Product Data Sheet
Regulated Power Supply, 380...500V AC, 24V, 20A, 3 phases, Universal
Model: ABLU3A24200
Product availability: Stock - Normally stocked in distribution facility
Main
Attribute | Value |
---|---|
Range of Product | Modicon Power Supply |
Product or Component Type | Power supply |
Power supply type | Regulated switch mode |
Variant option | Universal |
Enclosure Material | Metal |
Nominal input voltage | 380...500 V AC three phase |
Kw Rating | 480 W |
Output voltage | 24 V DC |
Power supply output current | 20 A |
Permissible temporary current boost | 1.5 x In for 5 seconds |
Complementary
Attribute | Value |
---|---|
Efficiency at full load | 93% 380...575 V AC 3 phase |
Nominal network frequency | 50...60 Hz |
Network system compatibility | TN, TT, IT |
Maximum leakage current | 2 mA 500 V AC |
Input protection type | Integrated fuse (not interchangeable) 3.15 A; External protection (recommended) |
Inrush current | 35 A 380 V; 35 A 500 V |
Power factor | 0.90 at 380 V AC; 0.88 at 500 V AC |
Efficiency | 93% 380 V AC; 93% 500 V AC |
Output voltage adjustment | 24...28 V |
Power dissipation in W | 33 W |
Current consumption | < 0.85 A 380 V AC; < 0.73 A 500 V AC |
Turn-on time | < 1 s |
Holding time | > 20 ms 380 V AC; > 20 ms 500 V AC |
Startup with capacitive loads | 200000 μF |
Residual ripple | < 150 mV |
Price is "List Price" and may be subject to a trade discount - check with your local distributor or retailer for actual price.
Specifications
Attribute | Value |
---|---|
Meantime between failure [MTBF] | 876500 h at 77 °F (25 °C), full load conforming to SR 332; 374800 h at 131 °F (55 °C), 80% load conforming to SR 332 |
Output protection type | Against overload and short-circuits, protection technology: manual or automatic reset by switch; Against over temperature, protection technology: automatic reset; Against overvoltage, protection technology: manual reset |
Connections - terminals | Screw connection 4...6 mm², AWG 12...AWG 10) without wire end ferrule output; Screw connection 4 mm², AWG 12) with wire end ferrule output; Screw connection 0.75...6 mm², AWG 18...AWG 12) without wire end ferrule input; Screw connection 0.75...4 mm², AWG 18...AWG 12) with wire end ferrule input; Cage clamp 0.2...1.5 mm², AWG 22...AWG 16) without wire end ferrule diagnostic relay; Cage clamp 0.2...0.75 mm², AWG 22...AWG 18) with wire end ferrule diagnostic relay; Cage clamp 0.2...0.75 mm², AWG 22...AWG 18) with wire end ferrule shut down input |
Line and load regulation | < 0.17% network 100% load in line at 77 °F (25 °C); < 0.6% +/- 0.5% network 150% load at 77 °F (25 °C) |
Status LED | 1 LED (green and red) product status |
Depth | 5.01 in (127.3 mm) |
Height | 4.9 in (124 mm) |
Width | 2.6 in (65 mm) |
Product Weight | 2.54 lb(US) (1.15 kg) |
Output coupling | Parallel |
Marking | CE, CUL Listed, CUL Recognized, RCM, CB Scheme, EAC, KC, UKCA, CURus |
Mounting support | Top hat type TH35-15 rail IEC 60715; Top hat type TH35-7.5 rail IEC 60715; Double-profile DIN rail |
Supply | SELV IEC 60950-1; SELV IEC 60204-1; SELV IEC 60364-4-41 |
Dielectric strength | 4000 V AC with input to output; 2000 V AC with input to ground; 1500 V AC with output to ground; 4000 V AC with input to diagnostic relay; 500 V AC with output to diagnostic relay; 1500 V AC with diagnostic relay to ground; with shutdown input not isolated from output |
Diagnostic relay | Electromechanical relay 1000.0 mA 30 V |
Service life | 10 year(s) 104 °F (40 °C) 80% load |
Overvoltage category | III, II |
Environment
Standards | Value |
---|---|
Standards | IEC 62368-1; EN/IEC 61204-3; IEC 61000-6-1; IEC 61000-6-2; IEC 61000-6-3; IEC 61000-6-4; IEC 61000-3-2; EN 61000-3-3; UL 62368-1; CSA C22.2 No 62368-1; CSA C22.2 No. 107.1 |
Product Certifications
Certification | Status |
---|---|
CE | Yes |
CUL Listed | Yes |
CUL Recognized | Yes |
RCM | Yes |
CB Scheme | Yes |
EAC | Yes |
KC | Yes |
UKCA | Yes |
CURus | Yes |
Operating Conditions
Attribute | Value |
---|---|
Operating altitude | < 5000 m overvoltage category III; overvoltage category II |
Shock resistance | 150 m/s² 11 ms |
IP degree of protection | IP20 |
Ambient air temperature for operation | -13...131 °F (-25...55 °C) without current derating mounting position A < 6561.68 ft (2000 m); 131...158 °F (55...70 °C) with current derating of 3.3% per °C mounting position A < 6561.68 ft (2000 m) |
Electrical shock protection class | Class I |
Pollution degree | 2 |
Vibration resistance | 3.5 mm (f= 3...11.9 Hz) conforming to IEC 60068-2-6; 20 m/s² (f= 11.9...150 Hz) conforming to IEC 60068-2-6 |
Electromagnetic immunity | Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2; Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2; Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3; Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4; Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5; Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5; Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6; Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8; Immunity to voltage dips conforming to IEC 61000-4-11 |
Electromagnetic emission | Disturbing field emission conforming to EN 55016-2-3; Limits for harmonic current emissions conforming to IEC 61000-3-2; conforming to EN 55016-1-2; conforming to EN 55016-2-1; Conducted emissions IEC 61000-6-3; Radiated emissions IEC 61000-6-4 |
Ordering and Shipping Details
Attribute | Value |
---|---|
Category | US1CP1222525 |
Discount Schedule | CP12 |
GTIN | 3606482185258 |
Returnability | Yes |
Country of origin | IN |
Packing Units
Attribute | Value |
---|---|
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 6.10 in (15.500 cm) |
Package 1 Width | 8.27 in (21.000 cm) |
Package 1 Length | 8.74 in (22.200 cm) |
Package 1 Weight | 3.252 lb(US) (1.475 kg) |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Height | 11.81 in (30.000 cm) |
Package 2 Width | 11.81 in (30.000 cm) |
Package 2 Length | 15.75 in (40.000 cm) |
Package 2 Weight | 24.097 lb(US) (10.930 kg) |
Unit Type of Package 3 | P12 |
Number of Units in Package 3 | 168 |
Package 3 Height | 31.50 in (80.000 cm) |
Package 3 Width | 35.43 in (90.000 cm) |
Package 3 Length | 47.24 in (120.000 cm) |
Package 3 Weight | 598.917 lb(US) (271.664 kg) |
Dimensions Drawings
Dimensions:
Front View:
Height: 4.9 in (124 mm)
Width: 2.6 in (65 mm)
Side View:
Depth: 5.01 in (127.3 mm)
Top View:
Width: 2.6 in (65 mm)
Length: 5.01 in (127.3 mm)
Back View:
Width: 2.6 in (65 mm)
Height: 4.9 in (124 mm)
Connections and Schema
Wiring Diagram
Input terminals: L1, L2, L3 for AC input; PE for protective earth.
Output terminals: +1, +2 for positive DC output; -3, -4 for negative DC output.
Diagnostic relay terminals: 11, 14.
Block Diagram
The block diagram illustrates the internal components of the power supply:
- (1) Input
- (2) EMI filter
- (3) Relay control
- (4) Interleave PFC converter
- (5) Primary control
- (6) Main LLC converter
- (7) PFC controller
- (8) Primary AUX
- (9) Synchronous rectifier
- (10) SR controller
- (11) CV & CC feedback
- (12) Secondary MCU
- (13) Secondary AUX
- (14) Output filter
- (15) Automanual switch
- (16) LED control
Mounting and Clearance
Mounting Position
Correct Mounting:
- Ensure adequate clearance around the unit for ventilation.
- Recommended clearances: 2.0 in (50 mm) on top and bottom, 0.40 in (10 mm) on sides, and 0.80 in (20 mm) on the front.
Incorrect Mounting:
Illustrations show incorrect mounting orientations that should be avoided, including mounting upside down or with insufficient clearance.
Performance Curves
Performance Curve (Ambient Temperature vs. Load Percentage)
The graph shows the relationship between ambient temperature (X-axis) and the percentage of maximum load (Y-axis). The power supply can operate at 100% load up to approximately 40°C, after which the maximum load capacity decreases.
Overvoltage Protection Behavior
This diagram illustrates the overvoltage protection behavior:
- (1) Variable output voltage range
- (2) Latch (indicates a protective shutdown)
- (3) Typical overvoltage condition at the output
- (4) Maximum overvoltage protection level
- (5) Overvoltage protection
- (6) Nominal output voltage
- (7) Zero output
The overvoltage range is 26-36 VDC in Latch Mode.
Environmental Data
Schneider Electric is committed to achieving Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via their "Use Better, Use Longer, Use Again" campaign.
Materials and Substances
- Packaging made with recycled cardboard: No
- Packaging without single use plastic: No
- EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
- REACH Regulation: REACH Declaration
Repack and remanufacture
- Circularity Profile: End of Life Information
- Take-back: No
- WEEE: The product must be disposed of in European Union markets following specific waste collection and never end up in rubbish bins.
Related Documents
![]() |
Schneider Electric ABLU3A48100 Regulated Power Supply Data Sheet Technical specifications and data for the Schneider Electric ABLU3A48100 regulated power supply, featuring 380-500V AC input, 48V DC output, and 10A current. |
![]() |
Schneider Electric ABLU3A24400 Regulated Power Supply Data Sheet Technical data sheet for the Schneider Electric ABLU3A24400, a 380-500V AC, 24V, 40A, 3-phase universal regulated power supply. Includes specifications, dimensions, wiring diagrams, and environmental data. |
![]() |
Schneider Electric ABLU3A24100 Regulated Power Supply Data Sheet Detailed product data sheet for the Schneider Electric ABLU3A24100, a 380-500V AC, 24V, 10A, 3-phase universal regulated power supply. Includes specifications, dimensions, wiring diagrams, block diagrams, performance curves, and environmental data. |
![]() |
Schneider Electric ABLS1A24021 Optimized Regulated Power Supply Data Sheet Technical data sheet for the Schneider Electric ABLS1A24021 Optimized Regulated Power Supply, featuring 100-240V AC input, 24V DC output, and 2.1A current. Includes specifications, environmental data, ordering information, and mounting guidelines. |
![]() |
Schneider Electric ABLS1A48050 Optimized Power Supply - 48V, 5A Technical data sheet for the Schneider Electric ABLS1A48050 Optimized Regulated Power Supply. Features include 100-240V AC input, 48V DC output, 5A current, and high efficiency. |
![]() |
Schneider Electric ABLS1A48100 Regulated Power Supply Data Sheet Technical data sheet for the Schneider Electric ABLS1A48100 regulated power supply, featuring 100-240V AC input, 48V DC output, and 10A current. Includes specifications, environmental data, ordering information, and performance curves. |
![]() |
Schneider Electric ATV320U15N4C Variable Speed Drive - 1.5kW, 380-500V Detailed product data sheet for the Schneider Electric ATV320U15N4C variable speed drive. It covers technical specifications, characteristics, environmental ratings, connection diagrams, and performance curves for industrial applications. |
![]() |
Schneider Electric Altivar Machine ATV320 Variable Speed Drive - 2.2kW, 380-500V, 3-Phase Technical data sheet for the Schneider Electric Altivar Machine ATV320 variable speed drive. This compact, 2.2kW, 3-phase drive operates at 380-500V and is suitable for complex machines. Includes specifications, dimensions, environmental data, and connection diagrams. |