ComfortAire Century CXP1524SA-1 Air Handler Heat Pump System
Submittal Data
General Information
Location: | Approval: | ||
Engineer: | Date: | ||
Submitted to: | Construction: | ||
Submitted by: | Unit #: | ||
Reference: | Drawing #: |
Indoor Unit Specifications
Dimensions (W×D×H)17.52 x 20.98 x 17.99 inches (445 x 533 x 457 mm) Package Dimensions (W×D×H)20.47 x 26.18 x 20.87 inches (520 x 665 x 530 mm) Net/Gross Weight42/50 lbs (19/22.5 kg) |
Certifications:
|
Outdoor Unit Specifications
Compressor Type: ROTARY |
Compressor Model: KTM240D46UKT2 |
Refrigerant: R454B |
Refrigerant Oil Charge (mL): 620 |
Refrigerant Oil: VG74 |
Outdoor Air Flow (Max) (CFM): 1,766 |
Outdoor Noise Level (dBA): 56 |
Dimensions (W×D×H): 35.04 x 13.46 x 26.50 inches (890 x 342 x 673 mm) |
Package Dimensions (W×D×H): 39.17 x 15.67 x 29.13 inches (995 x 398 x 740 mm) |
Net/Gross Weight: 89.29/97.00 lbs (40.5/44 kg) |
Efficiency
Rating | SEER2 | EER2 | HSPF2-4 | COP |
---|---|---|---|---|
Cooling | 15.5 | 10.6 | ||
Heating | / | / |
Performance of Cooling
Cooling (Btu/hr): 23,000 | |
Rated Capacity: 23,000 | |
Min/Max Capacity: 7,600~28,700 | |
Moisture Removal (L/h): 2.7 | |
Standard Operating Range (°F/°C): -13~122 (-25~50) | |
Rated Cooling Conditions: | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
Heating (Btu/hr): / |
1. @ 47°F Rated: / |
2. @ 47°F Min/Max Capacity: / |
3. @ 17°F Rated: / |
4. @ 5°F Rated: Capacity / COP: /(/) |
5. @ 5°F Max: Capacity: / |
Standard Operating Range (°F/°C): /(/) |
1. Rated Heating Conditions: Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions: Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency: Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply: 24V, 60Hz, 1Ph |
Indoor MCA 115V/(208/230V): / |
Indoor MOP: / |
Outdoor Power Supply: 208/230, 60Hz, 1Ph |
Outdoor MCA: 19 |
Outdoor MOP: 20 |
Communication Wiring: AWG 20-2 |
Compressor RLA: / |
Outdoor Fan Motor RLA: 1.8 |
Outdoor Fan Motor W: / |
Indoor Fan Motor RLA: / |
Indoor Fan Motor W: / |
System Power Input @ Cooling (W): 2,170(600~3,450) |
System Power Input @ Heating (W): /( / ) |
MCA: Min. circuit amps (A): MOCP: Max. over current protection (A) |
RLA: Rated load amps (A): W: Fan motor rated output (W) |
Piping
Throttle type (Indoor): EXV |
Throttle type (Outdoor): / |
Liquid Size: 9.52mm (3/8in) |
Gas Size: 19mm (3/4in) |
Max. Piping Length (ft/m): 164 (50) |
Max. Height Difference (ft/m): 82 (25) |
Max. Pre-charged Length (ft/m): 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg): 52.21 (1.48) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)): 0.7 (65) |
Connection Method: Flared |
Indoor Unit Dimensions Table
Model/Dimensions | MXP18/24B1A | MXP18/24A1A | MXP24/36A1A | MXP24/36B1A | MXP24/36C1A | MXP48/60C1A | MXP48/60D1A | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | |
A Model Height | 18 | 457 | 18 | 457 | 23-5/16 | 592 | 23-9/16 | 599 | 24 | 611 | 24 | 611 | 28 | 711 |
B Model Width | 17-1/2 | 445 | 14-1/2 | 368 | 14-1/2 | 368 | 17-1/2 | 445 | 21 | 534 | 21 | 534 | 24-1/2 | 622 |
C Supply Air Opening Width | 16-3/16 | 411 | 13-1/4 | 336 | 13-1/4 | 336 | 16-3/16 | 411 | 19-3/4 | 502 | 19-3/4 | 502 | 23-1/4 | 591 |
D Return Air Opening Width | 14-5/16 | 380 | 11-15/16 | 303 | 11-15/16 | 303 | 14-15/16 | 380 | 19-1/2 | 498 | 19-1/2 | 498 | 23-1/8 | 587 |
E Condensate Drains Height | 1-7/16 | 38 | 1-7/16 | 38 | 1-7/16 | 38 | 1-7/16 | 38 | 2-3/16 | 55 | 2-3/16 | 55 | 2-3/16 | 55 |
F Liquid Line Height | 11-3/8 | 290 | 11-3/8 | 290 | 17-5/16 | 455 | 16-3/8 | 417 | 17-1/2 | 445 | 17-1/2 | 445 | 21-7/16 | 545 |
Outdoor Unit Dimensions
Dimensions (W×H×D): 35-1/4in (895mm) W x 26-1/8in (663mm) H x 13-1/2in (342mm) D
Overall Dimensions (W×H×D): 35in (890mm) W x 26-1/2in (673mm) H x 15in (380mm) D
Overall Dimensions (W×H×D): 37-5/8in (955mm) W x 13-3/4in (348mm) H x 2-3/8in (61mm) D
Installation Instructions for Outdoor Unit
Ensure adequate clearance around the outdoor unit for proper ventilation and maintenance.
- Front and Sides: 20 inches (500mm) or more clearance.
- Left, Right, and Rear: 20 inches (500mm) or more clearance when any 2 sides are clear.
- Sides: 4 inches (100mm) or more clearance.
- Rear: 14 inches (350mm) or more clearance.
☑ Meets all spatial requirements shown in Installation Clearance Requirements above.
Features
- Multi-position installation: horizontal (left or right), vertical (up or down).
- Aluminum Coil.
- R454B refrigerant sensor.
- Easy Maintenance.
- Multiple control options available:
- Two-way communication wired controller with built-in WiFi: 120N(X6W).
- Third-Party 24V Thermostat.