EDECOA Hybrid Inverter / Charger

USER MANUAL

Models: EM-161A, EM-252A, EM-302A

Version: 2.3

1. ABOUT THIS MANUAL

This manual describes the operation and troubleshooting suggestions for EDECOA Hybrid Inverter EM-161A, EM-252A and EM-302A. Please read this manual carefully before operations. Keep this manual for future reference.

2. SAFETY INSTRUCTIONS

⚠️ WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION To reduce the risk of injury, charge only deep-cycle lead acid-type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. DO NOT disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. NEVER charge a frozen battery.
  5. For optimum operation of this inverter/charge, please follow the required specifications to select the appropriate cable size. It's very important to correctly operate this inverter/charger.
  6. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION for details.

3. INTRODUCTION

This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/ solar charger priority, and acceptable input voltage based on different applications.

Features

Basic System Architecture

The following illustration shows the basic application for this inverter/charger. It also includes the following devices to have a complete running system:

Consult with your system integrator for other possible system architectures depending on your requirements.

This inverter can power all kinds of appliances in the home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Diagram Description: A schematic shows a hybrid power system. A solar panel array is connected to a central unit labeled "EDECOA Hybrid Inverter/Charger". This unit is also connected to a "Generator OR Utility" source and "External Battery packs". The output of the central unit powers "Home Appliances" such as a fan, light bulb, computer, and television.

3. OPERATION

Power ON/OFF

Side view of unit

Once the unit has been properly installed and the batteries are connected, simply press the ON/OFF switch (located on the button of the case) to turn on the unit.

Operation and Display Panel

The operation and display panel, shown in the below chart, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LCD display

LED Indicator Table:

LED Indicator Messages
AC/INV (Green) Solid On: Output is powered by utility in Line mode
Flashing: Output is powered by battery or PV in battery mode
CHG (Green) Solid On: Battery is fully charged.
Flashing: Battery is charging.
FAULT (Red) Solid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function keys Table:

Function Keys Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

LCD Display Icons

Input Source Information:

Configuration Program and Fault Information:

Output Information:

Battery Information:

In AC mode, it indicates battery charging status.

Battery Charging Status Table:

Status Battery voltage LCD Display
Constant Current mode/ Constant <2V/cell 4 bars will flash in turns.
Voltage mode 2 ~ 2.083V/cell Bottom bar will be ON and the other three bars will flash in turns.
Voltage mode 2.083 ~ 2.167V/cell Bottom two bars will be ON and the other two bars will flash in turns.
Voltage mode > 2.167 V/cell Bottom three bars will be ON, and the top bar will flash.
Floating mode, Batteries are fully charged 4 bars will all be ON.

In battery mode, it indicates battery capacity.

Battery Capacity Table:

Load Percentage Battery Voltage LCD Display
Load >50% < 1.717V/cell [Battery Icon: Empty]
Load >50% 1.717V/cell ~ 1.8V/cell [Battery Icon: 1/4 full]
Load >50% 1.8 ~ 1.883V/cell [Battery Icon: 1/2 full]
Load >50% > 1.883V/cell [Battery Icon: 3/4 full]
50%>Load>20% < 1.817V/cell [Battery Icon: Empty]
50%>Load>20% 1.817V/cell~1.9V/cell [Battery Icon: 1/4 full]
50%>Load>20% 1.9 ~1.983V/cell [Battery Icon: 1/2 full]
50%>Load>20% > 1.983V/cell [Battery Icon: 3/4 full]
Load<20% <1.867V/cell [Battery Icon: Empty]
Load<20% 1.867V/cell~1.95V/cel [Battery Icon: 1/4 full]
Load<20% 1.95~2.033V/cell [Battery Icon: 1/2 full]
Load<20% >2.033V/cell [Battery Icon: 3/4 full]

Load Information:

Mode Operation Information:

Mute Operation:

Program Settings

After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Setting Program Table:

Program Description Selectable option
00 Exit setting mode Escape [ESC Icon]
01 Output source priority: To configure load power source priority SUB priority (default): Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility energy will supply power the loads at the same time. Battery provides power to the loads only when any one condition happens: Solar energy and utility are not available. Solar energy is not sufficient and utility is not available.
SUB priority: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power the loads at the same time. Utility provides power to the load only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02 Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) 10A, 80A
03 AC input voltage range Appliances (default) [RPL Icon]
UPS [UPS Icon]
04 Power saving mode enable/disable Saving mode disable (default) [SDS Icon]
Saving mode enable [SEN Icon]
05 Battery type AGM (default) [AGN Icon]
User-Defined [USE Icon]
Flooded [FLD Icon]
06 Auto restart when overload occurs Restart disabled (default) [Rtd Icon]
Restart enabled [Rte Icon]
07 Auto restart when over temperature occurs Restart disabled (default) [Rtd Icon]
Restart enabled [Rte Icon]
08 Output voltage 220V (Default), 230V, 240V
09 Output frequency 50Hz (default), 60Hz
10 BMS protocol PAC, PLY
11 Maximum utility charging current [Value in program 02]
12 Setting voltage point back to utility source when selecting "SBU priority". EM-252A/EM-302A: 22.0V (Default), 25.5V
EM-161A: 11.0V (default), 11.5V, 12.8V
13 Setting voltage point back to battery mode when selecting "SBU priority". EM-252A/EM-302A: Battery fully charged 24V, 27V(default), 29V
EM-161A: Battery fully charged 12.0V
16 Charger source priority: To configure charger source priority Solar first [SOL Icon]
Solar and Utility (default) [SNU Icon]
Only Solar [SOL Icon]
18 Alarm control Alarm on (default) [ALN Icon]
Alarm off [ALF Icon]
19 Auto return to default display screen Return to default display screen (default) [ESP Icon]
Stay at latest screen [SEP Icon]
20 Backlight control Backlight on (default) [LON Icon]
Backlight off [LOF Icon]
22 Beeps while primary source is Alarm on (default) [RON Icon]
Alarm off [ROF Icon]
23 Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. Bypass disabled (default) [bYD Icon]
Bypass enabled [bYE Icon]
25 Record Fault code Record enabled [FEN Icon]
Record disabled (default) [Fd5 Icon]
26 Bulk charging voltage (C.V voltage) EM-161A default: 14.1V
EM-252A/EM-302A default: 28.2V
27 Floating charging voltage EM-161A default: 13.5V
EM-252A/EM-302A default: 27.0V
29 Low DC cut-off voltage EM-161A default: 10.5V
3KVA-24V default: 21.0V
33 Battery equalization Battery equalization (default) [EEN Icon]
Battery equalization disable [EdS Icon]
34 Battery equalization voltage EM-161A default: 14.6V
EM-252A/EM-302A default: 29.2V
35 Battery equalized time 60min (default), 120min (default)
36 Battery equalized timeout 60min (default), 120min (default)
37 Equalization interval 30days (default)
39 Equalization activated immediately Enable [REN Icon]
Disable (default) [RdS Icon]

Display Setting

The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, PV power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, CPU Version.

Selectable information Table:

Selectable information LCD display
Input voltage/Output voltage (Default Display Screen) Input Voltage=230V, output voltage=230V
[Diagram: LCD showing input 230V, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
Input frequency Input frequency=50Hz
[Diagram: LCD showing input frequency 50.0Hz, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
PV voltage PV voltage=60V
[Diagram: LCD showing PV voltage 60V, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
PV power MPPT charging power = 500W
[Diagram: LCD showing PV power 500W, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
Charging current AC and PV Charging current=50A
[Diagram: LCD showing AC and PV charging current 50A, output 230V with icons for AC, PV, Utility, Bypass, Load, Solar, Battery]
Charging current: 25A
[Diagram: LCD showing charging current 25A, output 230V with icons for PV, Utility, Bypass, Load, Solar, Battery]
AC Charging current=50A
[Diagram: LCD showing AC charging current 50A, output 230V with icons for AC, Utility, Bypass, Load, Solar, Battery]
Battery voltage/ output voltage Battery voltage=25.5V, Output voltage=230V
[Diagram: LCD showing battery voltage 25.5V, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
Output frequency Output frequency=50Hz
[Diagram: LCD showing output frequency 50.0Hz, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
Load percentage Load percent=70%
[Diagram: LCD showing load percentage 70%, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
Load in VA When connected load is lower than 1kVA, load in VA will present xxx VA like below.
[Diagram: LCD showing 350 VA, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
When load is larger than 1kVA (≥1KVA), load in VA will present x.x kVA like below.
[Diagram: LCD showing 1.50 kVA, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
Load in Watt When load is lower than 1kW, load in W will present xxx W like below.
[Diagram: LCD showing 270 W, output 230V with icons for Utility, Bypass, Load, Solar, Battery]
When load is larger than 1kW (≥1KW), load in W will present x.x kW like below.
Battery voltage/DC discharging current Battery voltage=25.5V, discharging current=1A
[Diagram: LCD showing battery voltage 25.5V, discharging current 1A with icons for Utility, Bypass, Load, Solar, Battery]
CPU version checking CPU version 20 11
[Diagram: LCD showing CPU version 20 11 with icons for Utility, Bypass, Load, Solar, Battery]

Operating Mode Description

Operation mode Description LCD display
Standby mode / Power saving mode
Note:
*Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output.
*Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected.
No output is supplied by the unit but it still can charge batteries. Charging by utility and PV energy.
[Diagram: Icons for Solar, Utility, Battery, Load]
Charging by utility.
[Diagram: Icons for Utility, Battery, Load]
Charging by PV energy.
[Diagram: Icons for Solar, Battery, Load]
No charging.
[Diagram: Icons for Battery, Load]
Fault mode
Note
* Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on
PV energy and utility can still charge batteries. Charging by utility and PV energy.
[Diagram: Icons for Solar, Utility, Battery, Load]
Charging by utility.
[Diagram: Icons for Utility, Battery, Load]
Charging by PV energy.
[Diagram: Icons for Solar, Battery, Load]
No charging.
[Diagram: Icons for Battery, Load]
Line Mode The unit will provide output power from the mains. It will also charge the battery at line mode. Charging by utility and PV energy.
[Diagram: Icons for Solar, Utility, Bypass, Load, Battery]
Charging by utility.
[Diagram: Icons for Utility, Bypass, Load, Battery]
Battery Mode The unit will provide output power from battery and PV power. If "SUB priority" is selected as output source priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time.
[Diagram: Icons for Solar, Utility, Bypass, Load, Battery]
PV energy will supply power to the loads and charge battery at the same time.
[Diagram: Icons for Solar, Battery, Load]
Power from battery only.
[Diagram: Icons for Battery, Load]

4. Battery Equalization Description

Equalization function is added to charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have but up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.

How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in the device by either one of the following methods:

  1. Check that program 5 is the user-defined or flooded mode.
  2. Check program 33 is enabled.
  3. Setting equalization in program 34 to program 37, that depends on your battery requirements. (detailed information in LCD Setting part).
  4. Active equalization immediately in program 39.

When to Equalize

In the float stage, when the setting equalization interval (battery equalization cycle) arrives, or equalization is active immediately, the controller will start to enter Equalize stage.

Equalize charging time and timeout

[Diagram: Charging curve showing stages: BULK, ABSORPTION, FLOAT, EQUALIZE, FLOAT, with voltage and time axes.]

In Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

5. Fault Reference Code

When fault occurs, ERROR icon will be on, please check the fault code below when it happens.

Fault Code Fault Event Icon
01 Fan is locked when inverter is OFF [01 Icon]
02 Over temperature [02 Icon]
03 Battery voltage is too high [03 Icon]
04 Battery voltage is too low [04 Icon]
05 Output short circuited or over temperature is detected on internal converter components [05 Icon]
06 Output voltage is too high [06 Icon]
07 Overload time out [07 Icon]
08 Bus voltage is too high [08 Icon]
09 Bus soft start failed [09 Icon]
11 Main relay failed [11 Icon]
13 Solar charger stops due to high PV voltage [13 Icon]
51 Over current/Surge [51 Icon]
52 Bus voltage is too low [52 Icon]
53 Soft start failure [53 Icon]
55 Over DC voltage [55 Icon]
57 Current sensor failure [57 Icon]
58 Output voltage is too low [58 Icon]

6. Warning Indicator

When warning occurs, ⚠️ icon will be on, please check the fault code below when it happens.

Warning Code Warning Event Audible Alarm Icon flashing
01 Fan is locked when inverter is on. Beep three times every second [01 Icon]
03 Battery over-charged Beep once every second [03 Icon]
04 Low battery Beep once every second [04 Icon]
07 Overload Beep once every 0.5 second [07 Icon with LOAD/OVERLOAD diagram]
10 Output power derating Beep twice every 3 seconds [10 Icon]
12 Solar charger stops due to low battery. [12 Icon]
13 Solar charger stops due to high PV voltage [13 Icon]
14 Solar charger stops due to overload. [14 Icon]

7. Lithium Battery and The Interface

1. Long press ENTER key to enter the setting item and set the 05 item to lithium battery mode Lib (as shown in the figure below)

Communication port pin definition Table:

Pin number Port definitions
1 TX
2 RX
3 VCC
4 VCC
5 RS485A
6 RS485B
7 GND
8 GND

2. Long press the ESC key to enter the lithium battery display interface (as shown in the picture below)

The initial display interface indicates the total battery voltage and remaining battery capacity

Press the DOWN key to indicate the data as below in turn

LCD data on the left Table:

LCD data on the left LCD data on the right
Total battery voltage Remaining battery capacity
Battery charging current Battery discharge current
Battery capacity Battery charge/discharge times
BMS board temperature MOSFET temperature on BMS board

Detailed description of display interface for lithium battery

Total battery voltage, Battery residual capacity (Initial interface display)

Total battery voltage=50.5V Battery residual capacity=4%
[Diagram: LCD showing total battery voltage 50.5V, residual capacity 4% with icons for Battery, Load]

Battery charging current, Battery discharge current

Battery charging current= 0A Battery discharge current= 21A
[Diagram: LCD showing battery charging current 0A, discharge current 21A with icons for Input, Battery, Load]

Battery capacity; Battery charger/ discharge Times

Battery capacity= 100Ah Battery charger/discharge Times=4
[Diagram: LCD showing battery capacity 100Ah, charge/discharge times 4 with icons for Battery, Load]

BMS board temperature; MOSFET temperature of BMS board

Battery ambient temperature=25.9°C Battery MOS temperature=25.7°C
[Diagram: LCD showing battery ambient temp 25.9°C, MOS temp 25.7°C with icons for Temp, Battery, Load]

Maximum voltage of a single battery, Minimum voltage of a single battery

Maximum voltage of a single battery=3.20V Minimum voltage of a single battery= 3.10V
[Diagram: LCD showing max voltage 3.20V, min voltage 3.10V with icons for Battery, Load]

Maximum temperature of a single battery, Minimum temperature of a single battery

Maximum temperature of a single battery=25.0°C Minimum temperature of a single battery=24.2°C
[Diagram: LCD showing max temp 25.0°C, min temp 24.2°C with icons for Temp, Battery, Load]

4. Warning Code

Warning Code Event Indicator
21 Over-voltage from battery cell [21 Icon]
22 Low-voltage from battery cell [22 Icon]
23 Over-voltage from battery pack [23 Icon]
24 Low-voltage from battery pack [24 Icon]
25 Over current - charging [25 Icon]
26 Over current – discharging [26 Icon]
27 High temp. on charging battery cell [27 Icon]
28 High temp. on discharging battery cell [28 Icon]
29 Low temp. on charging battery cell [29 Icon]
30 Low temp. on discharging battery cell [30 Icon]
31 High temp. environment [31 Icon]
32 Low temp. environment [32 Icon]
33 High temp. on MOSFET [33 Icon]
35 Short circuit [35 Icon]
36 Over voltage on charger [36 Icon]

8.SPECIFICATIONS

Table 1 Line Mode Specifications

INVERTER MODEL EM-161A EM-252A EM-302A
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage 230Vac
Low Loss Voltage 170Vac± 7V (UPS)
90Vac± 7V (Appliances)
Low Loss Return Voltage 180Vac± 7V (UPS)
100Vac± 7V (Appliances)
High Loss Voltage 280Vac± 7V
High Loss Return Voltage 270Vac± 7V
Max AC Input Voltage 300Vac
Nominal Input Frequency 50Hz / 60Hz (Auto detection)
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
Output Short Circuit Protection Circuit Breaker
Efficiency (Line Mode) >95% (Rated R load, battery full charged)
Transfer Time 10ms typical (UPS);
20ms typical (Appliances)

Table 2 Inverter Mode Specifications

INVERTER MODEL EM-161A EM-252A/ EM-302A
Rated Output 2200VA/1800W 3200VA/3000W
Output Voltage Waveform Pure Sine Wave
Output Voltage Regulation 230Vac±5%
Output Frequency 50Hz
Peak Efficiency 94%
Overload Protection 5s@≥150% load; 10s@≥ 110% ~ 150% load
Surge Capacity 2* rated power for 5 seconds
Nominal DC Input Voltage 12Vdc 24Vdc
Cold Start Voltage 11.5Vdc 23.0Vdc
Low DC Warning Voltage @load < 50% 11.0Vdc 22.0Vdc
Low DC Warning Voltage @load >50% 10.5Vdc 21.0Vdc
Low DC Warning Return Voltage @ load < 50% 11.5Vdc 22.5Vdc
Low DC Warning Return Voltage @ load >50% 11.0Vdc 22.0Vdc
Low DC Cut-off Voltage @load < 50% 10.2Vdc 20.5Vdc
Low DC Cut-off Voltage @load >50% 9.6Vdc 20.0Vdc
High DC Recovery Voltage 14.5Vdc 29Vdc
High DC Cut-off Voltage 15.5Vdc 31Vdc
No Load Power Consumption <25W <35W

Table 3 Charge Mode Specifications

Utility Charging Mode EM-161A EM-252A/EM-302A
Charging Algorithm 3-Step
AC Charging Current (Max) 60Amp (@VI/p=230Vac) 60Amp (@VI/p=230V ac)
Bulk Charging Voltage Flooded 14.6
AGM / Gel Battery 14.1
29.2
28.2
Floating Charging Voltage 13.5Vdc 27Vdc

Charging Curve:

[Diagram: Charging curve showing Battery Voltage vs. Charging Current, with stages: Bulk (Constant Current), Absorption (Constant Voltage), Maintenance (Floating).]

MPPT Solar Charging Mode

INVERTER MODEL EM-161A EM-252A/EM-302A
Max. PV Array Power 2000W 3000W
Nominal PV Voltage 240Vdc
PV Array MPPT Voltage Range 55-430Vdc
Max. PV Array Open Circuit Voltage 450Vdc
Max Charging Current (Joint Utility and Solar Charging) 80Amp 80Amp

Table 4 General Specifications

INVERTER MODEL EM-161A EM-252A/EM-302A
Safety Certification CE/UKCA
Operating Temperature Range -10°C to 50°C
Storage temperature -15°C~60°C
Humidity 5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm 348 x 282 x 105mm 348 x 282 x 105mm
Net Weight, kg 5.0 5.5

9. TROUBLE SHOOTING

Problem LCD/LED/ Buzzer Explanation / Possible cause What to do
Unit shuts down automatically during startup process. LCD/LEDs and buzzer will be active for 3 seconds and then complete off. The battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. The battery voltage is fa too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Mains exist but the unit works in battery mode. Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped. Check if AC breaker is tripped and AC wiring is connected well.
Green LED is Flashing. Insufficient quality of AC power. (Shore or Generator) 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance)
When the unit is turned on, internal relay is switched on and off repeatedly. LCD display and LEDs are flashing Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. Fault code 07 Overload error. The inverter is overload 110% and time is up. Reduce the connected load by switching off some equipment.
Check if wiring is connected well and remove abnormal load.
Fault code 05 Output short circuited. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02 Temperature of internal converter component is over 120°C.
Fault code 03 Internal temperature of inverter component is over 100°C. Return to repair center.
Fault code 01 Battery is over-charged. The battery voltage is too high. Check if spec and quantity of batteries are meet requirements.
Fault code 06/ 58 Fan fault Replace the fan.
Fault code 08/09/53/ 57 Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) Reduce the connected load.
Return to repair center.
Fault code 51 Internal components failed. Return to repair center.
Fault code 52 Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Fault code 55 Bus voltage is too low. Output voltage is unbalanced.

Download and use of PC monitoring software

1. Scan the QR code, find "Power Monitor" and download it.

2. Use the communication cable in the accessories to connect the computer to the hybrid inverter and keep the inverter turned on.

3. Find and open “SolarPowerSystem.exe" in the package file,

You can use a computer to check the working status of the hybrid inverter.

Note: Computers with Win10 systems do not need to install a driver to use them. If you have a Win7 system, you need to install a USB driver file.

Models: EM-161A, EM-252A, EM-302A, EM-161A Hybrid Inverter Charger, EM-161A, Hybrid Inverter Charger, Inverter Charger, Charger

PDF preview unavailable. Download the PDF instead.

EM-161A EM-252A EM-302A EN v2.3 1 conv 1 ?v=1748571900 pdftk 1.41 - www tk.com itext-paulo-155 (itextpdf.sf.net-lowagie.com)

Related Documents

Preview EDECOA EM-302A Hybrid Inverter Installation and User Manual
Comprehensive guide for the EDECOA EM-302A hybrid inverter, covering installation, configuration, operation modes, LCD screen interpretation, error codes, and technical specifications. Learn how to optimize your solar energy system with this off-grid inverter.
Preview EDECOA EM-152A / EM-101A Hybrid Inverter Charger User Manual
Comprehensive user manual for the EDECOA EM-152A and EM-101A Hybrid Inverter Charger, covering installation, operation, features, specifications, and troubleshooting.
Preview EDECOA Hybrid Inverter/Charger User Manual
User manual for the EDECOA Hybrid Inverter/Charger, covering installation, operation, troubleshooting, and technical specifications for models EM-152A and EM-101A.
Preview EDECOA Hybrid Inverter/Charger User Manual (EM-352A, EM-654A)
This user manual provides detailed information on the EDECOA Hybrid Inverter/Charger, including safety instructions, operation, features, specifications, and troubleshooting for models EM-352A and EM-654A.
Preview EDECOA EM-152A / EM-101A Hybrid Inverter Battery Charger User Manual
Comprehensive user manual for the EDECOA EM-152A and EM-101A hybrid inverter and battery charger. Learn about installation, operation, features, specifications, and troubleshooting.
Preview EDECOA EM-454 Hybrid Inverter User Manual: Installation, Configuration & Troubleshooting
Comprehensive user manual for the EDECOA EM-454 hybrid solar inverter. Covers installation, LCD screen operation, configuration modes, error codes, troubleshooting, and technical specifications for 3800W and 6000W models.
Preview EDECOA EG-624B EG-422B Hybrid Inverter/Charger User Manual
User manual for the EDECOA EG-624B and EG-422B hybrid inverter/charger, detailing installation, operation, features, technical specifications, and troubleshooting.
Preview EDECOA EG-624B / EG-422B Hybrid Inverter/Charger User Manual
Comprehensive user manual for the EDECOA EG-624B and EG-422B hybrid inverter/chargers, covering installation, operation, safety, specifications, and troubleshooting.