R. STAHL LS Leitungsschutzschalter 8530/1-MCB-STA103-B6-000-3
Art. Nr. 272160
Product Overview
The R. STAHL 8530/1-MCB-STA103-B6-000-3 LS Miniature Circuit Breaker is designed for system technology applications. It offers good current limitation for short circuits and high breaking capacity (10, 15, or 25 kA), leading to reduced stress on cables and higher selectivity with upstream fuses. The modular design allows for 1- to 4-pole configurations and current ratings from 0.5–63 A, with a maximum installation capacity of 4.5 modules (TE).
Key features include:
- Trennerfunktion according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of installations due to modular design
- Simple mounting by snapping onto a top-hat rail in Ex e enclosures
- Fixed thermal and magnetic trip units
- Ergonomically shaped operating lever for secure switching
- Protection against re-switching during maintenance using padlocks (accessory)
Technical Data
Explosion Protection
Feature | Details |
---|---|
Einsatzbereich (Zonen) | 1, 2 |
Einsatzbereich (Zonen) Hinweis | Usable in Zone 21 / 22 with protection via enclosure Ex tb / tc |
IECEx Bescheinigung Gas | IECEx FMG 19.0029U |
IECEx Gasexplosionsschutz | Ex db eb IIC Gb |
ATEX Bescheinigung Gas | FM19ATEX0191U |
ATEX Gasexplosionsschutz | II 2 G Ex db eb IIC Gb |
Bescheinigungen | ATEX (FM), Brazil (ULB), IECEx (FM), People's Republic of China (CQST) |
Konformitätserklärungen | Conformity certificate (ATEX), People's Republic of China (CCC) |
Electrical Data
Feature | Details |
---|---|
Bemessungsbetriebsspannung AC | 230/400 V |
Bemessungsbetriebsstrom | 6 A |
Frequenz | 50/60 Hz |
Bemessungsschaltvermögen | 10 kA |
Elektrische Lebensdauer | 2 x 10⁴ |
Mechanische Lebensdauer | 2 x 10⁴ |
1. Hilfsfunktion | None |
Bemessungsspannung 1. Hilfsfunktion AC | - |
Max. Bemessungsstrom 1. Hilfsfunktion | - |
2. Hilfsfunktion | None |
Max. Spannung 2. Hilfsfunktion DC | - |
Auslösecharakteristik | B |
Polzahl | 3-pole |
Umgebungsbedingungen
Feature | Details |
---|---|
Umgebungstemperatur | -40 °C ... 70 °C (-40 °F ... 158 °F) |
Umgebungstemperatur Hinweis | Deviating ambient temperatures are available upon request based on current certificates. |
Mechanische Daten
Feature | Details |
---|---|
Schutzart (IP) (IEC 60529) | IP2X |
Gehäusematerial | Thermoplast |
Anschlussquerschnitt min. | 1.5 mm² |
Anschlussquerschnitt max. | 25 mm² |
Anschlussquerschnitt AWG min. | 16 AWG |
Anschlussquerschnitt AWG max. | 4 AWG |
Anschlussquerschnitt 2 min. | 1.5 mm² |
Anschlussquerschnitt 2 max. | 10 mm² |
Anschlussquerschnitt 2 AWG min. | 16 AWG |
Anschlussquerschnitt 2 AWG max. | 8 AWG |
Anzugsdrehmoment min. | 2 N·m |
Anzugsdrehmoment max. | 3 N·m |
Anschlussquerschnitt Hinweis | 2-conductor connection (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (A cross-section difference between the upper and lower chamber is permitted.) The permissible combination of connection cross-sections can be found in the operating manual. |
Breite | 83 mm (3.27 in) |
Länge | 165 mm (6.5 in) |
Einbautiefe | 138.3 mm (5.44 in) |
Gewicht | 1.4 kg (3.087 lb) |
Montage / Installation
Feature | Details |
---|---|
Anzugsdrehmoment | 2–3 N·m |
Anzugsdrehmoment lbf·in | 17.7 ... 26.6 lbf·in |
Anzugsdrehmoment Hilfskontakt | 0.4–0.6 N·m |
Anzugsdrehmoment Hilfskontakt lbf·in | 3.5 ... 5.3 lbf·in |
Technical Drawings
(Note: Diagrams are illustrative and subject to change. Refer to original documentation for precise details.)
Tripping Characteristic B Curve:
A graph illustrates the tripping time in seconds against multiples of the rated current (I/In) for AC and DC. The curve shows the typical response for a Type B breaker, indicating the threshold for tripping under overload and short-circuit conditions. The graph includes a limit curve from a cold state.
Dimensional Drawings:
Detailed drawings show the dimensions of the circuit breaker in millimeters and inches. Key dimensions include width, length, and installation depth. The drawings indicate the modularity (e.g., 8530/1; 3 division units) and mounting details.
Accessories
Abschließvorrichtung vierfach (Lock-out/Tag-out Device)
A four-way lock-out/tag-out device for individually securing components, allowing up to 4 cylinder locks. Art. Nr. 227232.
Befestigungsset (Mounting Set)
A mounting set for securing the component to the mounting plate without a top-hat rail. Art. Nr. 276618.
Zylinderschloss (Cylinder Lock)
For locking (shackle Ø 3). Art. Nr. 107115.
Changes to technical data, dimensions, weights, designs, and delivery options are reserved. Illustrations are non-binding.
Contact Information:
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30
74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777
Email: sales.de@r-stahl.com
Website: https://www.r-stahl.com