Eaton 9SX 2000I UPS
Powering Business Worldwide
Product Overview
The Eaton 9SX 2000I is a tower-style Uninterruptible Power Supply (UPS) designed for reliable power protection. It features an on-line double conversion topology with Power Factor Correction (PFC).
Part Number: 9SX2000I
Model: Eaton 9SX 2000I
General Specifications
Topology | On-line double conversion with PFC (Power Factor Correction) system |
Configuration | Tower |
Rating (VA/Watts) | 2000/1800 |
Dimensions (H x W x D, mm) | 346 x 214 x 412 |
Warranty | 2 years warranty |
Electrical Input
Connection | (1) IEC-320-C14 |
Input Voltage Range | 200-276V without derating (up to 140-276V with derating) |
Nominal Voltage | 200/208/220/230/240V |
Frequency | 50/60 Hz autoselection |
Frequency Range | 40-70 Hz |
Electrical Output
Outlets | (8) IEC-320-C13 |
Output Frequency | 50/60 Hz autoselect, frequency converter as standard |
Battery Performance
The runtime graph illustrates the approximate runtime in minutes versus load in Watts for the Eaton 9SX 2000I UPS with varying numbers of Extended Battery Modules (EBMs). The graph shows four distinct lines representing runtimes with 1, 2, 3, and 4 EBMs. As the load increases, the runtime decreases. Additional EBMs significantly extend the operational time. Battery runtimes are approximate and may vary with equipment, configuration, battery age, and temperature. Actual runtime may vary from +/- 15% around these typical values.
Battery Management: ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
Extended Battery Capability: EBM
Communications
User Interface | Multilingual graphical LCD display |
Communication Ports | 1 USB port + 1 serial RS232 port + 1 mini-terminal block for Remote Power Off + 1 mini-terminal block for Output relay |
Communication Slot | 1 slot for Network-M2, Network-MS, ModBus-MS or Relay-MS cards |
Environmental & Standards
Audible Noise | <45dB |
Operating Temperature | 0 to 40°C continuous |
Safety markings | IEC/EN 62040-1, UL 1778, CSA 22.2 |
EMC Markings | IEC/EN 62040-2, FCC Class B, CISPR22 Class B |
Approvals | CE /CB report (TUV) / cULus / EAC / RCM / BIS / KCC |