Stelpro SWU Series Industrial/Commercial Washdown Electric Unit Heater

User's Guide

Important Instructions

WARNING: Installation and maintenance personnel should familiarize themselves with this manual and all the IMPORTANT INSTRUCTIONS before installing or working on this heater to avoid potential unsafe conditions, severe property damage, personal injury or death.

SAVE THESE INSTRUCTIONS

Note: When a part of the product specification must be changed to improve operability or other functions, priority is given to the product specification itself. In such instances, the instruction manual may not entirely match all the functions of the actual product. Therefore, the actual product and packaging, as well as the name and illustration, may differ from the manual.

Installation

Risk of Fire / Explosion

These air heaters are designed for comfort heating and should not be used in ambient temperatures exceeding 80°F (26.7°C). They are to be permanently mounted to the wall or ceiling for horizontal discharge. The unit is designed to give years of safe, trouble-free operation when properly installed and maintained.

Site Selection

The heaters are intended for elevated mounting locations so that they blow warm air down to the floor area. A mounting height should be selected so that the heater is out of the way of possible moving equipment or personnel, yet low enough to deliver warm air to the selected area. See the mechanical installation section for recommended installation heights.

Heater airflow should be directed to areas of greatest heat loss. In general, greater numbers of small heaters will provide more uniform and even heat distributions than a few large ones. In order to help move heated air around the room, multiple heaters should be spaced out and direct air in a circular pattern around the room perimeter such that each heater supports the next heater's airstreams. See Figures 1 & 2 for some typical airflow pattern arrangements:

FIG.1: LARGE ROOM WITH EXPOSED WALLS AND ROOF
FIG.2: SMALL ROOM WITH ONE EXPOSED WALL

Mechanical Installation

These heaters are to be mounted for horizontal discharge only. Mounting is to be accomplished by using either (4) 3/8x16 threaded rods (supplied by others) or the stainless steel swivel mounting bracket factory supplied with the heater. Lock washers should be used on all mounting nuts and bolts to ensure they don't vibrate or work loose due to fan vibration or other vibration transmitted to the heater.

The supporting structure that the heater is attached to must have adequate strength to safely support the heater. The heater dimensions and maximum unit weights are:

TABLE 1
KW CABINET SIZE X Y Z WEIGHT
<= 12 1 15.5 in. (394mm) 21.5 in. (546mm) 13 in. (330mm) 56 lbs (25 kg)
12.1 to 47 2 26 in. (660mm) 28 in. (711mm) 20 in. (508mm) 115 lbs (52 kg)

Installation

FIG.3: Airflow Diagram

Select a location for installation such that the outlet air is not directed at an adjacent wall. Louvered grills can be installed to deflect the discharge air up, down or sideways.

TABLE 2
KW CABINET SIZE AIR VOLUME AIR THROW OUTLET VELOCITY
<= 7.5 1 700 CFM (1189 cubic m/hr) 26 ft. (8 m) 760 FPM (232 m/min)
7.6 to 12 1 1450 CFM (2463 cubic m/hr) 43 ft. (13 m) 1575 FPM (481 m/min)
7.6 to 12 1 1450 CFM (2463 cubic m/hr) 43 ft. (13 m) 1575 FPM (481 m/min)

Once an acceptable location has been determined, see the following instructions to complete the mechanical installation:

  1. To ensure proper heating of floor surfaces, observe the following recommended mounting height limitations (to bottom of heater):
TABLE 3: MAXIMUM MOUNTING HEIGHT FROM FLOOR, FEET (M)
<= 5 KW 5.1 to 10 KW 10.1 to 20 KW 20.1 to 47 KW
10 ft. (3m) 15 ft. (4.6m) 20 ft. (6.1m) 25 ft. (7.6m)
  1. Install the heater at least 6 feet (1.8m) from the floor and 8" (203mm) from the wall or ceiling.
  2. Mount heater using one of the following two options:

STANDARD CEILING OR WALL MOUNT USING THE SWIVEL BRACKET:

MOUNTING HOLE DETAIL - REAR VIEW OF BRACKETS

FIG.4A (1-12 KW)
FIG.4B (12.5-47 KW)

(See TABLE 4 on next page for tabulated dimensions)

Installation

FIG.5: Mounting Configurations

OPTIONAL CEILING INSTALLATION USING 4 THREADED RODS:

For ceiling installation using threaded rods, secure the four rods to the ceiling using locknuts.

FIG.6: Ceiling Installation with Threaded Rods

Installation & Operation

TABLE 4
KW BH BL M
<= 12 4.25 in. (108mm) 19.5 in. (495mm) 8.5 in. (216mm)
12.1 to 47 7.125 in. (181mm) 22.25 in. (565mm) 3.25 in. (83mm)

Electric Shock Hazard

Electrical installation should be made by a qualified licensed electrician. Wiring procedures, connections and grounding shall be in accordance with the national and local codes having jurisdiction.

Electrical Installation

Follow these instructions to complete the electrical installation:

  1. External branch circuit protection is required. See nameplate ratings and follow Code recommendations.
  2. Follow the national and local electrical and building codes related to the installation and intended use of the heater.
  3. When doing any work on a heater, including the initial electrical connection, disconnect the electrical supply at the main branch circuit switch, and lock the switch in the off (open) position. Tag the circuit "Out for Maintenance" to prevent potential lethal shock hazards.
  4. Confirm that the electrical power supply matches the nameplate voltage, phase, amperage and frequency rating of the heater to be connected.
  5. Field supply conductors must be sized for at least 125% of the circuit current. The circuit current in amps is calculated as follows:

Single Phase Amperage = Circuit kW x 1000 / Circuit Voltage

Three Phase Amperage = Circuit kW x 1000 / (1.732 x Circuit Voltage)

  1. Use copper conductors rated 90°C minimum with watertight conduit fittings.
  2. Field wiring to the heater must comply with all branch circuit requirements of any national and local codes having jurisdiction.
  3. Proper installation of the heater requires that an adequate grounding conductor be connected to the ground terminal. This terminal marked with the letter "G" and is located on the inside of the control enclosure.
  4. A wiring diagram is supplied with each heater and is located on the inside surface of the control enclosure cover.
  5. Check and confirm all connections are securely tightened. Remove any foreign objects from the control box and close access door.
  6. See section titled "OPERATION" before energizing the heater.

Operation

Risk of Fire / Explosion

Electric Shock Hazard

Risk of Injury / Burn

The unit is designed to give years of safe, trouble-free operation when properly installed and maintained. Please read the following guidelines to ensure reliable operation:

  1. Confirm proper mechanical and electrical installation before operation of the heater.
  2. This unit heater may be operated at ambient temperatures of 80°F (26.7°C) or less.
  3. Make sure the wiring enclosure cover is closed securely.
  4. Set the temperature control thermostat to a setting above the current room temperature.
  5. If the heater is provided with a selector switch, it must be in the ON position.
  6. Energize the heater electrical supply circuit.
  7. The heater and fan should come on.
  8. Check for the correct fan blade rotation. If air is not discharging through the louvers, interchange any two of the three field supplied power leads on three phase units only.
  9. Since the heater is equipped with a built-in time delay relay, the fan will remain in operation for about a minute to cool the elements after the heater is switched off either by the thermostat or the selector switch. Do not turn the heater off at the main disconnect switch, as this will prevent the fan from cooling elements.
  10. During normal operation, the limit controls are not supposed to cycle the heater ON and OFF. If frequent cycling of the limit controls occurs, verify the minimum mounting clearances are maintained, proper operation of the room thermostat and that there is no visible obstruction to the heater inlet or outlet. If this does not eliminate the limit control cycling, the heater must be examined by qualified service personnel before further operation to determine the cause.
  11. Heater may be provided with a manual reset limit control (order code M). This limit control disables the electrical function of the heater whenever excessive temperatures are present. If the manual reset limit control is suspected of causing heater non-function then the heater must be disconnected from the heater electrical supply and examined by a qualified service personnel. The personnel must determine the cause of the excessive temperatures, verify the minimum mounting clearances, verify proper orientation of the heater, verify proper orientation of the room thermostat, or if there are any obstructions or damage to the heater or heater inlet or heater outlet. The manual reset limit control may be reset, after determining the cause, by removing the electrical enclosure cover and pressing on the manual reset button. The location of the manual reset button within the electrical enclosure is shown in the Maintenance Instructions.
  12. Check out and report any unusual or questionable operating characteristics, such as noise, vibration, etc.
  13. Set the temperature control thermostat to the desired room temperature setting and place unit in service.

Maintenance

Electric Shock Hazard

Risk of Injury / Burn

Maintenance and repair must be performed by qualified service personnel only.

Electrical

Inspect all terminal connections, contactors and conductor insulation for damage, looseness, fraying, etc., as applicable. Tighten any loose terminals and replace or repair wire that has damaged or deteriorated insulation. Replace any contactor that has contacts that are badly pitted, welded together, or burned.

If reduced heat output is suspected, perform the mechanical checks. If low heat output is still suspected after completing the mechanical checks, verify the condition of the heating elements by visual inspection and by using an amperage meter to check the current draw of each input line. Adjust the room thermostat to its highest temperature to energize heater. All input lines should draw approximately equal current which should agree with the nameplate rating. If they do not, one or more of the heating elements could be burned out and should be replaced.

For heaters supplied with the optional manual reset limit control (order code 'M'), the electrical enclosure cover must be opened to gain access to the reset button. See below to locate the reset button:

FIG.7: Manual Reset Button Location

Mechanical

Before cleaning or servicing, ensure power has been turned off at the service panel and the heating elements are cool.

Limited Warranty

This limited warranty is offered by Stelpro Design inc. ("Stelpro") and applies to the following product made by Stelpro: model SWU. Please read this limited warranty carefully. Subject to the terms of this warranty, Stelpro warrants its products and their components against defects in workmanship and/or materials for the following periods from the date of purchase: 1 year. This warranty applies only to the original purchaser; it is non-transferable and cannot be extended.

Claim Procedure

If at any time during the warranty period the unit becomes defective, you must cut off the power supply at the main electrical panel and contact 1) your installer or distributor, 2) your service center or 3) Stelpro's customer service department. In all cases, you must have a copy of the invoice and provide the information written on the product nameplate. Stelpro reserves the right to examine or to ask one of its representatives to examine the product itself or any part of it before honoring the warranty. Stelpro reserves the right to replace the entire unit, refund its purchase price or repair a defective part. Please note that repairs made within the warranty period must be authorized in advance in writing by Stelpro and carried out by persons authorized by Stelpro.

Before returning a product to Stelpro, you must have a Stelpro authorization number (RMA). To obtain it, call the customer service department at: 1-800-363-3414 (electricians and distributors - French), 1-800-343-1022 (electricians and distributors - English), or 1-866-766-6020 (consumers). The authorization number must be clearly written on the parcel or it will be refused.

Conditions, Exclusions and Disclaimer of Liability

This warranty is exclusive and in lieu of all other representations and warranties (except of title), expressed or implied, and Stelpro expressly disclaims and excludes any implied warranty of merchantability or implied warranty of fitness for a particular purpose.

Stelpro's liability with respect to products is limited as provided above. Stelpro shall not be subject to any other obligations or liabilities whatsoever, whether based on contract, tort or other theories of law, with respect to goods or services furnished by it, or any undertakings, acts or omissions relating thereto. Without limiting the generality of the foregoing, Stelpro expressly disclaims any liability for property or personal injury damages, penalties, special or punitive damages, damages for lost profits, loss of use of equipment, cost of capital, cost of substitute products, facilities or services, shutdowns, slowdowns, or for other types of economic loss or for claims of a dealer's customers or any third party for such damages. Stelpro specifically disclaims all consequential, incidental and contingent damages whatsoever.

This warranty does not cover any damages or failures resulting from: 1) a faulty installation or improper storage; 2) an abusive or abnormal use, lack of maintenance, improper maintenance (other than that prescribed by Stelpro) or a use other than that for which the unit was designed; 3) a natural disaster or an event out of Stelpro's control, including, but not limited to, hurricanes, tornadoes, earthquakes, terrorist attacks, wars, overvoltage, flooding, water damages, etc. This warranty does not cover any accidental or intentional losses or damages, nor does it cover damages caused by negligence of the user or owner of the product. Moreover, it does not cover the cost of disconnection, transport, and installation.

The warranty is limited to the repair or the replacement of the unit or the refund of its purchase price, at the discretion of Stelpro. Any parts replaced or repaired within the warranty period with the written authorization of Stelpro will be warranted for the remainder of the original warranty period. This warranty will be considered null and void and Stelpro will have the right to refuse any claims if products have been altered without the written authorization of Stelpro and if the nameplate numbers have been removed or modified. This warranty does not cover scratches, dents, corrosion or discoloration caused by excessive heat, chemical cleaning products and abrasive agents. It does not cover any damage that occurred during the shipping.

Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages and some of them do not allow limitations on how long an implied warranty lasts, so these exclusions or limitations may not apply to you. This warranty gives you specific legal rights and you may have other rights which vary from state to state or from province to province.

Models: SWU Series, Industrial or Commercial Washdown Electric Unit Heater, SWU Series Industrial or Commercial Washdown Electric Unit Heater

File Info : application/pdf, 9 Pages, 919.14KB

PDF preview unavailable. Download the PDF instead.

INS SWU 0622 EN WEB

References

Adobe PDF Library 16.0.7 Adobe InDesign 17.3 (Macintosh)

Related Documents

Preview Stelpro ARUH Series Economical Unit Heater User Guide
Comprehensive user guide for the Stelpro ARUH Series Economical Unit Heater, covering important instructions, specifications, installation, maintenance, troubleshooting, and limited warranty information.
Preview Stelpro SEU Explosion-Proof Unit Heater Owner's Manual
Owner's manual for the Stelpro SEU series of explosion-proof unit heaters, covering installation, operation, maintenance, and safety information.
Preview Stelpro HVAC Product Catalogue
Stelpro's comprehensive HVAC product catalogue featuring electric furnaces, ventilation cabinets, custom duct heaters, dual energy duct heaters, make-up air units, and various thermostats. Explore innovative comfort solutions designed and manufactured in Canada.
Preview Stelpro 2020 Product Catalog: Comprehensive Heating Solutions
Explore the 2020 Stelpro product catalog, featuring a wide range of electric heating solutions including baseboard heaters, fan heaters, unit heaters, thermostats, and heating cables. Discover innovative designs, energy efficiency, and quality Canadian-made products for residential, commercial, and industrial applications.
Preview Stelpro Spider SGH/ASGH Ceiling Fan Heater Owner's Manual & Installation Guide
Comprehensive owner's manual for the Stelpro Spider SGH and ASGH series ceiling fan heaters (models SGH4002, ASGH4002). Includes installation instructions, safety warnings, maintenance tips, troubleshooting guide, and warranty information.
Preview STELPRO SONOMA STYLE Fan Heater Owner's Manual and Installation Guide
This comprehensive guide provides detailed instructions for installing, operating, maintaining, and troubleshooting the STELPRO SONOMA STYLE fan heater. It covers safety precautions, model compatibility, thermostat functions, and technical specifications.
Preview STELPRO ST402PFF Programmable Electronic Thermostat Owner's Manual
Owner's manual for the STELPRO ST402PFF programmable electronic thermostat. Covers installation, initial settings, programming, features, and technical specifications for baseboard, convector, and fan heaters.
Preview Stelpro ALUX2 Series Aluminum Mini Architectural Baseboard User's Guide
Comprehensive user's guide for the Stelpro ALUX2 Series Aluminum Mini Architectural Baseboard, covering installation, operation, maintenance, specifications, troubleshooting, and warranty information.