Eaton 9SX Gen2 UPS
Powering Business Worldwide
Product Overview
The Eaton 9SX Gen2 UPS delivers reliable battery backup and advanced power management for critical equipment. It is designed for small and medium datacenters, distributed IT environments, edge networks, network closets, and server rooms.
Optimize Your Space with Reliable Power Density
Reduce your physical footprint with impressive power density. The 9SX Gen2 offers up to 11kW in a 4U rackmount format and 6kW in a 3U format, maximizing space efficiency.
Advanced Connectivity for Modern Needs
Benefit from enhanced connectivity and robust cybersecurity with the optional NM3 Gigabit Network Card. Manage your entire install base remotely, including UPS settings and firmware upgrades. Seamlessly integrate the 9SX Gen2 with digital solutions from the Brightlayer Data Centers suite.
Save on Energy and Cooling Costs with Energy Star-Qualified UPS
Achieve up to 97.2% efficiency in the 11kW unit, thanks to advanced, next-generation power electronics components. This contributes to lower energy consumption and reduced cooling costs.
Connect More Equipment
The 9SX Gen2 UPS provides more outlets than previous versions, offering greater flexibility for power distribution needs. Models rated 5/6kVA include 3 C19 and 8 C13 outlets, while 8/11kVA models feature 4 C19 and 8 C13 outlets, organized into two remotely controlled groups.
Revolutionary Battery Management
Eaton's new ABM+ (Advanced Battery Management) technology utilizes predictive analytics to monitor battery health. It identifies the optimal time for easy, hot-swap battery replacement based on actual usage and conditions, preventing unexpected downtime and premature replacement costs. Optimized ABM+ charging can also increase battery lifespan by up to 50%.
Product Views and Features
Front Panel Features
- Graphical LCD display with LED Status bar: Provides clear information on UPS status and measurements. Offers enhanced configuration capabilities and is available in 7 languages.
- Panel for batteries replacement: Designed for easy, hot-swappable battery replacement.
Rear Panel Features
- Slot for optional communication card (e.g., Network-M3, INDGW-M2, INDRELAY-MS, Relay-MS).
- USB and Serial ports (cannot be used simultaneously).
- Relay output ports (2 outputs).
- RPO (Remote Power Off) and ROO (Remote On/Off) ports.
- MBP (Maintenance Bypass) detection port.
- IEC outputs: Two groups of remote-controlled sockets (3 C19 and 8 C13 for 5/6kVA models; 4 C19 and 8 C13 for 8/11kVA models).
- Input/output connection terminal block.
- External battery (EBM) connector.
Technical Specifications
Rating (kVA/kW) | 5kVA / 5kW | 6kVA / 6kW | 8kVA / 8kW | 11kVA / 11kW |
---|---|---|---|---|
Technology | On-line double conversion with Power Factor Correction (PFC) system | |||
Nominal voltage | 200/208/220/230/240V | |||
Input voltage range | 176-276V without derating (100-276V with derating) | |||
Output voltage / THDv | 200/208/220/230/240V +/- 1%; THDv <1% | |||
Input frequency range / THDI | 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 3% | |||
Efficiency | Up to 96.7% in Online mode | Up to 97.2% in Online mode | ||
Crest factor/short circuit current | 3:1 / 90A | 3:1 / 90A | 3:1 / 120A | 3:1 / 150A |
Overload capacity | 102%-125%: 10min, 125%-150%: 30s, >150%: 0.5s | |||
Input Connections | Terminal block (up to 10 mm²) | |||
Output Connections | Terminal block + 3 C19 + 8 C13 (2 controlled groups) | Terminal block + 3 C19 + 8 C13 (2 controlled groups) | Terminal block + 4 C19 + 8 C13 (2 controlled groups) |
Typical Backup Times (minutes / hours)
Load | 5kVA / +1EBM / +4EBM | 6kVA / +1EBM / +4EBM | 8kVA / +1EBM / +4EBM | 11kVA / +1EBM / +4EBM |
---|---|---|---|---|
1000W | 31 / 113 / 384 | 31 / 113 / 384 | 65 / 145 / 410 | 65 / 145 / 410 |
2000W | 13 / 52 / 185 | 13 / 52 / 185 | 25 / 65 / 185 | 25 / 65 / 185 |
4000W | 5 / 22 / 86 | 5 / 22 / 86 | 10.5 / 27 / 89 | 10.5 / 27 / 89 |
6000W | - | 2.5 / 13 / 53 | 5.5 / 16 / 56 | 5.5 / 16 / 56 |
8000W | - | - | 3.5 / 10.5 / 39 | 3.5 / 10.5 / 39 |
10000W | - | - | - | 2 / 7.5 / 30 |
Battery Management
ABM+ (Predictive battery life) & Temperature compensated charging method, Automatic battery test, deep discharge protection, automatic recognition of external battery units.
Communication
Communication Ports: 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 mini terminal blocks (Dry contacts, 2 inputs, 2 outputs).
Communication Slot: 1 slot for Network-M3, INDGW-M2, INDRELAY-MS or Relay-MS.
Operating Conditions, Standards and Approvals
- Operating temperature: 0 to 40°C continuous
- Typical Noise level: 38db
- Safety: IEC/EN 62040-1, UL 1778 & CSA 22.2
- EMC, Performance: IEC/EN 62040-2, IEC/EN 62040-3
- Approvals: CE, CB report (TUV), UL (except 9SXEBM240G2 & 9SXEBM240RT3UG2)
Dimensions and Weight
5kVA / 6kVA | 8kVA | 11kVA | |
---|---|---|---|
UPS (W x H x D) | 440(19") x 130(3U) x 684 mm | 440(19") x 174(4U) x 725 mm | 440(19") x 174(4U) x 725 mm |
UPS Weight | 43.1 kg | 78.8 kg | 78.8 kg |
EBM (W x H x D) | 440(19") x 130(3U) x 636 mm | 440(19") x 130(3U) x 670 mm | 440(19") x 130(3U) x 670 mm |
EBM Weight | 65.7 kg | 62 kg | 62 kg |
Parts Numbers
Description | 9SX G2 5kVA | 9SX G2 6kVA | 9SX G2 8kVA | 9SX G2 11kVA |
---|---|---|---|---|
UPS (RT format) | 9SX5KIRT3UG2 | 9SX6KIRT3UG2 | 9SX8KIG2 | 9SX11KIG2 |
UPS (RT with rack kit) | - | - | 9SX8KIRT4UG2 | 9SX11KIRT4UG2 |
EBM (RT format) | 9SXEBM180RT3UG2 | 9SXEBM180RT3UG2 | 9SXEBM240G2 | 9SXEBM240G2 |
EBM (RT with rack kit) | - | - | 9SXEBM240RT3UG2 | 9SXEBM240RT3UG2 |
HotSwap Maintenance Bypass | MBP6KIG2 | MBP6KIG2 | MBP11KIG2 | MBP11KIG2 |
2m battery connection cable | EBMCBL180RT | EBMCBL180RT | EBMCBL240RT | EBMCBL240RT |
Rack kit | - | - | 9RK | 9RK |