas valves, ignition modules, thermocouples, fan timers, furnace controls, aquastats, oil primaries, relays, and more. Features detailed product information and replacement guides.
Preview Resideo 32001754-001 Current Sensing Relay Installation Guide
Installation and wiring instructions for the Resideo 32001754-001 Current Sensing Relay. This device detects blower activation to energize accessory equipment like humidifiers in HVAC systems.
Preview Resideo V404, V504, V524, V804, VS824 Automatic Valve Operators Installation Guide
Comprehensive installation, wiring, and calibration guide for Resideo V404, V504, V524, V804, and VS824 automatic valve operators used in combination gas controls.
Preview V8205, VR8205 Direct Ignition Combination Gas Controls Installation Guide
Comprehensive installation instructions for Resideo's V8205 and VR8205 Direct Ignition Combination Gas Controls, detailing application, safety precautions, conversion procedures, installation steps, wiring, startup, and troubleshooting.
Preview Resideo L7224 Series Oil Electronic Aquastat Controller Guide
A technician's quick reference guide for the Resideo L7224 Series Oil Electronic Aquastat Controller, covering installation, operation, and troubleshooting.