Bosch D7050/D7050TH Multiplex Photoelectric Smoke Detectors

Installation Instructions

Notices

These instructions cover the installation of the D7050/D7050TH Multiplex Photoelectric Smoke Detectors on a D7024 or DS9400M 24 VDC Fire Alarm Control Panel (FACP) with a D7039 or DS9431 Multiplex Expansion Module installed. The D7024 and DS9400M FACPs require ROM version 2.0 or greater.

Install, test, and maintain the D7050/D7050TH according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).

Follow the procedures in these instructions to avoid personal injury and damage to equipment. Failure to follow the procedures can cause the D7050-D7050TH to not operate properly. Bosch is not responsible for improperly installed, tested, or maintained devices.

This device complies with Part 15 of the Federal Communications Commission (FCC) Rules and with RSS-210 of Industry and Science Canada. Operation is subject to the following conditions:

  • This device does not cause harmful interference.
  • This device must accept any interference received, including interference that might cause undesirable operation.

1.0 Description

The D7050/D7050TH are Underwriters Laboratories, Inc. (UL) Listed, open-area multiplex photoelectric smoke detectors. The D7050TH includes a built-in +135°F ± 5°F (+57°C ± 2.7°C) heat detector. Both detectors can be used with the D7024 or DS9400M FACP containing a D7039 or DS9431 Module. Each detector uses a D7050-B6 or MXB2W detector base.

For commercial and industrial installations, space the D7050/D7050TH 30 ft (9.2 m) according to NFPA 72.

Wall-mounted smoke detectors must be at least 4 in. (10.2 cm) and no more than 12 in. (30.5 cm) below the ceiling.

An LED indicator flashes every 3 to 8 seconds confirming the detector has power and the smoke sampling circuitry functions. The LED flashes at least once each second in an alarm, allowing easy confirmation of individual detector alarms. The detector automatically resets after the alarm condition clears.

Refer to Figure 1 for the D7050/D7050TH's dimensions and components.

Figure 1: D7050/D7050TH Side and Top Views. Shows a cylindrical smoke detector. Keyed components are labeled: 1 - Side view, 2 - Top view, 3 - Alarm/Test LED, 4 - Magnetic test locator, 5 - Calibration voltage pins, 6 - Tamper screw hole. Dimensions indicate a minimum distance of 4 inches (10.2 cm) from the ceiling and a height of 1.5 inches (3.8 cm).

2.0 Installation

Do not use shielded cable.

For multiplex bus wiring requirements, refer to the D7024 Operation and Installation Guide (P/N: 31799), the DS9400M Reference Guide (P/N: 44578), the D7039 Installation Guide (P/N: 38685), or the DS9431 Installation Instructions (P/N: 41381).

Do not exceed a maximum line resistance of 50 Ω.

3.0 Wiring the D7050-B6 Base

You can wire the D7050-B6 Base in series or T-tap (refer to Figure 2).

Figure 2: Wiring the D7050-B6 Base. Illustrates two wiring configurations for connecting multiple detectors to the multiplex bus. Connections are made to terminals labeled MUX A+, MUX A-, MUX B+, MUX B-. Keyed components are labeled: 1 - Input-output module for the D7039 or DS9431, 2 - Series connection, 3 - T-tap connection. A warning states "DO NOT PAINT" on the base terminals.

You can replace the dust cover during construction periods, but it must be removed once the alarm system is enabled.

4.0 Setting the Address

Set the D7050's address before connecting to the control panel and applying power. The address number is the same as the input point or zone number.

Set the D7050's address using a flat-blade screwdriver to position the rotary switches (Figure 3) located on the front. Note that the switches click when turned.

Figure 3: Setting the D7050 Address. Shows three rotary switches labeled 1, 2, and 3. Switch 1 is for Hundreds, Switch 2 for Tens, and Switch 3 for Ones. An example shows Switch 1 set to 0, Switch 2 to 9, and Switch 3 to 5, resulting in Address 95 for the D7024 FACP (indicated by 'A'). The valid address range is from 009 to 255.

The valid address range is from 009 to 255. Refer to the D7024 Operation and Installation Guide (P/N: 31499) or the DS9400M Reference Guide (P/N: 44578) for additional address limitations.

The 'A' address range works on the D7039 Multiplex Expansion Module with the D7024 FACP. The 'B' address range works on the DS9431 Multiplex Expansion Module with the DS9400M FACP. Figure 3 shows the 'A' address range set at 095, allowing the D7039 to work with the D7024 FACP.

5.0 Mounting

  1. Unscrew the tamper screw located in the recess on top of the dust cover.
  2. Remove the dust cover from the detector. The dust cover can be replaced during construction periods but must be removed once the alarm system is enabled.
  3. Mount and wire the base according to its instructions.
  4. Mount the detector on the base, turning it clockwise until it clicks into place. When secure, the alignment line aligns with the tamper screw hole (refer to Figure 4).

Figure 4: Mounting D7050/D7050TH on the Base. Shows the detector being attached to the base. Keyed components are labeled: 1 - Base contacts (3), 2 - Alignment arrow, 3 - Insert detector contacts here and rotate clockwise. A note indicates the detector is keyed and should not be forced onto the base.

6.0 Programming

Refer to the control panel's reference guide for multiplex programming instructions.

7.0 Testing

Test the D7050/D7050THs immediately after installation. Also test these detectors according to NFPA 72 or more often as required by local code.

7.1 Operational Testing

Notify all concerned parties before and after completing maintenance on or testing the fire alarm system.

  1. Apply power to the system and check for alarms.
  2. Note any detectors in alarm (indicated by one or more flashes per second) and shut down the system if any alarms are present.
  3. Remove alarmed detectors and recheck for proper wiring.
  4. If problems continue, replace affected detectors or swap them with known good units to determine if the problem is caused by the detector.
  5. When the system is free of alarms, check each detector to ensure the red LED indicator flashes approximately every 3 to 8 seconds to confirm proper operation.
  6. Test each detector to ensure it causes a control panel alarm.
  7. Alarm the detectors by doing one of the following:
    • Activate an internal reed switch by placing a magnet horizontally against the detector's side, centered over the "T" marked on the head.
    • Use a UL Listed aerosol smoke detector tester (e.g., Home Safeguard Industries' 25S) to simulate an alarm. Follow the tester's instructions.
  8. When a detector alarms, the red LED indicator activates and flashes at least once per second. Clear the alarm by initiating a System Reset before proceeding to the next detector.

7.2 Sensitivity

Calibration is important for determining a detector's continued operation. Depending on local regulations, calibration testing might be required more often than once a year. According to NFPA 72, perform a Calibration Test at installation and every other year thereafter. Perform a Functional Test monthly.

Test sensitivity to meet NFPA 72 requirements by conducting a Magnet Test (Section 7.2.3) or by measuring calibration voltage pins using a D1005 Test Cable (Section 7.2.4). Visually inspect the detector's LED to quickly determine calibration (Section 7.2.2 Visual Check). These tests confirm if the detector is within its factory marked calibration range.

7.2.1 Sensitivity Test

The control panel continually monitors the D7050/D7050THs. If sensitivity thresholds are exceeded, the control panel reports the detector and generates a fault condition.

7.2.2 Visual Check

The D7050/D7050TH includes the Chamber Check Automatic Trouble Indication, which automatically shows if its calibration is out of the factory listed range. This check meets NFPA guidelines for sensitivity testing by visually inspecting the detector and checking the LED flash rate.

If calibration is out of range during power-up or longer than 24 hours, the Alarm LED begins double flashing. The LED flashes approximately once every 3 to 8 seconds when the detector operates normally.

Visually check all detectors before disconnecting the multiplex bus. Disconnecting the bus erases the Chamber Check Automatic Trouble Indication. If the detector was disconnected or the control panel lost power within the last 24 hours, perform a Magnet Test or Voltage Measurement Test to confirm sensitivity.

7.2.3 Magnet Test

Ensure the control panel is in the Fire Walk Test Mode before performing a Magnet Test. If not, it sends Fire Reports to the central station. Refer to your control panel reference guide for Fire Walk Test information.

Hold a magnet horizontally against the detector for approximately 10 seconds, centering it over the "T" on the housing. Observe the LED.

  • If the detector is within the factory marked calibration range, it goes into alarm and the Alarm LED flashes at least once per second.
  • If the detector is too sensitive, the LED flashes rapidly six times (once every half second) and the detector goes into alarm.
  • If the detector is not sensitive enough, the LED flashes four times slowly (once every 2 seconds) and the detector goes into alarm.
  • If the detector is not operational, it does not signal an alarm. Return the detector for repair.

7.2.4 Voltage Measurement Test

  1. Plug a D1005 Test Cable (optional) into the calibration voltage pin.
  2. Connect a digital voltmeter to the D1005.
  3. Connect the meter's negative terminal to the D1005's black wire, and the positive terminal to the D1005's red wire. The D1005's white wire is not used. The measured voltage equals half the sensitivity (in %/ft obscuration) of the D7050.
  4. Multiply the voltage by two. The result should be within the factory marked calibration range printed on the detector's label.
  5. If the detector is outside the factory marked calibration range, remove and clean it or replace it as described in Section 7.1 Operational Testing.
  6. Recheck the calibration voltage measurement. If the detector is still outside the factory marked calibration range after cleaning, return it to the factory for recalibration.

7.2.5 Thermistor Test (D7050TH only)

  1. Expose the thermistor to a heat source (e.g., a hair dryer or shielded heat lamp) until the detector alarms and the Alarm LED latches on. Do not touch the thermistor directly.
  2. Clear each alarm for each test before proceeding to the next detector.

8.0 Maintenance

Notify all concerned parties before and after completing maintenance on or testing the fire alarm system.

Clean the detector and base at least once a year using a vacuum or clean dry compressed air. Pay particular attention to the screens. In dusty areas or areas of heavy insect concentration, cleaning might be required more often.

  1. Remove the detector from its base.
  2. Clean the base with a clean cloth and common window cleaner.
  3. Remove the detector cover using a thin, flathead screwdriver to pry the chamber from the cover. Insert the screwdriver into the cover slots as shown in Figure 5 and pry up the detector chamber cover.

Figure 5: Removing the D7050/D7050TH Cover. Illustrates removing the detector's chamber cover. Keyed components are labeled: 1 - Screwdriver inserted into cover slot, 2 - Cover slot (3), 3 - Detector chamber, 4 - Cover.

Gently pull the cover up and away from the chamber as shown in Figure 6.

Figure 6: Removing the D7050/D7050TH Chamber Cover. Shows a hand gently pulling the chamber cover upwards and away from the detector's main body.

With the chamber cover removed, clean the inside of the cover with a vacuum or clean dry compressed air.

Do not clean the D7050/D7050TH components with water or any liquid cleaner.

Replace the chamber cover, ensuring the holes for the LED and thermistor line up over the LED and thermistor. Place the cover parallel to the chamber and gently snap the locking tabs into place.

Replace the detector cover and carefully align the LED and thermistor holes.

Return the detector to its base.

Test the detectors for proper calibration using one of the tests described in Section 7.0 Testing.

Do not paint the D7050/D7050THs. Paint or other foreign matter covering the screens can stop or delay smoke from entering the detector.

9.0 Specifications

Table 1: Specifications
Parameter Value
Standby Current 0.5 mA at 12 VDC
Alarm Current 0.56 mA at 12 VDC
Minimum Operating Voltage 8 VDC peak
Power-up Time 22 sec maximum
Installation Temperature +32°F to 100°F (0°C to +38°C)
Relative Humidity 0% to 93% non-condensing
Required Accessories D7050-B6 Detector Base
Models: D7050, D7050TH, D7050 Multiplex Photoelectric Smoke Detectors, Multiplex Photoelectric Smoke Detectors, Photoelectric Smoke Detectors, Smoke Detectors, Detectors

File Info : application/pdf, 8 Pages, 362.02KB

PDF preview unavailable. Download the PDF instead.

d7050-bosch-manual-instalacion-sh-ingenieria

References

GPL Ghostscript 9.55.0

Related Documents

Preview Bosch Smoke Alarm II Quick Instructions: Installation, Safety & Setup Guide
Comprehensive quick instructions for the Bosch Smoke Alarm II (BSD-2). Learn about installation, safety precautions, maintenance, technical data, and troubleshooting. Ensure your home's safety with Bosch.
Preview Bosch FCP-320/FCH-320 Conventional Automatic Fire Detectors User Manual
Comprehensive user manual for Bosch FCP-320 and FCH-320 Conventional Automatic Fire Detectors. Learn about their multisensor technology, installation, maintenance, and specifications for reliable fire detection.
Preview Bosch Smart Home Smoke Detector Instruction Manual - Setup, Installation & Safety Guide
Comprehensive instruction manual for the Bosch Smart Home Smoke Detector. Learn about product features, installation steps, maintenance, safety guidelines, and technical specifications for enhanced home safety.
Preview Bosch FAP-520 Automatic Fire Detectors Operation Manual
This document provides comprehensive operational instructions for the Bosch FAP-520 series automatic fire detectors, including installation, programming, maintenance, and technical specifications. It covers both optical (FAP-O 520) and multisensor (FAP-OC 520) models designed for LSN improved systems.
Preview Bosch Fire Detectors LSN Improved Version Installation and Operation Manual
This document provides comprehensive instructions for the installation, programming, maintenance, and technical specifications of Bosch automatic fire detectors, LSN improved version, including models FAP-O 520, FAP-O 520-P, FAP-OC 520, and FAP-OC 520-P.
Preview Bosch Smart Home Smoke Alarm: Instruction Manual and Setup Guide
Comprehensive guide to installing, operating, and maintaining your Bosch Smart Home Smoke Alarm. Learn about its features, safety instructions, and technical specifications.
Preview Bosch AVENAR Detector 4000 User Manual
This manual provides comprehensive information on the Bosch AVENAR Detector 4000, covering its product description, system overview, programming, connection, accessories, and maintenance. It details various detector types, their functionalities, installation procedures, and technical specifications.
Preview Bosch Automatic Fire Detectors LSN Improved Series: Installation and Operation Manual
This manual provides detailed information on the installation, configuration, operation, and maintenance of Bosch Automatic Fire Detectors from the LSN Improved series, including models FAP-O 520, FAP-O 520-P, FAP-OC 520, and FAP-OC 520-P. It covers product features, technical specifications, and troubleshooting.