Product Data Sheet: ABLU3A48100
Product Name: Regulated Power Supply, 380...500V AC, 48V, 10A, 3 phases, Universal
Model Number: ABLU3A48100
Availability: Stock - Normally stocked in distribution facility
Main Specifications
Range of Product | Modicon Power Supply |
Product or Component Type | Power supply |
Power supply type | Regulated switch mode |
Variant option | Universal |
Enclosure Material | Metal |
Nominal input voltage | 380...500 V AC three phase |
Kw Rating | 480 W |
Output voltage | 48 V DC |
Power supply output current | 10 A |
Permissible temporary current boost | 1.5 x In for 5 seconds |
Complementary Specifications
Efficiency at full load | 92% (at 380V AC and 500V AC) |
Nominal network frequency | 50...60 Hz |
Network system compatibility | TN, TT, IT |
Maximum leakage current | 2 mA @ 500 V AC |
Input protection type | Integrated fuse (not interchangeable) 3.15 A; External protection (recommended) |
Inrush current | 35 A @ 380 V AC; 35 A @ 500 V AC |
Power factor | 0.90 @ 380 V AC; 0.88 @ 500 V AC |
Power dissipation in W | 33 W |
Current consumption | < 0.85 A @ 380 V AC; < 0.73 A @ 500 V AC |
Turn-on time | < 1 s |
Holding time | > 20 ms @ 380 V AC; > 20 ms @ 500 V AC |
Startup with capacitive loads | 200000 µF |
Residual ripple | < 150 mV |
Meantime between failure [MTBF] | 890200 h @ 77 °F (25 °C), full load; 346200 h @ 131 °F (55 °C), 80% load |
Output protection type | Against overload and short-circuits (manual or automatic reset); Against over temperature (automatic reset); Against overvoltage (manual reset) |
Connections - terminals | Screw connection 4...6 mm², AWG 12...AWG 10 (output, without wire end ferrule); Screw connection 4 mm², AWG 12 (output, with wire end ferrule); Screw connection 0.75...6 mm², AWG 18...AWG 10 (input, without wire end ferrule); Screw connection 0.75...4 mm², AWG 18...AWG 12 (input, with wire end ferrule); Cage clamp 0.2...1.5 mm², AWG 22...AWG 16 (diagnostic relay, without wire end ferrule); Cage clamp 0.2...0.75 mm², AWG 22...AWG 18 (diagnostic relay, with wire end ferrule); Cage clamp 0.2...0.75 mm², AWG 22...AWG 18 (shut down input, with wire end ferrule) |
Line and load regulation | < 0.17% (network 100% load @ 77 °F / 25 °C); < 0.6% +/- 0.5% (network 150% load @ 77 °F / 25 °C) |
Status LED | 1 LED (green and red) for product status |
Dimensions and Weight
Depth | 5.008 in (127.2 mm) |
Height | 4.9 in (124 mm) |
Width | 2.6 in (65 mm) |
Product Weight | 2.54 lb(US) (1.15 kg) |
Output coupling | Parallel |
Marking | CE, UKCA |
Mounting support | Top hat type TH35-15 rail IEC 60715; Top hat type TH35-7.5 rail IEC 60715; Double-profile DIN rail |
Electrical Characteristics
Supply | SELV (IEC 60950-1, IEC 60204-1, IEC 60364-4-41) |
Dielectric strength | 4000 V AC (input to output); 2000 V AC (input to ground); 1500 V AC (output to ground); 4000 V AC (input to diagnostic relay); 500 V AC (output to diagnostic relay); 1500 V AC (diagnostic relay to ground); with shutdown input not isolated from output |
Diagnostic relay | Electromechanical relay 1000.0 mA @ 30 V |
Service life | 10 year(s) @ 104 °F (40 °C) @ 80% load |
Overvoltage category | III, II |
Environment
Standards | IEC 62368-1, EN/IEC 61204-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3, IEC 61000-6-4, IEC 61000-3-2, EN 61000-3-3, UL 62368-1, CSA C22.2 No 62368-1, CSA C22.2 No. 107.1 |
Operating altitude | < 5000 m (overvoltage category III); < 2000 m (overvoltage category II) |
Shock resistance | 150 m/s², 11 ms |
IP degree of protection | IP20 |
Ambient air temperature for operation | -13...131 °F (-25...55 °C) without current derating (mounting position A < 6561.68 ft / 2000 m); 131...158 °F (55...70 °C) with current derating of 3.3% per °C (mounting position A < 6561.68 ft / 2000 m) |
Electrical shock protection class | Class I |
Pollution degree | 2 |
Vibration resistance | 3.5 mm (f= 3...11.9 Hz); 20 m/s² (f= 11.9...150 Hz) |
Electromagnetic immunity | Immunity to electrostatic discharge: 8 kV (contact), 15 kV (air); Immunity to conducted RF disturbances: 15 V/m (80 MHz-2 GHz), 5 V/m (2-2.7 GHz), 5 V/m (2.7-6 GHz); Immunity to fast transients: 4 kV (input-output); Surge immunity test: 4 kV (power supply and earth), 3 kV (between phases); Immunity to conducted RF disturbances: 15 V (0.15-80 MHz); Immunity to magnetic fields: 30 A/m (50-60 Hz); Immunity to voltage dips; Disturbing field emission; Limits for harmonic current emissions |
Electromagnetic emission | Conducted emissions: IEC 61000-6-3; Radiated emissions: IEC 61000-6-4 |
Ordering and Shipping Details
Category | US1CP1222525 |
Discount Schedule | CP12 |
GTIN | 3606482185265 |
Returnability | Yes |
Country of origin | TH |
Packing Units
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 3.72 in (9.45 cm) |
Package 1 Width | 6.97 in (17.7 cm) |
Package 1 Length | 7.36 in (18.7 cm) |
Package 1 Weight | 3.333 lb(US) (1.512 kg) |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 7 |
Package 2 Height | 11.81 in (30.0 cm) |
Package 2 Width | 11.81 in (30.0 cm) |
Package 2 Length | 15.75 in (40.0 cm) |
Package 2 Weight | 24.7 lb(US) (11.2 kg) |
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via its ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.
Materials and Substances
- Packaging made with recycled cardboard: No
- Packaging without single use plastic: No
- EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
- REACH Regulation: REACH Declaration
Repack and remanufacture
- Circularity Profile: End of Life Information
- Take-back: No
- WEEE: The product must be disposed of in European Union markets following specific waste collection and never end up in rubbish bins.
Dimensions Drawings
The following diagram illustrates the physical dimensions of the power supply:
[Diagram showing front, side, and top views with dimensions in mm and inches. Front view shows width 65mm (2.6in) and height 124mm (4.9in). Side view shows depth 127.2mm (5.008in).]
Wiring Diagram
The following diagram illustrates the basic wiring connections:
[Diagram showing input terminals L1, L2, L3, PE connected to a power source. Output terminals +1, +2, -3, -4 are shown. A relay contact 11-14 is also depicted.]
Block Diagram
The following diagram provides a functional block representation of the power supply:
[Block diagram showing input (1), EMI filter (2), Relay control (3), Interleave PFC converter (4), Primary control (5), Main LLC converter (6), PFC controller (7), Primary AUX (8), Synchronous rectifier (9), SR controller (10), CV & CC feedback (11), Secondary MCU (12), Secondary AUX (13), Output filter (14), Automanual switch (15), LED control (16). Connections between blocks are shown.]
Mounting and Clearance
Mounting Position
[Diagram showing recommended mounting with clearance requirements. Minimum clearance of 20mm (0.80in) above and below, and 10mm (0.40in) on the sides is indicated. Also shows incorrect mounting examples with 'X' marks.]
Performance Curves
Performance Curve
[Graph showing Percentage of Maximum Load (Y-axis) versus Surrounding Air Temperature (°C) (X-axis). The curve indicates that the power supply can operate at 100% load up to approximately 50°C, with derating occurring above this temperature.]
Overvoltage Protection Behavior
[Diagram illustrating overvoltage protection behavior. It shows a nominal output voltage range, overvoltage protection level, and latch mode for overvoltage conditions.]