Eaton SD40 40kA Surge Diverter

Installation and Operation Guide

IPN 997-00012-77D

March 2016

Worldwide Support

For product information and a complete listing of worldwide sales offices, visit Eaton's website at: dcpower.eaton.com or email: DCinfo@eaton.com

For technical support contact either your local Eaton dc product representative, the closest office from the following list, telephone (+64) 3-343-7448, or email CustomerServiceNZ@eaton.com

Region Contact Information
Australia Services 1300-303-059
DC Sales 1300-877-359
Canada 1-800-461-9166
LAN (Mexico, Central America, Caribbean and Andean region) +52 55-9000-5252
China +86 755-2757-2666 - extension 3024
Europe/Middle East / Africa +44 1243-810-500
Hong Kong/Korea/Japan +852 2745-6682
India +91 11-4223-2325
New Zealand 0508 NZ Service (0508-697-378)
Singapore/South East Asia Service Hotline +65 6825-1680
Sales +65 6825-1668
South America +54 11-4124-4000
South Pacific +64 3-343-7448
Taiwan +886 2-6600-6688 or free call 0800-038-168
United States of America (Toll Free) 1-800-843-9433 - option 2 - option 6

Product Overview

The Eaton SD40 is a 40kA surge diverter designed to protect Eaton dc power systems at sites with low-medium risk of damage from voltage transients (surges). Two models are available for either single-phase or 3-phase.

The SD40 includes an input MCB/isolator and metal oxide varistor (MOV) surge diverters connected line-neutral and neutral-earth.

The SD40 can be fitted with either Eaton or Phoenix MOVs.

Key Components:

Installation

Important Safety Note: All work must comply with the applicable electrical wiring regulations and be carried out by a registered electrician or other suitably qualified person. Isolate ac sources before making connections.

  1. Unpack and check the SD40. Check you have the correct model for either single-phase or 3-phase, as required. Contact the product supplier if any item is damaged or missing. Do not use the SD40 if it is damaged.
  2. Mount the SD40 as close as possible to the main switchboard or sub-distribution board.
  3. If required, wire from the MOV and MCB alarm connectors to a digital input of the Eaton dc power system (Active State = Closed), or other alarm monitoring system. The diagram shows the recommended connection method. For 3 phase versions, the MOV alarm contacts are wired in parallel. The alarm circuit will be closed if a MOV cartridge fails, a MOV cartridge is removed (Phoenix MOV only) or, the MCB is off.
  4. Install 32A (or greater) HRC fuses (one per phase) in the main switchboard or sub-distribution board. For the best transient protection the fuses must connect as close as possible to the main ac supply conductors. MCBs may be used, but must be rated 32A or greater.
  5. Wire (via the shortest route) from the HRC fuse(s) (or MCBs) to the MCB (L1, L2 and L3) in the SD40. All wire sizes must suit the rating of the HRC fuses (or MCBs).
  6. Wire from the neutral bar in the main switchboard or sub-distribution board to the neutral (N) terminal in the SD40.
  7. Wire from the protective-earth bar in the main switchboard or sub-distribution board to the protective-earth (PE) terminal in the SD40.
  8. Check that all connections are tight.
  9. Insert the HRC fuse(s) (or switch on the MCBs) in the main switchboard or sub-distribution board. Switch on the MCB in the SD40. Check that supply voltage is present at the L-N connected MOVs.
  10. Replace the cover of the SD40.

Maintenance

Monitoring the MOVs

MOVs are fitted with alarm contacts and visual indicators. Connect these alarms to the dc power system and from there extended to the building or network management system. If the MOVs are not monitored automatically, then regular visual inspections must be carried out.

Replacing the MOVs

MOVs must be functional at all times. In practice, it is impossible to predict when a MOV will fail. That depends entirely on the number and magnitude of the transients sustained.

For that reason, Eaton recommends the following, depending on how accessible the site is:

Specifications

Parameter Value
AC Voltage 220-240V ac (P-N)
Nominal 385V ac (P-N)/260V ac (N-PE)
Frequency 50/60Hz
Responding Time <25ns (P-N)/<100ns (N-PE)
Voltage Protection Level 1.8kV (P-N)/1.0kV (N-PE)
Nominal Discharge Current (8/20 µs) 20kA
Maximum Discharge Current (8/20 µs) 40kA (P-N)/60kA (N-PE)
Maximum back-up fuse 160Agl
MCB Rating 32A (D-curve)
Operating Temperature -40°C to +70°C
Degree of protection IP41
Dimensions 192mm W, 192mm H, 105mm D

The product discussed in this literature is subject to terms and conditions outlined in Eaton selling policies. The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling policy.

No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising from course of dealing or usage of trade, are made regarding the information, recommendations and descriptions contained herein.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.

The information contained in this literature is subject to change without notice.

Subject to the right to use its equipment, Eaton Corporation does not convey any right, title or interest in its intellectual property, including, without limitation, its patents, copyrights and know-how.

No part of this literature may be reproduced or transmitted in any form, by any means or for any purpose other than the Purchaser's personal use, without the express written permission of Eaton Corporation.

Eaton®, Matrix, Powerware®, Intergy™, CellSure™, SiteSure™, PowerManagerII™™ and DCTools™™ are trade names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. Unless otherwise noted, brands, product names, trademarks or registered trademarks are the property of their respective holders.

Copyright © 2009-2013 Eaton Corporation. All Rights Reserved.

Eaton Corporation
Telecommunications Power Solutions
dcpower.eaton.com
DCinfo@eaton.com

Models: SD40 40kVA Surge Diverter, SD40, 40kVA Surge Diverter, Surge Diverter, Diverter

File Info : application/pdf, 2 Pages, 266.54KB

PDF preview unavailable. Download the PDF instead.

eaton-sd40-40kva-surge-diverter-installation-and-operation-guide-en

References

Adobe PDF Library 10.0 Copyright © 2009-2013 Eaton Corporation. All Rights Reserved.

Related Documents

Preview SR-1600 PLUS Inverter Operation Handbook - Eaton
This handbook provides comprehensive operational guidance for the Eaton SR-1600 PLUS Inverter, covering installation, safety, functional characteristics, troubleshooting, and maintenance. Designed for installers and operators, it ensures safe and efficient use of the modular DC-AC inverter system.
Preview Eaton Complete Home Surge Protection CHSP Installation Guide
This document provides installation and operating instructions for the Eaton Complete Home Surge Protection (CHSP) system, including the CHSPT2SURGE and CHSPT2ULTRA modules. It covers mounting, wiring, and troubleshooting for indoor and outdoor installations.
Preview Eaton Complete Home Surge Protection Installation and Operating Guide
This guide provides detailed instructions for installing and operating the Eaton CHSP Complete Home Surge Protection system, including safety precautions, mounting, wiring, and troubleshooting for residential electrical systems.
Preview Eaton 3S Advanced User Guide: Installation, Operation, and Specifications
Comprehensive user guide for the Eaton 3S Uninterruptible Power System (UPS). Covers installation, connection, operation, troubleshooting, and technical specifications for models 3S450, 3S550, 3S700, and 3S850.
Preview Eaton SP1 Surge Protective Device: Installation and Operation Manual
Comprehensive installation and operation manual for the Eaton SP1 Surge Protective Device (SPD). Covers safety, mounting, wiring, specifications, and warranty for electrical systems.
Preview Eaton Aerospace Master Technical Publications Index List
A comprehensive index of technical publications for Eaton Aerospace products, detailing part numbers, model numbers, document types, issue dates, aircraft platforms, and manufacturing sites. This list serves as a crucial resource for maintaining and servicing aerospace components.
Preview Eaton 5E650IUSB UPS: Comprehensive Specifications and Features
Detailed specifications for the Eaton 5E650IUSB Uninterruptible Power Supply (UPS), including power, voltage, connectivity, and operational features. Learn about its compact design, AVR technology, and USB compatibility.
Preview Eaton TLM825USB 8-Outlet Industrial Safety Surge Protector with 2 USB-A Ports
Discover the Eaton TLM825USB, an industrial-grade 8-outlet surge protector featuring 2 USB-A charging ports, 25 ft. cord, 1960 joules of protection, and durable metal housing. Ideal for harsh environments, it offers advanced surge suppression, EMI/RFI filtering, and safety features. View detailed specifications, compliance, and warranty information.