Eaton SD40 40kA Surge Diverter
Installation and Operation Guide
IPN 997-00012-77D
March 2016
Worldwide Support
For product information and a complete listing of worldwide sales offices, visit Eaton's website at: dcpower.eaton.com or email: DCinfo@eaton.com
For technical support contact either your local Eaton dc product representative, the closest office from the following list, telephone (+64) 3-343-7448, or email CustomerServiceNZ@eaton.com
Region | Contact Information |
Australia | Services 1300-303-059 DC Sales 1300-877-359 |
Canada | 1-800-461-9166 |
LAN (Mexico, Central America, Caribbean and Andean region) | +52 55-9000-5252 |
China | +86 755-2757-2666 - extension 3024 |
Europe/Middle East / Africa | +44 1243-810-500 |
Hong Kong/Korea/Japan | +852 2745-6682 |
India | +91 11-4223-2325 |
New Zealand | 0508 NZ Service (0508-697-378) |
Singapore/South East Asia | Service Hotline +65 6825-1680 Sales +65 6825-1668 |
South America | +54 11-4124-4000 |
South Pacific | +64 3-343-7448 |
Taiwan | +886 2-6600-6688 or free call 0800-038-168 |
United States of America (Toll Free) | 1-800-843-9433 - option 2 - option 6 |
Product Overview
The Eaton SD40 is a 40kA surge diverter designed to protect Eaton dc power systems at sites with low-medium risk of damage from voltage transients (surges). Two models are available for either single-phase or 3-phase.
The SD40 includes an input MCB/isolator and metal oxide varistor (MOV) surge diverters connected line-neutral and neutral-earth.
The SD40 can be fitted with either Eaton or Phoenix MOVs.
Key Components:
- 1. Input MCB/isolator (one-pole or three-pole depending on model of SD40)
- 2. MCB alarm connectors
- 3. L-N MOV (one or three depending on model of SD40) and PE-N MOV cartridges
- 4. MOV indicators (green = ok, red = replace)
- 5. MOV alarm connectors (Eaton MOV only)
Installation
Important Safety Note: All work must comply with the applicable electrical wiring regulations and be carried out by a registered electrician or other suitably qualified person. Isolate ac sources before making connections.
- Unpack and check the SD40. Check you have the correct model for either single-phase or 3-phase, as required. Contact the product supplier if any item is damaged or missing. Do not use the SD40 if it is damaged.
- Mount the SD40 as close as possible to the main switchboard or sub-distribution board.
- If required, wire from the MOV and MCB alarm connectors to a digital input of the Eaton dc power system (Active State = Closed), or other alarm monitoring system. The diagram shows the recommended connection method. For 3 phase versions, the MOV alarm contacts are wired in parallel. The alarm circuit will be closed if a MOV cartridge fails, a MOV cartridge is removed (Phoenix MOV only) or, the MCB is off.
- Install 32A (or greater) HRC fuses (one per phase) in the main switchboard or sub-distribution board. For the best transient protection the fuses must connect as close as possible to the main ac supply conductors. MCBs may be used, but must be rated 32A or greater.
- Wire (via the shortest route) from the HRC fuse(s) (or MCBs) to the MCB (L1, L2 and L3) in the SD40. All wire sizes must suit the rating of the HRC fuses (or MCBs).
- Wire from the neutral bar in the main switchboard or sub-distribution board to the neutral (N) terminal in the SD40.
- Wire from the protective-earth bar in the main switchboard or sub-distribution board to the protective-earth (PE) terminal in the SD40.
- Check that all connections are tight.
- Insert the HRC fuse(s) (or switch on the MCBs) in the main switchboard or sub-distribution board. Switch on the MCB in the SD40. Check that supply voltage is present at the L-N connected MOVs.
- Replace the cover of the SD40.
Maintenance
Monitoring the MOVs
MOVs are fitted with alarm contacts and visual indicators. Connect these alarms to the dc power system and from there extended to the building or network management system. If the MOVs are not monitored automatically, then regular visual inspections must be carried out.
Replacing the MOVs
MOVs must be functional at all times. In practice, it is impossible to predict when a MOV will fail. That depends entirely on the number and magnitude of the transients sustained.
For that reason, Eaton recommends the following, depending on how accessible the site is:
- For easily accessible sites - If a MOV has failed (as indicated by a MOV Fail alarm or the visual indicator), then replace all the MOVs as soon as possible.
- For remote sites with difficult access - Replace all the MOVs during scheduled maintenance visits, whether they have failed or not.
Specifications
Parameter | Value |
AC Voltage | 220-240V ac (P-N) |
Nominal | 385V ac (P-N)/260V ac (N-PE) |
Frequency | 50/60Hz |
Responding Time | <25ns (P-N)/<100ns (N-PE) |
Voltage Protection Level | 1.8kV (P-N)/1.0kV (N-PE) |
Nominal Discharge Current (8/20 µs) | 20kA |
Maximum Discharge Current (8/20 µs) | 40kA (P-N)/60kA (N-PE) |
Maximum back-up fuse | 160Agl |
MCB Rating | 32A (D-curve) |
Operating Temperature | -40°C to +70°C |
Degree of protection | IP41 |
Dimensions | 192mm W, 192mm H, 105mm D |
The product discussed in this literature is subject to terms and conditions outlined in Eaton selling policies. The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling policy.
No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising from course of dealing or usage of trade, are made regarding the information, recommendations and descriptions contained herein.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.
The information contained in this literature is subject to change without notice.
Subject to the right to use its equipment, Eaton Corporation does not convey any right, title or interest in its intellectual property, including, without limitation, its patents, copyrights and know-how.
No part of this literature may be reproduced or transmitted in any form, by any means or for any purpose other than the Purchaser's personal use, without the express written permission of Eaton Corporation.
Eaton®, Matrix, Powerware®, Intergy™, CellSure™, SiteSure™, PowerManagerII™™ and DCTools™™ are trade names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. Unless otherwise noted, brands, product names, trademarks or registered trademarks are the property of their respective holders.
Copyright © 2009-2013 Eaton Corporation. All Rights Reserved.
Eaton Corporation
Telecommunications Power Solutions
dcpower.eaton.com
DCinfo@eaton.com
File Info : application/pdf, 2 Pages, 266.54KB
DocumentDocumentReferences
Related Documents
![]() |
SR-1600 PLUS Inverter Operation Handbook - Eaton This handbook provides comprehensive operational guidance for the Eaton SR-1600 PLUS Inverter, covering installation, safety, functional characteristics, troubleshooting, and maintenance. Designed for installers and operators, it ensures safe and efficient use of the modular DC-AC inverter system. |
![]() |
Eaton Complete Home Surge Protection CHSP Installation Guide This document provides installation and operating instructions for the Eaton Complete Home Surge Protection (CHSP) system, including the CHSPT2SURGE and CHSPT2ULTRA modules. It covers mounting, wiring, and troubleshooting for indoor and outdoor installations. |
![]() |
Eaton Complete Home Surge Protection Installation and Operating Guide This guide provides detailed instructions for installing and operating the Eaton CHSP Complete Home Surge Protection system, including safety precautions, mounting, wiring, and troubleshooting for residential electrical systems. |
![]() |
Eaton 3S Advanced User Guide: Installation, Operation, and Specifications Comprehensive user guide for the Eaton 3S Uninterruptible Power System (UPS). Covers installation, connection, operation, troubleshooting, and technical specifications for models 3S450, 3S550, 3S700, and 3S850. |
![]() |
Eaton SP1 Surge Protective Device: Installation and Operation Manual Comprehensive installation and operation manual for the Eaton SP1 Surge Protective Device (SPD). Covers safety, mounting, wiring, specifications, and warranty for electrical systems. |
![]() |
Eaton Aerospace Master Technical Publications Index List A comprehensive index of technical publications for Eaton Aerospace products, detailing part numbers, model numbers, document types, issue dates, aircraft platforms, and manufacturing sites. This list serves as a crucial resource for maintaining and servicing aerospace components. |
![]() |
Eaton 5E650IUSB UPS: Comprehensive Specifications and Features Detailed specifications for the Eaton 5E650IUSB Uninterruptible Power Supply (UPS), including power, voltage, connectivity, and operational features. Learn about its compact design, AVR technology, and USB compatibility. |
![]() |
Eaton TLM825USB 8-Outlet Industrial Safety Surge Protector with 2 USB-A Ports Discover the Eaton TLM825USB, an industrial-grade 8-outlet surge protector featuring 2 USB-A charging ports, 25 ft. cord, 1960 joules of protection, and durable metal housing. Ideal for harsh environments, it offers advanced surge suppression, EMI/RFI filtering, and safety features. View detailed specifications, compliance, and warranty information. |