GENESIS Commercial R-32 Unit Quick Installation Guide - Package
Model Numbers
PRV15BT-TFFT-EV, PRV17BT-TFFT-EV, PRV15BT-TVFT-EV, PRV17BT-TVFT-EV
Under/Over Unit
* Front discharge Air Handling Option shown for illustration purposes only.
[A2L Flammable Refrigerant] The system is charged with flammable refrigerant, safety checks are necessary to ensure that the risk of ignition is minimised.
IMPORTANT NOTE
This document contains installation information only. Do not attempt to install the unit without reading and understanding the complete installation manual. The complete Installation and Commissioning Guide (0525-147) can be accessed by scanning the QR Code or by visiting docs.actronair.com.au.
Symbol Key:
- [A2L Flammable Refrigerant]: This symbol shows that this appliance uses a flammable refrigerant. If the refrigerant leaks and is exposed to an external ignition source, there is a risk of fire.
- [Read Operation Manual]: This symbol shows that the Operation Manual should be read carefully.
- [Service Person Required]: This symbol shows that a service person should be handling this equipment with reference to the Installation Manual.
- [Information Included]: This symbol shows that there is information included in the Operation Manual and Installation Manual.
1. Codes, Regulation and Standards
The installer and/or contractor assumes responsibility to ensure that unit installation complies with the relevant council, state / federal codes, regulations and building code standards. All electrical wiring must be in accordance with national wiring regulations and all wiring connections to be as per electrical diagram provided with the unit.
2. Installation Safety Instructions
- Only licensed HVAC technicians* should install and service this air conditioning equipment.
- All electrical work must be carried out by a qualified technician. Make sure all wiring is in accordance with local wiring rules. Wiring connections should be made in accordance with the wiring diagram provided.
- Prevailing WH&S regulations must be observed and will take precedence to the safety instructions contained on this unit.
- Ensure that unit installation complies with relevant council regulations and building code standards.
- Always wear appropriate PPE, remove any dangling jewellery and protect long hair.
- Make sure that safety guards and panel covers are always firmly secured and not damaged before and during operation of unit.
- This appliance is not intended for use by young children, persons with a lack of experience and knowledge, or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance.
- Installer must incorporate a means of electrical disconnection (isolator) in the sub mains fixed wiring in accordance with the latest edition of the AS/NZS 3000 (also known as Australian Wiring Rules).
- Ensure all power and control cables are firmly secured. Use the cable ties provided in the control box.
* Qualifications required will be appropriate Electrical, Refrigeration and Refrigerant Handling License and Training dependent on local State/Territory regulations.
3. Unit Dimensions
Notes: Model shown below is for illustration purposes only.
*Mounting Distance Base Foot (Centre to Centre)
Top View
Diagram showing the top view of the unit, indicating overall dimensions (W, L, H), internal components like Indoor Coil and Fans, Outdoor Coil, and Compressor Side. It also denotes duct work dimensions (W-RD, W-SD) and service clearances (A*, B*).
Model Number | H | W | L | A* | B* |
---|---|---|---|---|---|
PRV15BT-T | 1166 | 1523 | 1136 | 1036 | 1208 |
PRV17BT-T | 1166 | 1523 | 1136 | 1036 | 1208 |
Front View
Diagram showing the front view of the unit, detailing its height (H), width (W), and base mounting distance (B*). It highlights Supply Air and Return Air outlets, Compressor Side, and service clearances (H-SD, H-RD).
Model Number | Supply Duct H-SD x W-SD | Return Duct H-RD x W-RD |
---|---|---|
PRV15BT-T | 200 x 740 | 348 x 1100 |
PRV17BT-T | 200 x 740 | 348 x 1100 |
Notes for Dimensions:
- Do not scale drawing. All dimensions are in mm unless otherwise specified. Refer to corresponding unit dimensional drawing for mounting hole details.
- Service Access Areas and Spaces for Airflow Clearances are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkaway passage of 1000 mm between the units or between the unit and the outside perimeter is available.
- Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
- Under all circumstances, condenser air must not recirculate back onto condenser coil. Keep all clearance free of any obstruction.
- MTG C-C DIST = Mounting Centre to Centre Distance.
- Use M12 bolt for feet mounting.
- Installation of this unit should be in accordance with AS/NZS 60335.2.40.
- Additional safety provision maybe needed such as leak detector sensor and/or ventilation to meet the minimum area requirement. For more details refer to Annex GG and Annex HH of the above standard.
- Refer to R-32 Safety Manual for minimum required area of installation.
4. Unit Weight, Airflow and Service Access Clearances
Diagram illustrating service clearances and airflow allowances around the unit. It specifies dimensions for duct work (A-B), service access (X, Y, Z), and a required Height Clearance of 1500 mm. Key components like Indoor Coil, Fans, Outdoor Coil, and Compressor Side are shown.
Model Number | A-B Duct Work | X | Y | Z | No. of Comp |
---|---|---|---|---|---|
PRV15BT-T | 300 | 400 | 600 | 1 | |
PRV17BT-T | 300 | 400 | 600 | 1 |
Unit and Corner Weights
Model Number | A (kg) | B (kg) | C (kg) | D (kg) | Total Weight (kg) |
---|---|---|---|---|---|
PRV15BT-T | 46 | 63 | 57 | 67 | 233 |
PRV17BT-T | 49 | 66 | 59 | 68 | 242 |
5. Cable Size and Circuit Breaker Size Requirement
Model Number | Circuit Breaker Size Amps |
---|---|
PRV15BT-T | 16.0 |
PRV17BT-T | 16.0 |
Refer to the latest edition of AS/NZS 3000 or Australian/New Zealand Wiring Rules to determine required cable size.
6. Outdoor Unit Preparation
- Rotate the Hex Recess 90 degrees using 8mm allen key [rotate 90 degrees].
- Remove Access Panel-Electrical as illustrated below.
- Remove the Shipping Blocks before installing Interconnection Field Pipes.
- a. Loosen the 3 x compressor feet bolts [loosen bolts].
- b. Remove Shipping blocks as shown below.
- c. Re tighten the 3 x compressor feet bolts (12 to 14Nm) [tighten bolts].
Illustration detailing outdoor unit preparation. It shows the access panel and its hex recess cam latch, with a three-step removal process: (A) Rotate latch 90 degrees [rotate 90 degrees], (B) Pull out 20mm, (C) Pull down. It also indicates the need to loosen [loosen bolts] and then re-tighten [tighten bolts] compressor feet bolts after removing shipping blocks [shipping blocks].
7. Electrical Connections
Diagram for electrical connections. It guides the user to loosen [loosen bolts] and re-tighten [tighten bolts] compressor feet bolts after removing shipping blocks [shipping blocks], and to gently push back the compressor. It also reminds to record the final refrigerant charge.
Wiring Diagram
Wiring diagram showing main electrical connections: Main Supply from Distribution Board via Sub-Mains Isolator and Circuit Breaker to the unit, and a Data Cable to the Wall Controller. Labeled as: 1. MAINS WIRING (400VAC, Three Phase + Neutral + Earth) 50Hz, 2. DATA CABLE TO WALL CONTROLLER (Cat5E UTP (AWG24) Data Cable).
8. Indoor Fan External Static Pressure Range
Model Number | External Static Pressure Pa |
---|---|
PRV15BT-T | 0-250 |
PRV17BT-T | 0-250 |
Note: Available external static pressure (Pa) within the airflow range.
9. Refrigeration System
Installation of this unit should be in accordance with AS/NZS-60335.2.40. Ensure that the minimum required release height (with respect to system's total R-32 refrigerant charge and minimum room size of the smallest conditioned area) is satisfied.
If the smallest room that needs to be conditioned is smaller than the required minimum room area (Amin), additional safety measures must be implemented according to AS/NZS-60335.2.40. For further details, please refer to Annex GG and Annex HH of the AS/NZS-60335.2.40 standard. Refer to the R-32 Safety Manual. Refer to Table Required Minimum Room Area (Amin).
If the maximum refrigerant amount exceeds 15964 grams, the installer must implement additional control measures in accordance with AS/NZS 60335.2.40 standard for the installation to be deemed acceptable.
Examples of control measures include, but are not limited to, ventilation, shut-off valves, and safety alarms. These control measures are not provided by ActronAir and must be determined by the installer based on the specific requirements of each installation.