Supplement to Installation, Operation, and Maintenance Manual for VALENT models including: Microprocessor Controller for Dedicated Outdoor Air System, Controller for Dedicated Outdoor Air System, Dedicated Outdoor Air System, Outdoor Air System, Air System

484755 Valent Heat-Cool Controller, Rev 3 December 2021

Valent

Valent Heat-Cool Only Control IOM Supplement

Resources | Valent

PDF Supplement Microprocessor Controller - Valent

4 HeatCool Only Controls for DOAS Third Party Responsibilities • Electric Preheat: When a preheat device is installed for energy recovery defrost, the third-party controller needs to ensure that the following conditions are met


File Info : application/pdf, 12 Pages, 207.74KB

PDF preview unavailable. Download the PDF instead.

valent heat-cool only control iom supp ?sfvrsn=28595f0a 10
Document 484755 Heat-Cool Only Controls for Dedicated Outdoor Air System
Supplement Microprocessor Controller
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Technical Support Call: 1-800-789-8550 Email: support@doas.com

Overview

This document is to be used in conjunction with the Microprocessor Controller for Dedicated Outdoor Air System Installation, Operation and Maintenance Manual (IOM). All safety information provided in that IOM pertains to Heat-Cool Only controls also.
Heat-Cool Only Overview
Heat-Cool Only is designed to allow third-party control of a packaged DX, split DX with remote condensers, or Heat Pump unit while maintaining the safeties of the refrigeration system and heating devices. To achieve this, the Heat-Cool Only controller is factory installed and factory commissioned. This controller is responsible for the operation of the refrigeration and heating components installed in the unit. The safety of the refrigeration system is assured by monitoring pressures and temperatures contained within the refrigeration circuit(s). The third party is required to control the following: supply and exhaust airflow, cooling or heating operation selection, dehumidification enable, temperature setpoints, and emergency shutdown.

control cabinet, as represented in the image below.
END DEVICES: End devices required for Heat-Cool Only operation are provided and installed in the unit for the sole purpose of operating the heat/cooling control system. Sensors required for the third-party controller operation are to be provided and installed by the third party. Additionally, the third-party control system may use additional end devices not provided by the factory. Please refer to the unit's submittal information for the exact unit configuration and selected options to determine factory provided end devices.
WARNING
Powering the third-party controller is the responsibility of the third party. The third party will supply and install a transformer to power their controller. This power cannot be taken from the control panel. The third-party device cannot be mounted in the electrical control panel of the unit.

Additionally, a third-party device that is field supplied and installed provides occupancy, temperature, and airflow monitoring. This third-party device interfaces to the Heat-Cool Only controller via a terminal strip in the

Third Party Controller

Terminal Strip

Heat-Cool Only Controller

Refrigeration & Heating
Components
Non-tempering Components

Heat-Cool Only Controls for DOAS 1

Table of Contents Overview . . . . . . . . . . . . . . . . . . . . . . 1 Third Party Responsibilities . . . . . . . . . . . . 3 Operation of Unit . . . . . . . . . . . . . . . . . . 6 Appendix
A: Terminal Strip Wiring . . . . . . . . . . . . . . 7 B: Gas Furnace Limitations. . . . . . . . . . . . . 8 C: Supply and Exhaust Airflow Connections. . . . 9 D: Outside Air Damper Airflow Connections . . . . 10 Our Commitment . . . . . . . . . . . . . Backcover
2 Heat-Cool Only Controls for DOAS

Third Party Responsibilities

Occupancy, temperature, airflow, and third-party device power with Heat-Cool Only are the responsibility of the third party through a third-party device. This control not only includes the timing of each occupied mode, but logic for enabling and modulating all non-refrigeration or heating components.
Occupancy
Scheduling and occupancy mode control are the responsibility of the third party.
Airflow

WARNING
When modulating the gas furnace heating capacity, it is recommended to maintain a maximum temperature rise and a minimum airflow for all units. The criteria must be met when controlling the staging and modulation of the gas furnaces in order to prevent improper combustion and damage to the unit.
Please see Appendix B ­ Heat-Cool Only Heating Limitations for minimum airflow specific to the unit size and furnace installed.

Maintaining the proper airflow by enabling and modulating the fans and dampers is the responsibility of the third-party controller.
During normal operation, airflow should continue over the unit's heat exchangers after removing the remote start command to the Heat-Cool Only controller. For units with variable speed compressors, the compressors may take up to two minutes to completely stop. Additionally, in heating mode, supply airflow should continue until the supply air temperatures drop below 80ºF to dissipate the heat remaining in the heating devices and prevent excessive component temperatures.
DAMPER POSITIONING: Dampers will need to be powered and a position signal provided, when the dampers are modulating. Prior to starting fans in the unit, the third party will ensure that there is an open path for airflow by confirming that the damper end switch is closed, when installed.

Please refer to the unit's submittal information for the exact gas furnace performance data.
- Gas Furnace Heat: When the unit is heating with a gas furnace, limit turndown to the minimum airflow based on the unit size or 50.0% of design airflow, whichever value is greater.
Please see Appendix B ­ Heat-Cool Only Heating Limitations for minimum airflow specific to the unit size and furnace installed.
· Exhaust fan: Exhaust fan modulation will need to maintain the building requirements.
Energy Recovery
Control of energy recovery equipment installed in the unit is the responsibility of the third party. A heat wheel with or without a VFD, or a face/bypass damper for a flat plate heat exchanger must be controlled to a thirdparty provided sensor.

FAN MODULATION: The enable and modulation signals are the responsibility of the third-party controller.
· Supply Fan: Supply fan modulation will need to follow these guidelines. The end switch signal must be received prior to the start of any fans in the unit when installed.
- Cooling or Heat Pump Heating: When the unit is operating in cooling mode or heat pump heating, the fan turndown must be limited to a minimum of 50% of the designed airflow to ensure the refrigeration system can adequately modulate to meet the desired temperature setpoints. Modulating below 50% of the designed airflow may result in loss of space temperature control and have a negative impact on the refrigeration and heating components.
- Electric Heat: Supply fan modulation must be limited to the minimum airflow requirements of the electric heater manufacturer. The minimum air flow required through a duct heater depends on the KW per square foot of face area for the highest capacity ON-OFF stage. In general, 500 FPM is adequate in most applications.

ENERGY WHEEL BYPASS DAMPER: When provided, the energy wheel bypass damper needs to be opened when exceeding design outdoor airflow rate in economizer mode by turning off the energy recovery wheel.
ENERGY RECOVERY DEFROST: Both forms of energy recovery must have a defrost sequence provided via the third-party controller.
· Energy Recovery Wheel: The third party will provide either an exhaust air temperature sensor or heat wheel pressure differential sensor/switch when pre-heat is not installed in the unit and the energy recovery device is used for exhaust air energy recovery. The exhaust air temperature must remain above 36°F or the differential pressure is less than 1.5"wc when the outside air temperature is below 10°F.
· Energy Core: The third party will provide an exhaust air temperature sensor when pre-heat is not installed in the unit and the energy recovery device is used for exhaust air energy recovery. The exhaust air temperature must remain above 36°F.

Please contact technical support to get more

information regarding specific products.

Heat-Cool Only Controls for DOAS 3

Third Party Responsibilities

· Electric Preheat: When a preheat device is installed for energy recovery defrost, the third-party controller needs to ensure that the following conditions are met prior to enabling the preheat device.
· Outside Air Damper >=30% open; AND · Supply Fan enabled; AND · Outdoor Air Temp < 10°F.
NOTE: Please see manufacturer's information for suggested minimum cfm for pre-heat.
Temperature
Heat-Cool Only Control requires the third party to make decisions based on operating conditions and setpoints to heat, cool, dehumidify, or economize. The third-party controller will communicate setpoints, via hard-wired 2-10 VDC signals, based on the operating mode:
· Cooling ­ Cooling Coil Setpoint

· Supply Temperature Limits: The heat-cool only controller also has high and low temperature limits. These limits are adjustable at the controller and will cause cooling or heating to be disabled. It is the responsibility of the third party to maintain the following conditions:
· Minimum Low Supply Temp Limit: 35°F · Maximum High Supply Temp Limit: 120°F
· Mode Switching ­ Cooling vs Heating: When heating and cooling are both installed in the unit, the third party is responsible for determining which mode of operation is required at any given time. The Cooling/Heating Control Mode input will be open for cooling or closed for heating. When the input changes state, the unit will shut down the current operation of the cooling or heating devices and switch to the other mode of operation after the mode switch timer expires.

· Dehumidifying ­ Cooling Coil and Supply Air Setpoints
· Heat Pump Heating ­ Supply Air Setpoint · Heating ­ Supply Air Setpoint
The third-party controller needs to control the amount of economizer and energy recovery capacity necessary to meet the current requirements, depending on the

· Mode Switching ­ Cooling vs Dehumidification: When a hot gas reheat coil is installed in the unit, the third party is responsible for determining when the hot gas reheat will control to the Supply Air Temperature Setpoint. The Cooling/Dehumidification Control Mode input will be open for cooling only or closed when reheat is desired.

equipment installed in the unit. Analog output signals are sent via the terminal strip that interfaces with the controller or directly to the end devices.
Please refer to the unit wiring schematics or see Appendix A ­ Terminal Strip Wiring for further information regarding control input types and terminal strip wiring.
· Cold Coil Temperature Control: The thirdparty controller will send a signal to control the compressors in the unit. This setpoint will range between 50ºF and 75ºF in cooling and dehumidification modes of operation.
· Supply Air Temperature Control: When the unit has a HGRH coil or heating, there will be a Supply Air Temperature Setpoint input for the third-party controller. This setpoint will range between 50°F and 95°F in all modes of operation. The HGRH valve and heating devices will control to this setpoint.

Digital Status
The Heat-Cool Only terminal strip provides the thirdparty controller with information from devices installed in the unit. The following information is available through those digital statuses.
OUTSIDE AIR DAMPER ACTUATOR END SWITCH: When installed, this status provides an indication that the outside air damper actuator has reached a specific open position.
CONDENSATE OVERFLOW SWITCH: This device, when installed, indicates when the condensate drain pan is full and further operation of the refrigeration system could cause an overflow of water in the pan.
ENERGY RECOVERY STATUS: When installed, the energy recovery device may have an indication back to the terminal strip that the device is rotating, or the bypass is open.

NOTE: A minimum setpoint of 60.0°F is advised in heating mode of a heat pump.

FILTER PRESSURE SWITCH: If a filter pressure switch or switches is installed, an indication back to the third-party indicates that the filters are dirty.

GLOBAL ALARM OUTPUT: The global alarm output is available on all Heat-Cool Only units. This status indicates that there is an alarm condition in the HeatCool Only controller.

4 Heat-Cool Only Controls for DOAS

Digital Commands

Third Party Responsibilities

EMERGENCY SHUTDOWN: This input is to remotely shutdown the unit during a fault condition. All heating or cooling operation will stop when this input is open. This input affects the Global Alarm status.

REMOTE START/STOP: This input is to remotely start or stop the refrigeration and heating control of the unit. This input will be closed for the unit to provide cooling or heating.

COOLING/DEHUMIDIFICATION CONTROL MODE: This input determines whether the unit is in cooling mode or dehumidification mode.

COOLING/HEATING CONTROL MODE: This input determines whether the unit is in cooling or heating mode.

Heat-Cool Only Controls for DOAS 5

Operation of Unit

All Modes

The following conditions are required for the third party to enable the unit to operate in any mode:

· Remote Start Input:

Closed

· Shutdown Input:

Closed

· Damper Positioning:

OAD/RAD End Switch Closed (when installed)**

· Supply Fan Status:

Closed

· Supply Fan Control:

Not below 50.0% of the full-load airflow for the unit**

**NOTE: These safety checks are the responsibility of the third-party controller and do NOT input to the controller.

Cooling

The following conditions are required for the third party to enable the unit and start compressors in cooling mode:

· Cooling/Dehumidification Control Input:

Cooling mode (Open)

· Cooling/Heating Control Input:

Cooling mode (Open)

· Outside Air Temperature:

> Cooling Ambient Lockout (55.0°F) (adj.)

· Cooling Coil Leaving Air Temp:

> Coil Low Temp Limit (42.0°F) (adj.)

· Refrigerant Pressure Switches:

Closed (Both High and Low)

· Supply Air Temperature:

> Minimum Low Supply Temp Limit (35.0°F)

· Cooling Coil Setpoint:

50 - 75°F scaled from 2-10vdc (Compressor staging)

Dehumidifying NOTE: Hot Gas Reheat must be installed in the unit to utilize this functionality.

The following conditions are required for the controller to enable a unit in dehumidification mode:

· Cooling/Dehumidification Control Input:

Dehumidification mode (Closed)

· Cooling/Heating Control Input:

Cooling mode (Open)

· Outside Air Temperature:

> Cooling Ambient Lockout (55.0°F) (adj.)

· Cooling Coil Leaving Air Temp:

> Coil Low Temp Limit (42.0°F) (adj.)

· Refrigerant Pressure Switches:

Closed (High and Low)

· Supply Air Temperature:

> Minimum Low Supply Temp Limit (35.0°F)

· Supply Air Setpoint:

50 - 95°F scaled from 2-10vdc (HGRH valve modulation)

· Cooling Coil Setpoint:

50 - 75°F scaled from 2-10vdc (Compressor staging)

Heating

The following conditions are required for the controller to enable a unit in heating mode:

· Heating/Cooling Control Mode:

Heating mode (Closed)

· Outside Air Temperature:

< Heating Ambient Lockout (80.0°F) (adj.)

· Supply Air Temperature:

< Maximum High Supply Temp Limit (120.0°F)

· Supply Air Setpoint Request:

50 - 95°F scaled from 2-10vdc

Heating - Heat Pump
The following conditions are required for the controller to enable a unit and start compressors in heating mode.

· Heating/Cooling Control Mode:

Heating mode (closed) (Heat Pumps Only)

· Outside Air Temperature:

< Heating Ambient Lockout (80.0°F) (adj.)

· Outside Air Temperature:

> ASHP Low Ambient Lockout (17ºF) (adj.) (ASHP only)

· Refrigerant Pressure Switches:

Closed (High and low)

· Supply Air Temperature:

< Maximum High Supply Temp Limit (120.0°F)

· Supply Air Setpoint Request:

50-95°F scaled from 2-10vdc

6 Heat-Cool Only Controls for DOAS

Appendix A: Terminal Strip Wiring
Third-Party Wiring
The following table/diagram is the terminal strip wiring of the terminal strip for Heat-Cool Only operation. This terminal strip is the wiring point for the third-party control's device. Please refer to the unit schematics for additional information.

Terminal 50C (2)
501 502 503 51C 511 512 60C (2) 601 602 603 604 605 606 70P (2) 701 702 703 704 80C (3) 801 802 803 804 805 90C (2) 901 (2) 902 903 904

Terminal Type
0.0-10.0 VDC 0.0-10.0 VDC 0.0-10.0 VDC
2.0-10.0 VDC 2.0-10.0 VDC
2.0-10.0 VDC 24 VAC 24 VAC 24 VAC 24 VAC 24 VAC
24 VAC 24 VAC 24 VAC 24 VAC
24 VAC 0.0-10.0 VDC 0.0-10.0 VDC 0.0-10.0 VDC

Description/Device Common
Supply Fan Speed Input Exhaust Fan Speed Input Energy Recovery Capacity Input Common from Controller Cooling Coil Temperature Setpoint Input Supply Air Temperature Setpoint Input
Common OA/RA Modulating Damper Signal
Damper Actuator Power Supply Fan Start Exhaust Fan Start
Energy Recovery Wheel Start Pre-Heater Enable
24 VAC Power from Unit Remote Start Input Shutdown Input
Cooling(0)/Dehumidification(1) Control Mode Cooling(0)/Heating(1) Control Mode Common
Global Alarm Output (Heat/Cool Alarms Only) OA Damper End Switch (100% OA Units) Condensate Overflow Switch Energy Recovery Status Filter Pressure Switch Common AFMS Power Supply Airflow Measuring Station Exhaust Airflow Measuring Station Outdoor Airflow Measuring Station

Third Party IO Type Common
Analog Command Analog Command Analog Command
Analog Command Analog Command
Common Analog Command Digital Command Digital Command Digital Command Digital Command Digital Command
Digital Command Digital Command Digital Command Digital Command
Common Digital Status Digital Status Digital Status Digital Status Digital Status
Common 24 VAC Analog Feedback Analog Feedback Analog Feedback

Heat-Cool Only Controls for DOAS 7

Appendix B: Gas Furnace Limitations
Supply fan modulation must be limited to the minimum airflow based on the unit size or 50% of design airflow, whichever value is greater. When modulating the gas furnace heating capacity, it is recommended to maintain a maximum temperature rise and a minimum airflow for all units.

WARNING

The following criteria must be met when controlling the staging and modulation of the gas furnaces to prevent improper combustion and damage to the unit. The airflow reduction is only allowed if the supply air temperature does not exceed the max temp rise listed below. The supply air temp must be monitored, and the furnace must be modulated to prevent over-firing of the furnace at low airflows.

1. In the table below, locate the unit casing size, the correct furnace MBH, and the airflow supply direction for the minimum airflow in CFM.
2. All gas furnaces must be limited to the greater of the following: a. minimum airflow in CFM; OR b. 50% of design airflow.
3. The third-party controls will send a 2-10VDC signal to control to a supply air temperature setpoint

between 50.0°F (10.0°C) and 95.0°F (35.0°C) during all modes of operation.
4. The third-party controls must have a high supply temperature limit of 120.0°F (48.8°C) that shuts down all heating sources within the unit when the supply air temperature is greater than or equal to this high supply temp limit.
5. Minimum Temp Rise of 20.0°F for all furnaces.

Unit

Furnace

Bottom Discharge

Side Discharge

CASING SIZE

MBH

MAX TEMP RISE

MIN AIRFLOW CFM

MAX TEMP RISE

MIN AIRFLOW CFM

100

100.0°F

741

60.0°F

1,235

VPR-110

150

100.0°F

1,111

60.0°F

1,852

200

100.0°F

1,481

60.0°F

2,469

200

100.0°F

1,481

60.0°F

2,469

250

100.0°F

1,852

60.0°F

3,086

VPR-210

300

100.0°F

2,222

60.0°F

3,704

350

100.0°F

2,593

60.0°F

4,321

400

100.0°F

2,963

60.0°F

4,938

400

100.0°F

2,963

60.0°F

4,938

500

100.0°F

3,704

60.0°F

6,173

VPR-310

600

100.0°F

4,444

60.0°F

7,407

700

100.0°F

5,186

60.0°F

8,642

800

100.0°F

5,926

60.0°F

9,877

VPR-352 VX-352 VXE-352

600 800 1000 1200

100.0°F 100.0°F 100.0°F 100.0°F

4,444 5,926 7,407 8,889

60.0°F 60.0°F 60.0°F 60.0°F

7,407 9,877 12,346 14,815

75

100.0°F

556

100.0°F

556

VX-12

100

100.0°F

741

100.0°F

741

150

100.0°F

1,111

100.0°F

1,111

200

100.0°F

1,481

100.0°F

1,481

100

100.0°F

741

100.0°F

741

VX-112

200

100.0°F

1,481

100.0°F

1,481

300

100.0°F

2,222

100.0°F

2,222

300

100.0°F

2,222

100.0°F

2,222

VX-212

400

100.0°F

2,963

100.0°F

2,963

500

100.0°F

3,704

100.0°F

3,704

600

100.0°F

4,444

100.0°F

4,444

VX-312

800 1000

100.0°F 100.0°F

5,926 7,407

100.0°F 100.0°F

5,926 7,407

1200

100.0°F

8,889

100.0°F

8,889

8 Heat-Cool Only Controls for DOAS

Appendix C: Supply and Exhaust Airflow Calculations If airflow monitoring for the outside air damper is installed it could be one of two types of airflow. Each type has their own calculations and/or setup.
Supply and Exhaust Fan Models
The following table shows the available models for the supply and exhaust fan blades installed in a unit and the corresponding K Factor for the fan blade. The third party needs to know the model number of the fan, how many fans are installed, and whether the airflow monitoring station was purchased with the supply and/or exhaust fans.

Manufacturer Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Greenheck Ziehl-Abegg Ziehl-Abegg Ziehl-Abegg Ziehl-Abegg

Supply and Exhaust Fan Models

Model Number

Fan Blade Material Fan Blade Diameter

QEP/APM15

Aluminum

15"

QEP/APM16

Aluminum

16"

QEP/APM 18

Aluminum

18"

QEP/APM 20

Aluminum

20"

QEP/APM 24

Aluminum

24"

APD280

Aluminum

280mm/11"

APD315

Aluminum

315mm/12.5"

APD355

Aluminum

355mm/14"

APD400

Aluminum

400mm/16"

APD450

Aluminum

450mm/18"

APD500

Aluminum

500mm/20"

APD560

Aluminum

560mm/22"

APD630

Aluminum

630mm/25"

PRM-450

Aluminum

450mm/18"

PRM-560

Aluminum

560mm/22"

PDL-355

Aluminum

355mm/14"

ER35C

Steel

350mm/14"

ER45C

Steel

450mm/18"

ER50C

Steel

500mm/20"

ER56C

Steel

560mm/22"

K Factor 1296 1537 1888 2253 3334 739 936 1198 1479 1956 2377 3089 3838 1899 2975 1160 1133 1844 2359 2883

Supply and Exhaust Fan Airflow Measurement
The third-party controller can use the transducer's signal from the supply fan and/or from the exhaust fan and the airflow formula to determine the amount of current airflow.
FORMULA: CFM = k * (P)
P = Differential Pressure (0.0-30.0 in. wc scaled from 0.0 to 10.0 VDC reading from transducer) k = K Factor (from table) * # of Fans = Square Root
NOTE: The supply and exhaust airflow will be calculated separately. Only include the fans of the same type in the calculation.

Heat-Cool Only Controls for DOAS 9

Appendix D: Outside Air Damper Airflow Calculations If airflow monitoring for the outside air damper is installed it could be one of two types of airflow. Each type has their own calculations and/or setup.
Outside AMD
The following table shows the unit casing and tonnage along with the model of the AMD-23 that would be used with the optional purchase of airflow monitoring of OAD. Select the proper Supply CFM Range to determine the values to use in the calculation. The values are also available on the AMD.
NOTE: The operating range for the AMD damper is 300 to 2000 fpm. Airflows outside of the operating range may not properly register

Unit Casing Supply CFM Range
Area K Factor M Value Transducer Range

110 < 2700 1.75 ft2 2699 0.477 0 ­ 0.5"wc

110 > 2700 2.33 ft2 2697 0.477 0 ­ 1"wc

Outside AMD

210

210

< 5100

> 5100

3.33 ft2

4.72 ft2

2716

2714

0.477

0.477

0 ­ 0.5"wc 0 ­ 1"wc

310 < 8300 5.43 ft2 2748 0.477 0 ­ 0.5"wc

310 > 8300 7.67 ft2 2747 0.477 0 ­ 1"wc

352 < 13700 9.17 ft2
2813 0.477 0 ­ 0.5"wc

352 > 13700 12.22 ft2
2812 0.477 0 ­ 0.5"wc

Outside Air Damper Airflow Measurement
The third-party controller can use the transducer's signal from the AMD for the airflow formula to determine the amount of current airflow through the OAD.
FORMULA: CFM = A * K * (P)M
A = Area K = K Value P = Pressure M = M Value

GreenTrol Airflow Monitoring

The GreenTrol® airflow monitoring station measures airflow using advanced thermal dispersion technology. An integral LCD display provides a local indication of airflow measurement and device configuration. The GreenTrol also accepts up to two airflow probes for averaging.

GreenTrol Airflow Monitor functions:

· LCD readout of measured airflow · Dual airflow probe averaging

ANALOG OUTPUTS: The airflow monitoring controller has two configurable analog outputs that transmit airflow, temperature, or PID control. They can be configured for one of three analog output ranges: 0-10VDC, 0-5VDC, and 2-10VDC. The controller has been factory configured to use analog output 1 for transmitting outdoor airflow rate and analog output 2 for outdoor air temperature. The airflow monitoring output is wired to the customer terminal strip for Heat-Cool Only controls. See the technical manual for the airflow controller provided with the unit for instructions on configuring the analog outputs and using the Field Calibration Wizard.

FORMULA: Calculating airflow based on the analog output signal:

Airflow = (Signal Voltage-Minimum Voltage)

Full Scale Airflow

Maximum Voltage-Minimum Voltage

10 Heat-Cool Only Controls for DOAS

Heat-Cool Only Controls for DOAS 11

Contact Us

Contact Us / More Information

Technical Support and Service 800-789-8550 support@doas.com

Valent Dedicated Outdoor Air Systems 60­28th Avenue North Minneapolis, MN 55411 Main: 612-877-4800

More Information
Unit Schematics For configuration and connection questions, see the schematics that shipped with your unit. They can typically be found attached to the main control panel door.

© 2021 Valent Continuous product improvement is a policy of Valent; therefore, product functionality and specifications are subject to change without notice. For the most recent product information visit the product website.

Valent Heat-Cool Controller
Part number: 484755 Rev. 3 December 2021


Adobe PDF Library 16.0.3

Related Documents

Preview Valent Heat-Cool Only Controls for Dedicated Outdoor Air Systems: Supplement Microprocessor Controller
This document provides supplemental information for the Valent Heat-Cool Only Controller for Dedicated Outdoor Air Systems. It details third-party responsibilities, operational modes, wiring, and airflow calculations, serving as a guide for integrating third-party control systems with Valent's HVAC solutions.
Preview Valent DOAS Microprocessor Controller Reference Guide
A comprehensive reference guide for the Valent DOAS Microprocessor Controller, detailing its features, operation, and control sequences for dedicated outdoor air systems.
Preview Valent Dedicated Outdoor Air Systems Datasheet
Datasheet detailing Valent's Dedicated Outdoor Air Systems (DOAS), including model specifications, features, and dimensions for VX, VXE, and VXC casings.
Preview Valent VX Dedicated Outdoor Air Systems for Contractors
Discover the Valent VX packaged dedicated outdoor air systems, designed for high outdoor air applications. Learn about simple start-ups, short lead times, affordable quality, robust design, and detailed specifications.
Preview Valent DOAS Products: Robust, Efficient, and Reliable Air Handling Units
Explore Valent's range of Dedicated Outdoor Air Systems (DOAS) units, featuring robust designs, efficient controls, and reliable performance for conditioning 100% outdoor air. Learn about cooling, heating, and energy recovery options, capacities, and product data.
Preview Valent RTU Microprocessor Controller Reference Guide
This comprehensive reference guide details the Valent RTU v1.1 Microprocessor Controller for rooftop units. It covers features, sequences of operation, user interface, and advanced functionalities for efficient HVAC system management.
Preview Valent VX/VXE/VXC Dedicated Outdoor Air Unit Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Valent VX, VXE, and VXC Dedicated Outdoor Air Units. Covers safety information, product overview, subassemblies, installation procedures, service clearances, and technical specifications.
Preview Valent Dedicated Outdoor Air Systems Datasheet
Datasheet for Valent Dedicated Outdoor Air Systems (DOAS) designed for 100% outdoor air applications, detailing features, specifications, and dimensions for various models.