Resideo S8610U Universal Intermittent Pilot Gas Ignition Control

TECHNICIAN'S QUICK REFERENCE GUIDE

Product Overview

The following service procedure provides a quick overview for the S8610U series control. For more information, refer to form 69-1955.

WARNING: Explosion Hazard. Can cause serious injury or death. This device can malfunction if it gets wet. Never try to use a device that has been wet - replace it. If module has been used with vent damper, it will only work with damper connected.

Typical Wiring Connections

Refer to Figure 1 for typical wiring connections.

Connector Label Size or Type Description
MV 1/4 inch Main Valve connection
MV/PV 1/4 inch Common terminal for gas valves
PV 1/4 inch Pilot Valve connection
BRN GND 1/4 inch Burner Ground
24V GND 1/4 inch Return path to transformer
24V (OPT.) 1/4 inch Optional - 24 Vac power connection for Vent Damper
TH-W 1/4 inch Connector for "Call for Heat" signal from thermostat
P1 6-pin keyed plug Connector for Vent Damper connection (used to control a connected damper in atmospheric appliances)
SPARK 1/4 inch High voltage sparking electrode
METER (μΑ) Wire with 3/16 inch quick connect Connection for ammeter probes for measuring flame current in μAmp DC.
SENSE JUMPER WIRE 3/16 inch quick connect Connects to the REMOTE SENSE connector for installations with a single spark rod (local flame sensing)
REMOTE SENSE 3/16 inch quick connect For single rod installations, connect the SENSE JUMPER WIRE to this terminal connector. For dual rod installations, connect the flame sense wire from the burner/igniter to this terminal connector.

Figure 1: Typical wiring connections.

Settings and Adjustments

DIP Switch (S1) Settings

When replacing an existing ignition control with the S8610U, refer to 69-1955 for the correct DIP switch settings.

IMPORTANT: Do not power the ignition control prior to setting the DIP switches.

The following timing parameters may be set with this 2-position DIP switch:

Prepurge

To select Prepurge, set SW1 according to Table 2.

Trial for Ignition (TFI)

To select the Trial for Ignition timing, set SW2 according to Table 2.

SW1 SW2 Prepurge Trial For Ignition
OFF OFF None 90 seconds
ON OFF 30 seconds 90 seconds
OFF ON None 15 seconds
ON ON 30 seconds 15 seconds

Figure 2: DIP Switch (S1) Location.

Figure 3: DIP Switch (S1) - shown with factory default settings (OFF) for SW1 and SW2.

NOTE: For installations with spark and sensor rods, this jumper wire is clipped as close to the circuit board as possible and the wire is discarded.

LED Status and Troubleshooting

The ignition control module has one LED used for flame sensing and system status.

Figure 4: Location of LED.

Green LED Flash Codes Indicates Next System Action Recommended Service Action
OFF No "Call for Heat" Not applicable None
Flash Fast Heartbeat Power up - internal check None
4 Seconds ON then "x" flashes Normal startup - ignition sequence started (including prepurge) Not applicable None
2 flashes 5 minute Retry Delay Initiate new trial for ignition after retry delay completed. If system fails to light on next trial for ignition check gas supply, pilot burner, spark and flame sense wiring, flame rod contaminated or out of position, burner ground connection.
3 flashes Pilot flame not detected during trial for ignition Initiate new trial for ignition. Flash code will remain through the ignition trial until flame is proved. If system fails to light on next trial for ignition, check gas supply, pilot burner, flame sense wiring, contamination of flame rod, burner ground connection.
4 flashes Flame sensed out of sequence Recycle Check for pilot flame. Replace gas valve if pilot flame present. If no pilot flame, cycle "Call for Heat." If error repeats, replace control.
5 flashes Damper Error: Damper required but not present, Damper failed to open within 60 seconds, Damper failed to close within 60 seconds If situation self corrects within 10 seconds, control module returns to normal sequence. If flame out of sequence remains longer than 10 seconds, control will resume normal operation 1 hour after error is corrected. If damper error corrects, ignition control resumes normal operation. Check damper connection, damper wiring, and 24V connection on control. Replace damper if necessary. Cycle "Call for Heat." If error repeats, replace control.
6 flashes Control Internal Error Control module remains in wait mode. When the fault corrects, control module resumes normal operation. Cycle "Call for Heat." If error repeats, replace control.
7 flashes Flame rod shorted to ground Control module remains in wait mode. When the fault corrects, control module resumes normal operation. Check flame sense lead wire for damage or shorting. Check that flame rod is in proper position. Check flame rod ceramic for cracks, damage or tracking.
8 flashes Low secondary voltage supply Control module remains in wait mode. When the fault corrects, control module resumes normal operation. Check transformer and AC line for proper input voltage to the control. Check with full system load on the transformer.

Flash Code Descriptions:

Flame Current Measurement

Flame current of the device can be measured using a standard micro-ammeter by simply inserting the meter probes into the holes labeled FLAME CURRENT, as shown in Figure 5.

Flame current must be measured with pilot valve lit but no main gas flowing.

NOTE: Trying to measure the pilot flame current in series with the wiring will not be accurate.

Recommended Minimum Pilot Only Flame Current: Must read steady 1 µAmp DC minimum. Flame current should be 2 µAmp or greater for reliable appliance operation.

Figure 5: Measuring flame current with micro-ammeter.

Contact Information

Resideo Technologies, Inc.

1985 Douglas Drive North, Golden Valley, MN 55422

1-800-468-1502

www.resideo.com

Models: S8610U, Universal Intermittent Pilot Gas Ignition Control

File Info : application/pdf, 2 Pages, 919.44KB

PDF preview unavailable. Download the PDF instead.

69-2042 Acrobat Distiller 21.0 (Windows)

Related Documents

Preview Resideo SV9401/SV9402/SV9403, SV9501/SV9502/SV9503, SV9601/SV9602 SmartValve™ Installation Instructions
Comprehensive installation instructions, specifications, and troubleshooting guide for Resideo SV9401, SV9402, SV9403, SV9501, SV9502, SV9503, SV9601, and SV9602 SmartValve™ ignition system controls. Covers application, safety warnings, installation procedures, wiring diagrams, and maintenance.
Preview Resideo S9200U1000 Universal Hot Surface Ignition Integrated Furnace Control Installation Instructions
This document provides installation, configuration, and troubleshooting instructions for the Resideo S9200U1000 Universal Hot Surface Ignition Integrated Furnace Control, designed for single-stage gas heating and cooling appliances.
Preview V8205, VR8205 Direct Ignition Combination Gas Controls Installation Guide
Comprehensive installation instructions for Resideo's V8205 and VR8205 Direct Ignition Combination Gas Controls, detailing application, safety precautions, conversion procedures, installation steps, wiring, startup, and troubleshooting.
Preview Resideo Application Selection and Cross-Reference Guide
A comprehensive guide from Resideo for selecting and cross-referencing HVAC components, including gas valves, ignition modules, thermocouples, fan timers, furnace controls, aquastats, oil primaries, relays, and more. Features detailed product information and replacement guides.
Preview 34-00029-03: Replacing R8184G4009 with R7284U Wiring and Installation Guide
Installation guide for the Resideo R7284U1004 oil primary control, detailing wiring to replace the R8184G4009 and comprehensive installer setup options for HVAC systems.
Preview Resideo V400 & V800 Combination Gas Controls Installation Guide
Comprehensive installation and operation manual for Resideo V400 and V800 Combination Gas Controls, detailing application, installation, wiring, safety checks, and troubleshooting for gas-fired appliances.
Preview Resideo Q314U Universal Pilot Burner Installation Guide
Comprehensive installation guide for the Resideo Q314U Universal Pilot Burner, covering safe replacement, cross-reference tables, and operational checks for gas appliances.
Preview Resideo V404, V504, V524, V804, VS824 Automatic Valve Operators Installation Guide
Comprehensive installation, wiring, and calibration guide for Resideo V404, V504, V524, V804, and VS824 automatic valve operators used in combination gas controls.