ifm AL1302 IO-Link Master with PROFINET Interface
IO-Link Master DL PN 8P IP67
Product Overview
The ifm AL1302 is an IO-Link master designed for field applications, providing a robust fieldbus interface. It integrates seamlessly with PROFINET networks, enabling efficient data acquisition and control in industrial environments.
Application
Application Type: I/O modules for field applications
Function: Fieldbus interface
Daisy-chain function: Supported
Electrical Data
Parameter | Value |
---|---|
Operating voltage | 20...30 DC; (US; to SELV/PELV) [V] |
Current consumption | 300...3900; (US) [mA] |
Protection class | III |
Sensor supply US | (Value not specified) |
Max. current load total | 3.6 [A] |
Inputs / Outputs
Total number of inputs and outputs: 16; (configurable)
Breakdown: Number of digital inputs: 16; Number of digital outputs: 8
Inputs
Parameter | Value |
---|---|
Number of digital inputs | 16; (IO-Link Port Class A: 8 x 2) |
Switching level high | 11...30 [V] |
Switching level low | 0...5 [V] |
Digital inputs protected against short circuits | Yes |
Outputs
Parameter | Value |
---|---|
Number of digital outputs | 8; (IO-Link Port Class A: 8 x 1) |
Max. current load per output | 300 [mA] |
Short-circuit proof | Yes |
Interfaces
Communication interface: Ethernet; IO-Link
Ethernet - Internet of Things
Parameter | Details |
---|---|
Transmission standard | 10Base-T; 100Base-TX |
Transmission rate | 10; 100 [Mbps] |
Protocol | MQTT JSON |
Factory settings | IP address: 169.254.x.x Subnet mask: 255.255.0.0 Gateway IP address: 0.0.0.0 MAC address: see type label Secure protocol: HTTPS |
Ethernet - PROFINET
Parameter | Details |
---|---|
Transmission standard | 10Base-T; 100Base-TX |
Transmission rate | 10; 100 [Mbps] |
Protocol | PROFINET |
Factory settings | IP address: 0.0.0.0 Subnet mask: 0.0.0.0 Gateway IP address: 0.0.0.0 MAC address: see type label Conformance Class: CC-C Netload Class: III IRT capability: Supported |
Note on interfaces | SNMP (Simple Network Management Protocol), MRP (Media Redundancy Protocol). Supported network topologies: line, ring. |
IO-Link Master
Parameter | Details |
---|---|
Transmission type | COM1 (4.8 kBaud); COM2 (38.4 kBaud); COM3 (230.4 kBaud) |
IO-Link revision | 1.1 |
Number of ports class A | 8 |
Operating Conditions
Parameter | Value |
---|---|
Ambient temperature | -25...60 [°C] |
Storage temperature | -25...85 [°C] |
Max. relative air humidity | 90 [%] |
Protection | IP 65; IP 66; IP 67 |
Degree of soiling | 2 |
Tests / Approvals
Category | Standard / Specification |
---|---|
EMC | EN 61000-6-2, EN 61000-6-4 |
Shock resistance | DIN EN 60068-2-27 |
Vibration resistance | DIN EN 60068-2-64 2009-04, DIN EN 60068-2-6 2008-10 |
MTTF | 78 [years] |
Mechanical Data
Parameter | Details |
---|---|
Weight | 379.5 [g] |
Materials | Housing: PA; Socket: brass nickel-plated |
Sealing material | FKM / FKM |
Remarks: For further information please see the operating instructions.
Pack quantity: 1 pcs.
Electrical Connections
Ethernet Connection
Connector: M12; Sealing: FKM
Pinout Description: 5-pin M12 connector for Ethernet.
Pin 1: TX+Pin 2: RX+Pin 3: TX-Pin 4: RX-Pin 5: not usedPROFINET X21, X22
Pinout Description: 5-pin connector for PROFINET.
Pin 1: TX +Pin 2: RX +Pin 3: TX -Pin 4: RX -Pin 5: not usedIoT X23
Pinout Description: 5-pin connector for IoT.
Pin 1: TX +Pin 2: RX +Pin 3: TX -Pin 4: RX -Pin 5: not usedProcess Connection
Connector: M12; Sealing: FKM
IO-Link Port Class A (X01...X08)
Connector: M12
Pinout Description: 5-pin M12 connector for IO-Link ports.
Pin 1: Sensor supply (US) L+Pin 2: digital inputPin 3: Sensor supply (US) L-Pin 4: C/Q IO-LinkPin 5: not usedVoltage Supply Connection
Connector: M12
Pinout Description: 4-pin M12 connector (X31) for voltage supply.
Pin 1: + 24 V DC (US)Pin 2: not usedPin 3: GND (US)Pin 4: not used