Finder 58 Series ATEX Relay Interface Module

SWITCH TO THE FUTURE

GENERAL SAFETY INFORMATION

These safety instructions refer to the installation, utilization and maintenance of 58 series relays to be used in potentially explosive areas due to the presence of combustible GAS. The information of these instructions are only for qualified personnel. The relays and the sockets comply with the Essential Health and Safety Requirements for potentially explosive atmospheres provided by European Standards: EN 60079-0 (2012+A11:2013), EN 60079-15(2010), EN 60079-7(2015)

Interface CodeSocket CodeRelay CodeModulesRetaining clip
58.32.V.XXX.W0JK94.02.755.32.V.XXX.W0Y399.02.Z.XXX.QT094.71
58.32.V.XXX.W0JK94.04.755.32.V.XXX.W0Y399.02.Z.XXX.QT094.71
58.33.V.XXX.W0JK94.03.755.33.V.XXX.W0Y399.02.Z.XXX.QT094.71
58.34.V.XXX.W0JK94.04.755.34.V.XXX.W0Y399.02.Z.XXX.QT094.71
58.32.V.XXX.W00K94.02.755.32.V.XXX.W0Y3094.71
58.32.V.XXX.W00K94.04.755.32.V.XXX.W0Y3094.71
58.33.V.XXX.W00K94.03.755.33.V.XXX.W0Y3094.71
58.34.V.XXX.W00K94.04.755.34.V.XXX.W0Y3094.71

J = 4, 5, 6 - K = 8, 9 - V = 8, 9 - Q = 5, 9 - Y = 0, 2 - Z = 0, 9 - T = 8, 9 Marker tags 060.72; xxx**= supply voltage

TRANSPORT, STORAGE

[!] On receipt verify that the relay has not been damaged during transport. If damaged, do not install and immediately advise the transport service.

INSTALLATION

[!] Installation must comply with the rules of the standard EN60079-14 or with the current national standards. Before the installation in an explosive atmosphere, the installer must ensure that the relay is suitable for the classified area in consideration of the different inflammable substances present in the installation area (please verify the marking on the relay cover before installation). The relay must be installed only by qualified people with knowledge of electrical apparatus for explosive gas atmospheres and electrical installations in hazardous areas and has to be done with the relay and equipment at standstill, electrically dead and locked against restart.

MARKING

[EX] II 3G Ex ec nC IIC Gc -40°C ≤Ta≤+70°C

Specific marking of explosion protection:

  • II - Component for surface plant (different from mines)
  • 3 - Category 3: normal level of protection
  • G - explosive atmosphere due to presence of combustible gas vapour or mist
  • Ex ec - Increased safety
  • Ex nC - Sealed device (type of protection for category 3G)
  • IIC - Gas group
  • Gc - Equipment Protection Level
  • -40°C ≤ Ta ≤ +70°C - Ambient temperature

Certificate details: EPTI 17 ATEX 0195 U (EPTI: laboratory which issued the certificate, 17: year of issue, 0195: number, U: Ex component)

TECHNICAL CHARACTERISTICS

CONTACT CHARACTERISTICS

  • Contact configurations: 2 CO (58.32) - 3 CO (58.33) - 4 CO (58.34)
  • Rated Current / maximum peak current: 10/20 A (58.32) - 9/20 A (58.33) - 6/15 A (58.34)
  • Rated voltage / max switching voltage: 250/400 V AC (58.32) - 250/400 V AC (58.33) - 250/250 V AC (58.34)
  • Rated load-Category AC1: 2500 VA (58.32) - 2250 VA (58.33) - 1500 VA (58.34)
  • Rated load-Category AC15 (230 V AC): 500 VA (58.32) - 500 VA (58.33) - 350 VA (58.34)
  • Capacity for single phase motor (230 V AC): 0.37 kW (58.32) - 0.37 kW (58.33) - 0.125 kW (58.34)
  • Breaking capacity-Category DC1(30/110/220 V): 10/0.25/0.12 A (58.32) 9/0.25/0.12 A (58.33) 6/0.25/0.12 A (58.34)

CHARACTERISTICS OF COIL

  • Rated Voltage* (UN): 12...230 V AC, 12...230 V DC
  • Rated power AC/DC: 1.5/1 VA (50 Hz)/W
  • Operating range: (0.8...1.1)UN AC, (0.8...1.1)UN DC
  • Ambient temperature: (-40...+70)°C

* Special rated voltages on request

The supply voltage depends on the characteristics of the timer

SPECIAL CONDITION FOR SAFE USE

[!] Maximum temperature recorded on the surface of the component (obtained suppling the coil at the nominal voltage, Tamb 70°C) not exceed 111°C with the value of rated current as described at the point 5. The wire connected to the terminals of the socket, must be at least 2.5 mm². On multi-installation, the value of the nominal current is reduced depending on the model of the interface.

A pack connection of 5 interface, power supply = rated voltage, T.amb = 70°C:

INTERFACEMAX PEAK CURRENT [A] (for pack)
58.32....JK7
58.33....JK6
58.34....JK5

The component must be inserted in an enclosure that meets the general requirements for enclosures listed in paragraph 4.10 of EN 60079-7. Connections must be carried out according to the requirements in paragraph 4.2.2 of EN 60079-7.

MAINTENANCE AND REPAIR

[!] The user must not open, modify or repair this relay in any way.

Models: 58.32.V.XXX.W0JK, 58.33.V.XXX.W0JK, 58.34.V.XXX.W0JK, 58 Series ATEX Relay Interface Module, 58 Series, ATEX Relay Interface Module, Relay Interface Module, Interface Module, Module

File Info : application/pdf, 1 Pages, 270.64KB

PDF preview unavailable. Download the PDF instead.

IB58AtexEN

References

Adobe PDF Library 17.0 Adobe InDesign 18.5 (Macintosh)

Related Documents

Preview Finder OPTA 8A.58/8A.88 Programmable Logic Relay - Technical Specifications
Technical overview of the Finder OPTA 8A.58 and 8A.88 series programmable logic relays, detailing specifications, connectivity options with Arduino, and compliance information.
Preview Finder 22.32 Modular Contactor 25 A Technical Data Sheet
Technical specifications and operational details for the Finder 22.32 modular contactor, a 25A device compliant with EN 61095, featuring a universal AC/DC coil and compatibility with auxiliary contact modules. Includes connection diagrams, outline drawings, and UL listing information.
Preview Finder OPTA 8A.58/8A.88 Programmable Logic Relay Technical Specifications
Comprehensive technical details, wiring diagrams, and setup instructions for the Finder OPTA 8A.58 and 8A.88 series programmable logic controllers, featuring Arduino integration.
Preview Finder 22.32 Modular Contactors 25A Technical Data Sheet
Technical specifications and connection diagram for the Finder 22.32 modular contactor, a 25A device with AC/DC coil and optional auxiliary modules.
Preview Finder 13.61 Multifunction Step/Monostable Relay with Set & Reset Commands
Technical specifications and operating instructions for the Finder 13.61 multifunction step/monostable relay. This relay features set and reset commands, suitable for 35mm rail mounting and compatible with 3 or 4 wire systems. Includes connection diagrams, front view details, function descriptions (step relay, timing step relay, monostable relay, light-on), and working condition guidelines.
Preview Finder 7S.23 Series Force Guided Relay Modules for Safety Applications
Finder's 7S.23 Series compact force-guided relay modules are designed for safety applications up to SIL 2 EN 62061 and PL d IEC 13849-1, featuring 10A contacts and DC coils.
Preview Finder 13.22.8.230.8000 Multifunction Relay - Technical Guide
Technical specifications, wiring diagrams, and functional descriptions for the Finder 13.22.8.230.8000 YESLY multifunction relay, featuring Bluetooth connectivity and the Finder Toolbox app.
Preview Finder Electrical Installer's Guide: Residential and Public Buildings Wiring Diagrams
A comprehensive guide for electrical installers from Finder, detailing wiring diagrams for residential and public buildings. This manual covers various relay types, their applications, and comparisons with traditional systems, offering insights into smart home integration and energy efficiency.