Lochinvar EcoCharger Hybrid Flue Guide

EcoCharger Hybrid Flue Guide

Lochinvar HIGH EFFICIENCY BOILERS & WATER HEATERS

General Information

Lochinvar water heaters are certified for use on the following flue categories only:

Installation Type Category Description
B23 Open flue An appliance intended to be connected to a flue that evacuates the products of combustion to the outside of the room containing the appliance. The combustion air is drawn directly from the room.
C13 Closed Flue An appliance connected to either a concentric or twin-pipe flue system with a Horizontal flue terminal. Both the air inlet and flue exhaust must be in the same pressure zone.
C33 Closed Flue An appliance connected to either a concentric or twin-pipe flue system with a Vertical flue terminal. Both the air inlet and flue exhaust must be in the same pressure zone.
C43 Closed Flue An appliance connected to a common air inlet and flue exhaust system, which is designed for more than one appliance. This common system has a single air inlet and flue exhaust and is part of the building not the appliance.
C53 Closed Flue An appliance connected to a twin-pipe flue system with a Horizontal or Vertical flue terminal. Both air inlet and flue exhaust may be in different pressure zones.
C63 Closed Flue An appliance intended to be connected to a separately approved and marketed system for the supply of combustion air and discharge of combustion products (i.e. other than that supplied by the water heater manufacturer).

EcoCharger Hybrid water heaters use either: An Aluminium Concentric Or Twin pipe system flue system.

Concentric Systems

Horizontal Flue Assembly (Models HWH32-220 to HWHC63-370)

Components Included

Item No. Description Included
LV302505CONCENTRIC HORIZONTAL TERMINAL Ø100/150 ALU1
LV302499CONCENTRIC EXTENSION Ø100/150 (500mm) ALU CUT TO LENGTH1
LV302502CONCENTRIC BEND 90° Ø100/150 ALU1

Diagram illustrating the configuration of a concentric horizontal flue terminal with dimensions labeled V, W, X, and Y.

ModelV (mm)W (mm)X (mm)Y (mm)
HWH32-22055072515351010
HWH33-370 to HWH63-370
HWHC44-370,HWHC63-370
55079020751030
HWH87-480 to HWH129-48064094022301170

Horizontal Flue Assembly (Models HWH87-480 to HWH129-480)

Components Included

Item No.DescriptionIncluded
LV302313CONCENTRIC HORIZONTAL TERMINAL Ø130/200 ALU1
LV302301CONCENTRIC EXTENSION Ø130/200 (500mm) ALU CUT TO LENGTH1
LV311456CONCENTRIC BEND 90° Ø130/200 ALU1

Diagram illustrating the configuration of a concentric horizontal flue terminal with dimensions labeled V, W, X, and Y.

ModelV (mm)W (mm)X (mm)Y (mm)
HWH32-22013056802965625
HWH33-370 to HWH63-370
HWHC44-370,HWHC63-370
150010353325465
HWH87-480 to HWH129-48064094022301170

Vertical Flue Assembly (Models HWH32-220 to HWHC63-370)

Components Included

Item No.DescriptionIncluded
LV311458CONCENTRIC VERTICAL TERMINAL Ø100/150 ALU1
LV311450CONCENTRIC EXTENSION Ø100/150mm (1000mm) ALU CUT TO LENGTH1
LV302509ROOF FLASHING (170mm) ALU1

Diagram illustrating the configuration of a concentric vertical flue terminal with dimensions labeled V, W, X, and Y.

ModelV (mm)W (mm)X (mm)Y (mm)
HWH32-22013056802965625
HWH33-370 to HWH63-370
HWHC44-370,HWHC63-370
150010353325465
HWH87-480 to HWH129-48064094022301170

Vertical Flue Assembly (Models HWH87-480 to HWH129-480)

Components Included

Item No.DescriptionIncluded
LV306390CONCENTRIC VERTICAL TERMINAL Ø130/200 ALU1
LV302301CONCENTRIC EXTENSION Ø130/200 (500mm) ALU CUT TO LENGTH1
LV302328FLAT ROOF FLASHING (210mm) ALU1

Diagram illustrating the configuration of a concentric vertical flue terminal with dimensions labeled V, W, X, and Y.

ModelV (mm)W (mm)X (mm)Y (mm)
HWH32-22013056802965625
HWH33-370 to HWH63-370
HWHC44-370,HWHC63-370
150010353325465
HWH87-480 to HWH129-48064094022301170

Maximum Flue Lengths

Maximum equivalent flue length = 40 Metres

Maximum number of bends allowed = 7

Note: Even if using less than the maximum number of bends, the maximum pipe length may not be exceeded. Even if using less than the maximum pipe length, the maximum number of bends may not be exceeded.

Concentric System Ancillary Items

Ancillary Items for HWH32-220 to HWHC63-370

Item No.Description
LV303854CONCENTRIC TEST POINT Ø100/150 ALU
LV302499CONCENTRIC EXTENSION Ø100/150 (500mm) ALU CUT TO LENGTH
LV311450CONCENTRIC EXTENSION Ø100/150mm (1000mm) ALU CUT TO LENGTH
LV311451CONCENTRIC EXTENSION Ø100/150mm (1500mm) ALU CUT TO LENGTH
LV302502CONCENTRIC BEND 90° Ø100/150 ALU (A=223mm B=208mm)
LV311454CONCENTRIC BEND 45° Ø100/150mm ALU (A=128mm B=128mm)
M87196WALL CLAMP Ø150

Diagram illustrating flue bends with dimensions labeled A and B.

Ancillary Items for HWH87-480 to HWH129-480

Item No.Description
LV303855CONCENTRIC TEST POINT Ø130/200 ALU
LV302301CONCENTRIC EXTENSION Ø130/200 (500mm) ALU CUT TO LENGTH
LV311452CONCENTRIC EXTENSION Ø130/200mm (1000mm) ALU CUT TO LENGTH
LV302303CONCENTRIC EXTENSION Ø130/200 (1500mm) ALU FIXED
LV311456CONCENTRIC BEND 90° Ø130/200 ALU (A=223mm B=208mm)
LV311455CONCENTRIC BEND 45° Ø130/200mm ALU (A=128mm B=223mm)
M87198WALL CLAMP Ø200

Diagram illustrating flue bends with dimensions labeled A and B.

Twin-Pipe Flue Systems

Horizontal Flue Assembly (ECPH001)

Models: HWH32-220, HWH33-370, HWH52-370, HWH63-370, HWHC44-370, HWHC63-370

Item No.DescriptionIncluded
LV302505CONCENTRIC HORIZONTAL TERMINAL Ø100/150 ALU1
LV307142TWIN PIPE TO CONCENTRIC ADAPTOR Ø100/100mm TO Ø100/150mm ALU1
LV307161EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH2
LV307164BEND 90° Ø100mm ALU2
LV304204CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU1

Diagram illustrating a horizontal twin-pipe flue assembly with concentric terminal.

Horizontal Flue Assembly (ECPH002)

Models: HWH87-480, HWH106-480, HWH129-480

Item No.DescriptionIncluded
LV306803CONCENTRIC HORIZONTAL TERMINAL Ø130/200mm ALU1
LV306801TWINPIPE TO CONCENTRIC ADAPTOR Ø130/130mm TO Ø130/200mm ALU1
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH2
LV306805BEND 90° Ø130mm ALU2
LV309605CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU1

Diagram illustrating a horizontal twin-pipe flue assembly with concentric terminal.

Horizontal Flue Assembly (ECPH003)

Models: HWH32-220, HWH33-370, HWH52-370, HWH63-370, HWHC44-370, HWHC63-370

Item No.DescriptionIncluded
LV302505CONCENTRIC HORIZONTAL TERMINAL Ø100/150 ALU1
LV307161EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH2
LV305039HORIZONTAL TERMINAL Ø100mm ALU1
LV307164BEND 90° Ø100mm ALU2
LV304204CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU1

Diagram illustrating a horizontal twin-pipe flue assembly.

Horizontal Flue Assembly (ECPH004)

Models: HWH87-480, HWH106-480, HWH129-480

Item No.DescriptionIncluded
LV302313CONCENTRIC HORIZONTAL TERMINAL Ø130/200 ALU1
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH2
LV307178HORIZONTAL TERMINAL Ø130mm ALU1
LV306805BEND 90° Ø130mm ALU2
LV309605CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU1

Diagram illustrating a horizontal twin-pipe flue assembly.

Maximum Flue Length

HWH32-220 to HWH63-370
HWHC44-370,HWHC63-370
HWH87-480 to HWH129-480
Maximum flue length5565
Equivalent length 90° bend4.62.4
Equivalent length 45° bend1.21.4

Twin-Pipe Vertical Flue Systems

Vertical Flue Assembly (ECPV001)

Models: HWH32-220, HWH33-370, HWH52-370, HWH63-370, HWHC44-370, HWHC63-370

Item No.DescriptionIncluded
LV311458CONCENTRIC VERTICAL TERMINAL Ø100/150 ALU1
LV307142TWIN PIPE TO CONCENTRIC ADAPTOR Ø100/100mm TO Ø100/150mm ALU1
LV307160EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH2
LV304204CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU1

Diagram illustrating a vertical twin-pipe flue assembly with concentric terminal.

Vertical Flue Assembly (ECPV002)

Models: HWH87-480, HWH106-480, HWH129-480

Item No.DescriptionIncluded
LV306800CONCENTRIC VERTICAL TERMINAL Ø130/200 ALU1
LV306801TWIN PIPE TO CONCENTRIC ADAPTOR Ø130/130mm TO Ø130/200mm ALU1
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH2
LV309605CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU1

Diagram illustrating a vertical twin-pipe flue assembly with concentric terminal.

Vertical Flue Assembly (ECPV003)

Models: HWH32-220, HWH33-370, HWH52-370, HWH63-370, HWHC44-370, HWHC63-370

Item No.DescriptionIncluded
LV305040VERTICAL TERMINAL Ø100mm ALU1
LV305039HORIZONTAL TERMINAL Ø100mm ALU1
LV307160EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH2
LV307164BEND 90° Ø100mm ALU (A=115mm,B=115mm)1
LV310197BEND 45° Ø100mm ALU (A=100mm,B=100mm)1
LV304204CONCENTRIC TO TWIN PIPE ADAPTOR Ø100/150mm TO Ø100/100mm ALU1

Diagram illustrating a vertical twin-pipe flue assembly.

Vertical Flue Assembly (ECPV004)

Models: HWH87-480, HWH106-480, HWH129-480

Item No.DescriptionIncluded
LV307175VERTICAL TERMINAL Ø130mm ALU1
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH2
LV307178HORIZONTAL TERMINAL Ø130mm ALU1
LV306805BEND 90° Ø130mm ALU1
LV309605CONCENTRIC TO TWIN PIPE ADAPTOR Ø130/200mm TO Ø130/130mm ALU1

Diagram illustrating a vertical twin-pipe flue assembly.

Maximum Flue Length

HWH32-220 to HWH63-370
HWHC44-370,HWHC63-370
HWH87-480 to HWH129-480
Maximum flue length5565
Equivalent length 90° bend4.62.4
Equivalent length 45° bend1.21.4

Twin-Pipe System Ancillary Items

Ancillary Items for HWH32-220 to HWHC63-370

Item No.Description
LV307160EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH
LV307161EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH
LV307164BEND 90° Ø100mm ALU (A=115mm,B=115mm)
LV310197BEND 45° Ø100mm ALU (A=100mm,B=100mm)
LV302520ROOF FLASHING (140mm) ALU
M87193WALL CLAMP Ø100mm

Diagram illustrating flue bends with dimensions labeled A and B.

Ancillary Items for HWH87-480 to HWH129-480

Item No.Description
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH
LV306802EXTENSION Ø130mm(1000mm) ALU CUT TO LENGTH
LV306805BEND 90° Ø130mm ALU (A=160mm,B=160mm)
LV308026BEND 45° Ø130mm ALU (A=100mm,B=100mm)
LV302520ROOF FLASHING (140mm) ALU
M87195WALL CLAMP Ø130mm

Diagram illustrating flue bends with dimensions labeled A and B.

Conventional (Exhaust Only) Flue Systems

Flue Assembly (ECCV001)

Models: HWH32-220, HWH33-370, HWH52-370, HWH63-370, HWHC44-370, HWHC63-370

Item No.DescriptionIncluded
LV305040VERTICAL TERMINAL Ø100mm ALU1
LV307160EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH2
LV304872APPLIANCE AIR INTAKE GUARD Ø1001

Diagram illustrating a conventional exhaust flue assembly.

Flue Assembly (ECCV001)

Models: HWH87-480, HWH106-480, HWH129-480

Item No.DescriptionIncluded
LV307175VERTICAL TERMINAL Ø130mm ALU1
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH2
LV307176APPLIANCE AIR INTAKE GUARD Ø130mm ALU1

Diagram illustrating a conventional exhaust flue assembly.

Maximum Flue Length

HWH32-220 to HWH63-370
HWHC44-370,HWHC63-370
HWH87-480 to HWH129-480
Maximum flue length5565
Equivalent length 90° bend4.62.4
Equivalent length 45° bend1.21.4

Ancillary Items for HWH32-220 to HWHC63-370

Item No.Description
LV307160EXTENSION Ø100mm(500mm) ALU CUT TO LENGTH
LV307161EXTENSION Ø100mm(1000mm) ALU CUT TO LENGTH
LV307164BEND 90° Ø100mm ALU (A=115mm,B=115mm)
LV310197BEND 45° Ø100mm ALU (A=100mm,B=100mm)
LV302520ROOF FLASHING (140mm) ALU
M87193WALL CLAMP Ø100mm

Diagram illustrating flue bends with dimensions labeled A and B.

Ancillary Items for HWH87-480 to HWH129-480

Item No.Description
LV306804EXTENSION Ø130mm(500mm) ALU CUT TO LENGTH
LV306802EXTENSION Ø130mm(1000mm) ALU CUT TO LENGTH
LV306805BEND 90° Ø130mm ALU (A=160mm,B=160mm)
LV308026BEND 45° Ø130mm ALU (A=100mm,B=100mm)
LV302520ROOF FLASHING (140mm) ALU
M87195WALL CLAMP Ø130mm

Diagram illustrating flue bends with dimensions labeled A and B.

Common Flue Systems

Any installations using flue type C63 must be designed and installed in compliance with any local Building or planning regulations. As these systems use a flue system not supplied by Lochinvar, Lochinvar cannot comment, advise, or provide support on the design of this type of flue system. To design such a flue system, the installer/contractor must consult a specialist flue supplier who will be responsible for the design and installation of the separate flue system. When designing the type C63 flue system, the instructions in the Installation Manual, provided with the water heater, must be taken into account. Lochinvar will provide pressure loss figures for the specific units, but other than that, Lochinvar cannot provide support on Common Flue requests because flue certification is limited to the certified categories in the table on page 2. Lochinvar cannot accept any responsibility for Flue system design.

Pressure Loss Figures

Model Maximum pressure Inlet only Outlet only Inlet + Outlet Flue gas rate
Pinlet (Pa) Poutlet (Pa) Pinlet (Pa) Poutlet (Pa) Pinlet (Pa) Poutlet (Pa) G20 (kg/h) G31 (kg/h)
HWH32-220-550052-262651.753.6
HWH33-370-660062-323253.554.4
HWH52-370-14200133-696984.685.6
HWH63-370-18400173-9090103.7103.8
HWH87-480-900088-4747141.9149.1
HWH106-480-12900126-6767172.9181.6
HWH129-480-18400180-9696213.3221.7

Order Form and Notes

Notes-Items to order

Item No.No requiredNotes

To order additional flue items email this page to info@lochinvar.ltd.uk.

Important Information

⚠ IMPORTANT INFORMATION

These instructions must be read and understood before installing, commissioning, operating or maintaining the equipment.

Lochinvar Ltd reserves the right to change specifications without prior notice.

Contact Information:

Lochinvar

HIGH EFFICIENCY BOILERS & WATER HEATERS

7 Lombard Way, The MXL Centre, Banbury, Oxon, OX16 4TJ

Tel: +44(0) 1295 269 981, Fax: +44(0) 1295 271 640, Email: info@lochinvar.ltd.uk

Website: www.lochinvar.ltd.uk

Certifications include: ACS, ISO 14001, ISO 9001, Iphe, CIBSE, ICOM, CE.

Models: Hybrid HWHC Water Heaters, HWHC Water Heaters, Water Heaters, Heaters

File Info : application/pdf, 12 Pages, 729.02KB

PDF preview unavailable. Download the PDF instead.

Flue-assemblies-and-ancillaries EcoCharger-hybrid

References

GPL Ghostscript 9.55.0

Related Documents

Preview Lochinvar EFB Boiler Range Flue Guide
A comprehensive guide to Lochinvar EFB boiler flue systems, detailing concentric, twin-pipe, conventional, and common flue types. Includes installation requirements, terminal locations, risk assessment criteria, and sizing calculations for EFB85, EFB105, EFB125, and EFB155 models.
Preview Lochinvar CPM Boiler Range Flue Guide
Comprehensive guide for Lochinvar CPM boiler flue system installation, covering concentric, twin-pipe, and conventional types. Includes terminal locations, risk assessments, and sizing calculations based on BS5440-1 and IGEM/UP/10 standards.
Preview Lochinvar EcoForce Water Heater Flue Guide: Installation and Sizing
Comprehensive guide for installing and sizing flue systems for Lochinvar EcoForce water heaters (EF80, EF100, EF120, EF150, EF180). Covers concentric, twin-pipe, and conventional flue types, installation standards, and technical specifications.
Preview Lochinvar HeatPak LTHW Module: Technical Specifications and Benefits
Discover the Lochinvar HeatPak LTHW module for efficient integration with EcoCharger water heaters. Learn about its benefits, technical specifications, and installation details for combined heating and DHW systems.
Preview Lochinvar Standard Terms and Conditions
Official terms and conditions governing the purchase of products from Lochinvar Limited, detailing contract basis, delivery, warranty, payment, termination, liability, and governing law.
Preview Lochinvar Imperium System Controller Installer Quick Guide
A comprehensive quick guide for installers on setting up and connecting the Lochinvar Imperium System Controller. This guide covers system configurations, screen navigation, safety warnings, and error codes for efficient operation of heat pump systems.
Preview Lochinvar LSTR Direct Storage Vessel Installation, Commissioning, User & Maintenance Instructions
Comprehensive guide for the Lochinvar LSTR Direct Storage Vessel, covering installation, commissioning, user operation, and maintenance procedures. Includes technical specifications, dimensions, warranty information, and safety guidelines.
Preview Lochinvar Smart Electric Heat Pump Water Heater Submittal Sheet & Specifications
Technical specifications, features, and dimensions for Lochinvar Smart Electric Heat Pump Hybrid Water Heaters, including model numbers HPSA050KD DAK, HPSA065KD DAK, and HPSA080KD DAK. This document provides essential data for product selection and installation.