EDA Wiring Diagram

This document outlines the wiring connections for the EDA unit, compatible with Lennox control boards CBK45UHET, CBK45UHVT, and CBK47UHET.

EDA Unit Components

EDA Unit

RDS in EDA

EDA Valve (M)

Connections: RED, GREY, BLACK wires.

EDA Relay

Terminals: 1, 2, 3, 4, 5, 6.

* DIODE IS CONCEALED IN THE WIRE.

Control Board and Connections

CONTROL BOARD

Sensor #1 (W1, G, O/S, R, DS, C, Y1, Y2)

Sensor #2 (W2, G, O/S, R, DS, C, Y1, Y2)

Power: 24V

CBK45UHET/ CBK45UHVT/ CBK47UHET

RDS in Air Handler

K183 Indoor Blower Relay

2-STAGE UNIT

Connections: Y1, Y2 to B2, B3 via K183-1.

1-STAGE UNIT

Connections: Y1, Y2 to B2, B3 via K183-1.

Wiring Notes and Instructions

⚠️ DS-Y1 JUMPER - MUST BE REMOVED FOR HUMIDITROL OPERATION

⚠️ Y1-Y2 JUMPER - ONLY REMOVE IF 2-STAGE COOLING

⚠️ RDS SENSOR in EDA UNIT MUST BE INSTALLED IN SENSOR #2 LOCATION

CONNECT LOW VOLTAGE EDA HARNESS TO CONTROL BOARD IN AIR HANDLER FOR HUMIDITROL OPERATION

⚠️ REFER TO EDA INSTALLATION INSTRUCTION, REPLACE THE CONTROL BOARD IN AIR HANDLER (1 RDS INPUT) WITH CONTROL BOARD SHIPPED WITH THE EDA (2 RDS INPUT) FOR HUMIDITROL OPERATION

Component Key

KEY DESCRIPTION COMPONENT
RDS A2L LEAK SENSOR
K183 INDOOR BLOWER RELAY

NOTE: IF ANY WIRE IN THIS APPLIANCE IS REPLACED, IT MUST BE REPLACED WITH WIRE OF LIKE SIZE, RATING, INSULATION THICKNESS AND TERMINATION.

Models: CBK45UHET, CBK45UHVT, CBK47UHET, CBK45UHET Horizontal Air Handler, CBK45UHET, Horizontal Air Handler, Air Handler, Handler

PDF preview unavailable. Download the PDF instead.

538621-01 pdfplot16.hdi 16.02.053.00000 AutoCAD LT 2023 - English 2023 (24.2s (LMS Tech))

Related Documents

Preview Lennox Heat Pump AHRI System Matches
Comprehensive guide to Lennox heat pump AHRI system matches, detailing model compatibility, cooling and heating performance ratings (SEER2, EER2, HSPF2, COP), and specifications for HVAC professionals and consumers.
Preview R454B Refrigerant Charging Information and Procedures for Lennox HVAC Systems
Comprehensive guide for R454B refrigerant charging, detailing subcooling and weigh-in methods, operating pressures, and indoor unit compatibility with charge levels for Lennox HVAC equipment.
Preview Lennox CBK47UHET Air Handler Unit Information and Specifications
Comprehensive guide to the Lennox CBK47UHET Series Air Handler Units, covering installation, operation, safety precautions, and technical specifications. Includes dimensions, electrical data, and blower performance charts for various models.
Preview Lennox SL280UHVK Furnace Wiring Diagram Addendum
This document provides an addendum to the installation instructions for the Lennox SL280UHVK gas furnace, featuring wiring diagram 538484-02. It details electrical connections, safety components, and blower speed configurations for optimal furnace operation and installation.
Preview Lennox RDS Non-Communicating Control Board Installation and Setup Guide
Comprehensive guide for installing and setting up the Lennox Low GWP Refrigerant Detection System (RDS) Non-Communicating Control Board (24 Volt Only), including features, specifications, wiring diagrams, and troubleshooting.
Preview Lennox VOWD018S6-5P VRF 1-Way Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox VOWD018S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, refrigerant system, fan, controls, external heat control, convenience features, technical specifications, and accessories.
Preview Lennox LB-101123B Low Ambient Control Kit Installation Instructions
Comprehensive installation guide for the Lennox LB-101123B Low Ambient Control Kit, designed for single outdoor fan heat pump units operating with R410A refrigerant. Includes detailed steps, wiring diagrams, component specifications, and operational checkout procedures for both cooling and heating modes.
Preview Lennox ML296UHV(K) Merit Series Gas Furnace - Product Specifications and Features
Comprehensive product specifications, feature highlights, installation details, and technical data for the Lennox ML296UHV(K) Merit Series residential gas furnace. Learn about its 96% AFUE, two-stage heating, variable speed blower, and advanced controls.