Mark Fan Coil Technical Manual

Model: 0662570

Introduction

This technical manual provides detailed information for the Mark Fan Coil unit, distributed by Puravent. It covers identification, receiving, safety guidelines, operating limits, installation, hydraulic and electrical connections, maintenance, and troubleshooting.

Index of Contents

Identification of the Appliance

Each unit is identified with a label located inside the unit on the electrical control side. This label displays the manufacturer's data and the unit type.

Receiving the Appliance

Inspect each unit thoroughly before acceptance. Ensure the packaging is not damaged, bent, or broken. If a package is damaged, open it immediately and check the contents. Verify the chassis, panels, heat exchanging coil, condensate drain pan, filters, fan rotation, and any accessories. Do not refuse shipment if damage is found; instead, document all damages on the shipping document and take pictures.

General Warnings

This manual must always accompany the appliance. After unpacking, confirm there are no damages and the appliance matches your order. For significant damage, describe it on the carrier's shipping documents, take pictures, send a letter to the carrier immediately, and provide a copy to your dealer and/or manufacturer, including the model and serial number.

General Indications

A 230V single-phase electric connection and a hydraulic connection to a water chiller/boiler are required for proper operation. The unit is designed for heating and/or cooling of occupied rooms. All units are factory-tested before delivery. Repairs and maintenance must be performed by qualified specialists. Failure to follow manual instructions or unauthorized modifications can lead to dangerous situations and will invalidate the warranty. The manufacturer is not liable for damages caused by unauthorized changes, improper installation, or improper use.

Mandatory Safety Rules During Installation

Do not install the Fan Coil:

A bipolar safety switch, properly sized and easily accessible, must be installed to disconnect the appliance from the power supply (minimum 3 mm contact distance). The appliance must be properly earthed. ⚠️ Do not place flammable or dusty goods near the appliance. ⚠️ Do not remove internal labels.

Mandatory Safety Rules During Use, Maintenance, Repair

It is dangerous to:

Before any maintenance or repair:

If the Fan Coil is installed in very cold climates and will be inoperative for a long period, the hydraulic circuit must be completely emptied to prevent ice damage. If an external air damper is installed, cold air can cause ice formation and tube breakage. In such cases, mix glycol with the water in the hydraulic circuit. Coils are tested up to 3000 kPa (30 bar). Ensure the air filter is refitted correctly before restarting the unit after cleaning or replacement.

Operating Limits

For installations where temperatures can drop below 0°C, add glycol to the water according to the table provided. Ethylene glycol protects the circuit from freezing. The table shows the percentage of glycol needed for specific freezing temperatures. Water-glycol mixtures have varying mass and viscosity, affecting Fan Coil capacity. Glycol also acts as a corrosion inhibitor; its concentration should be checked at least annually.

Diagram Description: A line graph showing Temperature (°C) on the Y-axis (from -80°C to 20°C) and G-energy antifreeze SNF concentration (% in vol.) on the X-axis (from 0% to 100%). A specific point is marked at -23°C on the Y-axis, corresponding to approximately 40% concentration on the X-axis.

Waste Disposal

Packaging, consumables, and replaced parts must be disposed of according to local safety and environmental protection laws.

Technical Characteristics of the Fan Motor Minimum Cross Section of the Electric Supply Wires

Size FLE 100 130 150 180 250 300
Motor absorption (Ain) 1.17 1.44 1.51 0.98 2.65 2.28
Motor Power (Win) 154 200 221 165 400 390
Minimum cable section (mm²) 1.5 1.5 1.5 1.5 2.5 2.5

Data in the table are valid only for the fan motor and do not include accessories like valves or electric heaters.

Electric Heaters V230/1/50-60Hz

Tube: INOX AISI 304L – Fins: Fe/AlZn – Rules: DPR 547/55 – CENELEC EN60 – IEC 335.1 – CEI 61-50

Each power element (±5%) 700 W 1000 W 1200 W 1500 W 2000 W 2500 W 3000 W 4000 W 5000 W
Active length (L mm) 350 350 550 750 750 950 1150 1350 1550
Current absorbed (A) 3.1 4.5 5.5 6.6 9.0 11.0 13.0 18.0 21.7
Thermic charge (W/cm²) 4.3 6.0 4.4 4.0 5.3 5.1 5.0 5.7 6.2

Mechanical Installation

Choose an installation area that allows proper air circulation (incoming and outgoing). Avoid placing curtains or objects that obstruct the air outlet and return. Ensure adequate clearance around the unit for maintenance and cleaning. The Fan Coil must be mounted level to ensure proper operation and drainage. Use the supporting feet or hanging rods for leveling, checking on the unit casing. Do not use the coil or drain pan for leveling. Employ shock absorber supports to prevent noise and vibration transmission through walls and air ducts. Do not install where water dripping inside the appliance is possible. Ensure electrical and hydraulic connections are on opposite sides of the appliance before installation.

Hydraulic Connections

Proper hydraulic connections and water circulation ensure good operation, longevity, and limited energy consumption. Piping must be properly sized (diameter) and insulated to prevent condensate dripping and heat dissipation. Typically, the water inlet is at the bottom of the coil, and the outlet is at the top. If space is limited, valves may necessitate reversing the inlet/outlet positions. Allowed materials for condensate drain piping include PVC or steel. Use tape sealant to prevent leaks after connecting piping. Before installation, ensure the water circuit is filtered, free from scale or iron oxides. Water may require chemical treatment to prevent scale, corrosion, algae, or sludge. When connecting the heat exchanging coil, use two spanners and avoid damaging copper tubes. Fit two gate valves on the water circuit (inlet and outlet). Motorized water valves need adequate space for removal and must not be mounted upside down. For condensate drain piping, create a drain trap, ensure a minimum slope of 50 mm/m, avoid counterslopes, do not kink the pipe, and check the connection. After connecting, pour water into the drain pan to check the circuit. Perform hydrostatic pressure tests and air vent the coil, ensuring no dripping occurs. Avoid circuit checks just before holidays.

Drain Pan Discharge: General Note

A siphon must be installed on the drain line to prevent the fan from sucking obnoxious odors or bacteria from the drain system, which could lead to the proliferation of pathogenic germs and microorganisms, including "Legionella Pneumophila". A missing or incorrectly installed siphon can cause air to be sucked into the unit, prevent condensate drainage, and lead to flooding. The siphon must not be hermetically connected to the drain line to allow air locks to break. A siphon under positive pressure should not be connected to one under negative pressure. The drain line downstream of the siphon must have sufficient slope for condensate removal and be at least the same diameter as the unit drain connection. Drain piping can be steel, copper, or PVC. Improperly supported drain lines may deform, create air locks, and hinder drainage. Insulating the siphon and drain line helps prevent external condensation. Antifreeze should be added in winter. Beware of siphon water evaporation during shutdown periods; ensure siphons are always full. An inspection plug should be fitted in an accessible position. The condensate drain pan should be cleaned periodically to prevent scale, algae, and encrustations.

Drain in Positive Pressure:

Diagram Description: A schematic showing a U-shaped pipe (siphon) with labels T, p, S, H. The formulas provided are: T = 2p, S = T/2, H = T - S. Example: P = 400Pa = 40 mmwc. Calculated values: T = 80 mm, S = 40 mm, H = 40 mm.

Drain in Negative Pressure:

Diagram Description: Similar schematic to positive pressure, but with a negative pressure indication. The formulas provided are: T = -2p, S = T/2, H = T - S. Example: P = -250Pa = -25 mmwc. Calculated values: T = 50 mm, S = 25 mm, H = 25 mm.

Electrical Connections General Rules

Electrical connections must be made by qualified personnel only, adhering to local electrical and safety codes. A bipolar safety switch, properly sized and easily accessible, must be installed to disconnect power (minimum 3 mm contact distance). All connections must comply with local codes. The Fan Coil must be properly earthed before any other electrical connection. Refer to the unit's wiring diagram for wiring and installation details. Accessories not described in this manual require separate power supplies, protected by switches and fuses. Ensure the voltage is within the allowed limits (refer to "Operating Limits" and "Technical Characteristics"). The upstream electrical circuit must be adequately sized for the Fan Coil's current draw and other connected devices. Minimum wire cross-section is 1.5 mm². Auxiliary circuits (switches, controls, interlocks) require a minimum 1.5 mm² cross-section. Wire selection should limit current to 5 A/mm² and voltage drop to 3% between operating and non-operating states.

Motor Wiring

The Fan Coil features a terminal block on the internal side panel opposite the hydraulic connections. This block is ready for connection to a fan speed selector switch or thermostats, which are supplied as accessories. Connection details are shown in the accessory installation instructions. Ensure terminal screws are tightened securely after wire insertion to guarantee good electrical contact. Improperly tightened terminals can cause serious danger and fire risk.

Start-up Procedures

For installation or after any maintenance, perform the following checks before starting the unit:

Filter

The air filter removes foreign matter like dirt, soot, and pollen to prevent damage to the Fan Coil. It should be replaced annually, or more frequently in dusty environments. A dirty filter impairs efficiency by restricting airflow and can encourage bacterial growth. To clean the filter: remove it, vacuum it, or replace it if too dirty. Always refit the filter correctly after cleaning.

Condensate Drain Pan

Check the condensate drain pan before the cooling season. The pan and discharge hole can clog with scale; use appropriate chemical products for cleaning. Dirt accumulation may impair condensate evacuation, leading to water leakage. To clean: remove the pan, clean with fresh water, dry carefully, and refit.

Heat Exchanging Coil

If the air filter is clean, the coil requires no maintenance. Use a vacuum cleaner for light cleaning. For heavy dirt, use a stiff nylon brush between fins, being careful not to damage them. For persistent dirt or odors, consult a specialized technician for fan and fan motor cleaning and maintenance. Fan motors are permanently lubricated and require no lubrication. Annually, remove dust and dirt from the scroll and ensure the fan is securely fixed and balanced. Fan motors do not require maintenance.

Troubleshooting

The motor does not rotate at all, or does not rotate properly

The Fan Coil does not cool / heat properly

Water comes out from the unit

Wiring Diagram: PS_FLE: Brushless EC motor 0-100%

Diagram Description: A simplified wiring diagram showing connections for a Brushless EC motor. It includes inputs for SIGNAL (0-10Vdc, PWM), BY CUSTOMER, NEUTRAL, EARTH, and power supply (120V-240V). Components like FILTER BOX and CONTROL BOARD are indicated.

Manufacturer and Distributor Information

This technical data is not binding. The manufacturer reserves the right to introduce modifications for product improvement.

Mark Branches:

Distributor:

Puravent
Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
Call: 0845 6880112
Email: info@adremit.co.uk

Various certifications are displayed, including CE, EUROVENT CERTIFIED PERFORMANCE, ISO 9001, and others.

Models: FLE 070 EC, 0662570 Fan Coil, 0662570, Fan Coil, Coil

File Info : application/pdf, 12 Pages, 564.59KB

PDF preview unavailable. Download the PDF instead.

Technical-manual-Mark-Fan-Coil-decentralized-unit

References

FPDF 1.82

Related Documents

Preview MARK PinTherm Infra Connect Technical Manual
This technical manual provides comprehensive instructions for the MARK PinTherm Infra Connect, covering installation, operation, and technical specifications. Learn how to set up and utilize the device for optimal climate control.
Preview Mark 4-7 V2 Installation Manual
This document provides the installation manual for the Mark 4-7 V2, detailing the packing list and step-by-step assembly instructions.
Preview MARK Slot 2 Wall Direct/Indirect Pattern: Specifications and Ordering Guide
Comprehensive technical specifications and ordering guide for the MARK Slot 2 Wall Direct/Indirect Pattern LED luminaire. Details include fixture performance, dimensions, shielding options, integrated controls (nLight, nLight Air), sensor configurations, emergency lighting features, and warranty information.