EDECOA Hybrid Inverter / Charger
USER MANUAL
Models: EM-161A, EM-252A, EM-302A
Version: 2.3
1. ABOUT THIS MANUAL
This manual describes the operation and troubleshooting suggestions for EDECOA Hybrid Inverter EM-161A, EM-252A and EM-302A. Please read this manual carefully before operations. Keep this manual for future reference.
2. SAFETY INSTRUCTIONS
⚠️ WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION To reduce the risk of injury, charge only deep-cycle lead acid-type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- DO NOT disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charge, please follow the required specifications to select the appropriate cable size. It's very important to correctly operate this inverter/charger.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION for details.
3. INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/ solar charger priority, and acceptable input voltage based on different applications.
Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- Wi-Fi (Optional)
- Can connect to lithium battery
- Intelligent fan speed adjustment
Basic System Architecture
The following illustration shows the basic application for this inverter/charger. It also includes the following devices to have a complete running system:
- Generator or Utility.
- PV modules
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in the home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.
Diagram Description: A schematic shows a hybrid power system. A solar panel array is connected to a central unit labeled "EDECOA Hybrid Inverter/Charger". This unit is also connected to a "Generator OR Utility" source and "External Battery packs". The output of the central unit powers "Home Appliances" such as a fan, light bulb, computer, and television.
3. OPERATION
Power ON/OFF
Side view of unit
Once the unit has been properly installed and the batteries are connected, simply press the ON/OFF switch (located on the button of the case) to turn on the unit.
Operation and Display Panel
The operation and display panel, shown in the below chart, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
LCD display
LED Indicator Table:
LED Indicator | Messages |
---|---|
AC/INV (Green) | Solid On: Output is powered by utility in Line mode Flashing: Output is powered by battery or PV in battery mode |
CHG (Green) | Solid On: Battery is fully charged. Flashing: Battery is charging. |
FAULT (Red) | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
Function keys Table:
Function Keys | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Icons
Input Source Information:
- AC Icon: Indicates the AC input.
- PV Icon: Indicates the PV input.
- INPUT BATT TEMP Display: Indicate input voltage, input frequency, PV voltage, battery voltage, and charger current.
Configuration Program and Fault Information:
- Program Icon (8.8): Indicates the setting programs.
- Warning/Fault Icon (Error with number): Indicates the warning and fault codes. Warning: ERROR flashing with warning code. Fault: ERROR lighting with fault code.
Output Information:
- OUTPUT BATT LOAD Display: Indicate output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
Battery Information:
- Battery Icon: Indicates battery level by 0-24%, 25-49%, 50-74%, and 75-100% in battery mode and charging status in line mode.
In AC mode, it indicates battery charging status.
Battery Charging Status Table:
Status | Battery voltage | LCD Display |
---|---|---|
Constant Current mode/ Constant | <2V/cell | 4 bars will flash in turns. |
Voltage mode | 2 ~ 2.083V/cell | Bottom bar will be ON and the other three bars will flash in turns. |
Voltage mode | 2.083 ~ 2.167V/cell | Bottom two bars will be ON and the other two bars will flash in turns. |
Voltage mode | > 2.167 V/cell | Bottom three bars will be ON, and the top bar will flash. |
Floating mode, Batteries are fully charged | 4 bars will all be ON. |
In battery mode, it indicates battery capacity.
Battery Capacity Table:
Load Percentage | Battery Voltage | LCD Display |
---|---|---|
Load >50% | < 1.717V/cell | [Battery Icon: Empty] |
Load >50% | 1.717V/cell ~ 1.8V/cell | [Battery Icon: 1/4 full] |
Load >50% | 1.8 ~ 1.883V/cell | [Battery Icon: 1/2 full] |
Load >50% | > 1.883V/cell | [Battery Icon: 3/4 full] |
50%>Load>20% | < 1.817V/cell | [Battery Icon: Empty] |
50%>Load>20% | 1.817V/cell~1.9V/cell | [Battery Icon: 1/4 full] |
50%>Load>20% | 1.9 ~1.983V/cell | [Battery Icon: 1/2 full] |
50%>Load>20% | > 1.983V/cell | [Battery Icon: 3/4 full] |
Load<20% | <1.867V/cell | [Battery Icon: Empty] |
Load<20% | 1.867V/cell~1.95V/cel | [Battery Icon: 1/4 full] |
Load<20% | 1.95~2.033V/cell | [Battery Icon: 1/2 full] |
Load<20% | >2.033V/cell | [Battery Icon: 3/4 full] |
Load Information:
- OVERLOAD Icon: Indicates overload.
- Load Level Diagram: Indicates the load level as below.
[Diagram: Load level from 0-25%, 25-50%, 50-75%, 75-100% represented by increasing bar fill levels.]
Mode Operation Information:
- Utility Icon: Unit connected to the utility.
- BYPASS Icon: Unit connected to the PV panel. Load is supplied by utility power.
- [Arrow Icon]: Utility charger circuit is working.
- [Arrow Icon]: DC/AC inverter circuit is working.
Mute Operation:
- [Mute Icon]: Device muted.
Program Settings
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.
Setting Program Table:
Program | Description | Selectable option |
---|---|---|
00 | Exit setting mode | Escape [ESC Icon] |
01 | Output source priority: To configure load power source priority | SUB priority (default): Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility energy will supply power the loads at the same time. Battery provides power to the loads only when any one condition happens: Solar energy and utility are not available. Solar energy is not sufficient and utility is not available. SUB priority: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power the loads at the same time. Utility provides power to the load only when battery voltage drops to either low-level warning voltage or the setting point in program 12. |
02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 10A, 80A |
03 | AC input voltage range | Appliances (default) [RPL Icon] UPS [UPS Icon] |
04 | Power saving mode enable/disable | Saving mode disable (default) [SDS Icon] Saving mode enable [SEN Icon] |
05 | Battery type | AGM (default) [AGN Icon] User-Defined [USE Icon] Flooded [FLD Icon] |
06 | Auto restart when overload occurs | Restart disabled (default) [Rtd Icon] Restart enabled [Rte Icon] |
07 | Auto restart when over temperature occurs | Restart disabled (default) [Rtd Icon] Restart enabled [Rte Icon] |
08 | Output voltage | 220V (Default), 230V, 240V |
09 | Output frequency | 50Hz (default), 60Hz |
10 | BMS protocol | PAC, PLY |
11 | Maximum utility charging current | [Value in program 02] |
12 | Setting voltage point back to utility source when selecting "SBU priority". | EM-252A/EM-302A: 22.0V (Default), 25.5V EM-161A: 11.0V (default), 11.5V, 12.8V |
13 | Setting voltage point back to battery mode when selecting "SBU priority". | EM-252A/EM-302A: Battery fully charged 24V, 27V(default), 29V EM-161A: Battery fully charged 12.0V |
16 | Charger source priority: To configure charger source priority | Solar first [SOL Icon] Solar and Utility (default) [SNU Icon] Only Solar [SOL Icon] |
18 | Alarm control | Alarm on (default) [ALN Icon] Alarm off [ALF Icon] |
19 | Auto return to default display screen | Return to default display screen (default) [ESP Icon] Stay at latest screen [SEP Icon] |
20 | Backlight control | Backlight on (default) [LON Icon] Backlight off [LOF Icon] |
22 | Beeps while primary source is | Alarm on (default) [RON Icon] Alarm off [ROF Icon] |
23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disabled (default) [bYD Icon] Bypass enabled [bYE Icon] |
25 | Record Fault code | Record enabled [FEN Icon] Record disabled (default) [Fd5 Icon] |
26 | Bulk charging voltage (C.V voltage) | EM-161A default: 14.1V EM-252A/EM-302A default: 28.2V |
27 | Floating charging voltage | EM-161A default: 13.5V EM-252A/EM-302A default: 27.0V |
29 | Low DC cut-off voltage | EM-161A default: 10.5V 3KVA-24V default: 21.0V |
33 | Battery equalization | Battery equalization (default) [EEN Icon] Battery equalization disable [EdS Icon] |
34 | Battery equalization voltage | EM-161A default: 14.6V EM-252A/EM-302A default: 29.2V |
35 | Battery equalized time | 60min (default), 120min (default) |
36 | Battery equalized timeout | 60min (default), 120min (default) |
37 | Equalization interval | 30days (default) |
39 | Equalization activated immediately | Enable [REN Icon] Disable (default) [RdS Icon] |
Display Setting
The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, PV power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, CPU Version.
Selectable information Table:
Selectable information | LCD display |
---|---|
Input voltage/Output voltage (Default Display Screen) | Input Voltage=230V, output voltage=230V [Diagram: LCD showing input 230V, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
Input frequency | Input frequency=50Hz [Diagram: LCD showing input frequency 50.0Hz, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
PV voltage | PV voltage=60V [Diagram: LCD showing PV voltage 60V, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
PV power | MPPT charging power = 500W [Diagram: LCD showing PV power 500W, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
Charging current | AC and PV Charging current=50A [Diagram: LCD showing AC and PV charging current 50A, output 230V with icons for AC, PV, Utility, Bypass, Load, Solar, Battery] Charging current: 25A [Diagram: LCD showing charging current 25A, output 230V with icons for PV, Utility, Bypass, Load, Solar, Battery] AC Charging current=50A [Diagram: LCD showing AC charging current 50A, output 230V with icons for AC, Utility, Bypass, Load, Solar, Battery] |
Battery voltage/ output voltage | Battery voltage=25.5V, Output voltage=230V [Diagram: LCD showing battery voltage 25.5V, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
Output frequency | Output frequency=50Hz [Diagram: LCD showing output frequency 50.0Hz, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
Load percentage | Load percent=70% [Diagram: LCD showing load percentage 70%, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
Load in VA | When connected load is lower than 1kVA, load in VA will present xxx VA like below. [Diagram: LCD showing 350 VA, output 230V with icons for Utility, Bypass, Load, Solar, Battery] When load is larger than 1kVA (≥1KVA), load in VA will present x.x kVA like below. [Diagram: LCD showing 1.50 kVA, output 230V with icons for Utility, Bypass, Load, Solar, Battery] |
Load in Watt | When load is lower than 1kW, load in W will present xxx W like below. [Diagram: LCD showing 270 W, output 230V with icons for Utility, Bypass, Load, Solar, Battery] When load is larger than 1kW (≥1KW), load in W will present x.x kW like below. |
Battery voltage/DC discharging current | Battery voltage=25.5V, discharging current=1A [Diagram: LCD showing battery voltage 25.5V, discharging current 1A with icons for Utility, Bypass, Load, Solar, Battery] |
CPU version checking | CPU version 20 11 [Diagram: LCD showing CPU version 20 11 with icons for Utility, Bypass, Load, Solar, Battery] |
Operating Mode Description
Operation mode | Description | LCD display |
---|---|---|
Standby mode / Power saving mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output. *Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected. |
No output is supplied by the unit but it still can charge batteries. | Charging by utility and PV energy. [Diagram: Icons for Solar, Utility, Battery, Load] Charging by utility. [Diagram: Icons for Utility, Battery, Load] Charging by PV energy. [Diagram: Icons for Solar, Battery, Load] No charging. [Diagram: Icons for Battery, Load] |
Fault mode Note * Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on |
PV energy and utility can still charge batteries. | Charging by utility and PV energy. [Diagram: Icons for Solar, Utility, Battery, Load] Charging by utility. [Diagram: Icons for Utility, Battery, Load] Charging by PV energy. [Diagram: Icons for Solar, Battery, Load] No charging. [Diagram: Icons for Battery, Load] |
Line Mode | The unit will provide output power from the mains. It will also charge the battery at line mode. | Charging by utility and PV energy. [Diagram: Icons for Solar, Utility, Bypass, Load, Battery] Charging by utility. [Diagram: Icons for Utility, Bypass, Load, Battery] |
Battery Mode | The unit will provide output power from battery and PV power. | If "SUB priority" is selected as output source priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time. [Diagram: Icons for Solar, Utility, Bypass, Load, Battery] PV energy will supply power to the loads and charge battery at the same time. [Diagram: Icons for Solar, Battery, Load] Power from battery only. [Diagram: Icons for Battery, Load] |
4. Battery Equalization Description
Equalization function is added to charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have but up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.
How to Apply Equalization Function
You must enable the battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in the device by either one of the following methods:
- Check that program 5 is the user-defined or flooded mode.
- Check program 33 is enabled.
- Setting equalization in program 34 to program 37, that depends on your battery requirements. (detailed information in LCD Setting part).
- Active equalization immediately in program 39.
When to Equalize
In the float stage, when the setting equalization interval (battery equalization cycle) arrives, or equalization is active immediately, the controller will start to enter Equalize stage.
Equalize charging time and timeout
[Diagram: Charging curve showing stages: BULK, ABSORPTION, FLOAT, EQUALIZE, FLOAT, with voltage and time axes.]
In Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
5. Fault Reference Code
When fault occurs, ERROR icon will be on, please check the fault code below when it happens.
Fault Code | Fault Event | Icon |
---|---|---|
01 | Fan is locked when inverter is OFF | [01 Icon] |
02 | Over temperature | [02 Icon] |
03 | Battery voltage is too high | [03 Icon] |
04 | Battery voltage is too low | [04 Icon] |
05 | Output short circuited or over temperature is detected on internal converter components | [05 Icon] |
06 | Output voltage is too high | [06 Icon] |
07 | Overload time out | [07 Icon] |
08 | Bus voltage is too high | [08 Icon] |
09 | Bus soft start failed | [09 Icon] |
11 | Main relay failed | [11 Icon] |
13 | Solar charger stops due to high PV voltage | [13 Icon] |
51 | Over current/Surge | [51 Icon] |
52 | Bus voltage is too low | [52 Icon] |
53 | Soft start failure | [53 Icon] |
55 | Over DC voltage | [55 Icon] |
57 | Current sensor failure | [57 Icon] |
58 | Output voltage is too low | [58 Icon] |
6. Warning Indicator
When warning occurs, ⚠️ icon will be on, please check the fault code below when it happens.
Warning Code | Warning Event | Audible Alarm | Icon flashing |
---|---|---|---|
01 | Fan is locked when inverter is on. | Beep three times every second | [01 Icon] |
03 | Battery over-charged | Beep once every second | [03 Icon] |
04 | Low battery | Beep once every second | [04 Icon] |
07 | Overload | Beep once every 0.5 second | [07 Icon with LOAD/OVERLOAD diagram] |
10 | Output power derating | Beep twice every 3 seconds | [10 Icon] |
12 | Solar charger stops due to low battery. | [12 Icon] | |
13 | Solar charger stops due to high PV voltage | [13 Icon] | |
14 | Solar charger stops due to overload. | [14 Icon] |
7. Lithium Battery and The Interface
1. Long press ENTER key to enter the setting item and set the 05 item to lithium battery mode Lib (as shown in the figure below)
Communication port pin definition Table:
Pin number | Port definitions |
---|---|
1 | TX |
2 | RX |
3 | VCC |
4 | VCC |
5 | RS485A |
6 | RS485B |
7 | GND |
8 | GND |
2. Long press the ESC key to enter the lithium battery display interface (as shown in the picture below)
The initial display interface indicates the total battery voltage and remaining battery capacity
Press the DOWN key to indicate the data as below in turn
LCD data on the left Table:
LCD data on the left | LCD data on the right |
---|---|
Total battery voltage | Remaining battery capacity |
Battery charging current | Battery discharge current |
Battery capacity | Battery charge/discharge times |
BMS board temperature | MOSFET temperature on BMS board |
Detailed description of display interface for lithium battery
Total battery voltage, Battery residual capacity (Initial interface display)
Total battery voltage=50.5V Battery residual capacity=4%
[Diagram: LCD showing total battery voltage 50.5V, residual capacity 4% with icons for Battery, Load]
Battery charging current, Battery discharge current
Battery charging current= 0A Battery discharge current= 21A
[Diagram: LCD showing battery charging current 0A, discharge current 21A with icons for Input, Battery, Load]
Battery capacity; Battery charger/ discharge Times
Battery capacity= 100Ah Battery charger/discharge Times=4
[Diagram: LCD showing battery capacity 100Ah, charge/discharge times 4 with icons for Battery, Load]
BMS board temperature; MOSFET temperature of BMS board
Battery ambient temperature=25.9°C Battery MOS temperature=25.7°C
[Diagram: LCD showing battery ambient temp 25.9°C, MOS temp 25.7°C with icons for Temp, Battery, Load]
Maximum voltage of a single battery, Minimum voltage of a single battery
Maximum voltage of a single battery=3.20V Minimum voltage of a single battery= 3.10V
[Diagram: LCD showing max voltage 3.20V, min voltage 3.10V with icons for Battery, Load]
Maximum temperature of a single battery, Minimum temperature of a single battery
Maximum temperature of a single battery=25.0°C Minimum temperature of a single battery=24.2°C
[Diagram: LCD showing max temp 25.0°C, min temp 24.2°C with icons for Temp, Battery, Load]
4. Warning Code
Warning Code | Event | Indicator |
---|---|---|
21 | Over-voltage from battery cell | [21 Icon] |
22 | Low-voltage from battery cell | [22 Icon] |
23 | Over-voltage from battery pack | [23 Icon] |
24 | Low-voltage from battery pack | [24 Icon] |
25 | Over current - charging | [25 Icon] |
26 | Over current – discharging | [26 Icon] |
27 | High temp. on charging battery cell | [27 Icon] |
28 | High temp. on discharging battery cell | [28 Icon] |
29 | Low temp. on charging battery cell | [29 Icon] |
30 | Low temp. on discharging battery cell | [30 Icon] |
31 | High temp. environment | [31 Icon] |
32 | Low temp. environment | [32 Icon] |
33 | High temp. on MOSFET | [33 Icon] |
35 | Short circuit | [35 Icon] |
36 | Over voltage on charger | [36 Icon] |
8.SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL | EM-161A | EM-252A EM-302A |
---|---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac± 7V (UPS) 90Vac± 7V (Appliances) |
|
Low Loss Return Voltage | 180Vac± 7V (UPS) 100Vac± 7V (Appliances) |
|
High Loss Voltage | 280Vac± 7V | |
High Loss Return Voltage | 270Vac± 7V | |
Max AC Input Voltage | 300Vac | |
Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
Low Loss Frequency | 40±1Hz | |
Low Loss Return Frequency | 42±1Hz | |
High Loss Frequency | 65±1Hz | |
High Loss Return Frequency | 63±1Hz | |
Output Short Circuit Protection | Circuit Breaker | |
Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
Table 2 Inverter Mode Specifications
INVERTER MODEL | EM-161A | EM-252A/ EM-302A |
---|---|---|
Rated Output | 2200VA/1800W | 3200VA/3000W |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 94% | |
Overload Protection | 5s@≥150% load; 10s@≥ 110% ~ 150% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 12Vdc | 24Vdc |
Cold Start Voltage | 11.5Vdc | 23.0Vdc |
Low DC Warning Voltage @load < 50% | 11.0Vdc | 22.0Vdc |
Low DC Warning Voltage @load >50% | 10.5Vdc | 21.0Vdc |
Low DC Warning Return Voltage @ load < 50% | 11.5Vdc | 22.5Vdc |
Low DC Warning Return Voltage @ load >50% | 11.0Vdc | 22.0Vdc |
Low DC Cut-off Voltage @load < 50% | 10.2Vdc | 20.5Vdc |
Low DC Cut-off Voltage @load >50% | 9.6Vdc | 20.0Vdc |
High DC Recovery Voltage | 14.5Vdc | 29Vdc |
High DC Cut-off Voltage | 15.5Vdc | 31Vdc |
No Load Power Consumption | <25W | <35W |
Table 3 Charge Mode Specifications
Utility Charging Mode | EM-161A | EM-252A/EM-302A |
---|---|---|
Charging Algorithm | 3-Step | |
AC Charging Current (Max) | 60Amp (@VI/p=230Vac) | 60Amp (@VI/p=230V ac) |
Bulk Charging Voltage | Flooded 14.6 AGM / Gel Battery 14.1 |
29.2 28.2 |
Floating Charging Voltage | 13.5Vdc | 27Vdc |
Charging Curve:
[Diagram: Charging curve showing Battery Voltage vs. Charging Current, with stages: Bulk (Constant Current), Absorption (Constant Voltage), Maintenance (Floating).]
MPPT Solar Charging Mode
INVERTER MODEL | EM-161A | EM-252A/EM-302A |
---|---|---|
Max. PV Array Power | 2000W | 3000W |
Nominal PV Voltage | 240Vdc | |
PV Array MPPT Voltage Range | 55-430Vdc | |
Max. PV Array Open Circuit Voltage | 450Vdc | |
Max Charging Current (Joint Utility and Solar Charging) | 80Amp | 80Amp |
Table 4 General Specifications
INVERTER MODEL | EM-161A | EM-252A/EM-302A |
---|---|---|
Safety Certification | CE/UKCA | |
Operating Temperature Range | -10°C to 50°C | |
Storage temperature | -15°C~60°C | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Dimension (D*W*H), mm | 348 x 282 x 105mm | 348 x 282 x 105mm |
Net Weight, kg | 5.0 | 5.5 |
9. TROUBLE SHOOTING
Problem | LCD/LED/ Buzzer | Explanation / Possible cause | What to do |
---|---|---|---|
Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
No response after power on. | No indication. | 1. The battery voltage is fa too low. (<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
Mains exist but the unit works in battery mode. | Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected well. |
Green LED is Flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
|
When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. Check if wiring is connected well and remove abnormal load. |
Fault code 05 | Output short circuited. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
Fault code 02 | Temperature of internal converter component is over 120°C. | ||
Fault code 03 | Internal temperature of inverter component is over 100°C. | Return to repair center. | |
Fault code 01 | Battery is over-charged. The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | |
Fault code 06/ 58 | Fan fault | Replace the fan. | |
Fault code 08/09/53/ 57 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | Reduce the connected load. Return to repair center. |
|
Fault code 51 | Internal components failed. | Return to repair center. | |
Fault code 52 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
Fault code 55 | Bus voltage is too low. Output voltage is unbalanced. |
Download and use of PC monitoring software
1. Scan the QR code, find "Power Monitor" and download it.
2. Use the communication cable in the accessories to connect the computer to the hybrid inverter and keep the inverter turned on.
3. Find and open “SolarPowerSystem.exe" in the package file,
You can use a computer to check the working status of the hybrid inverter.
Note: Computers with Win10 systems do not need to install a driver to use them. If you have a Win7 system, you need to install a USB driver file.