Valent Dedicated Outdoor Air Systems

Introduction

Valent Dedicated Outdoor Air Systems are designed for 100% outdoor air applications. Valent was a pioneer in specializing in high outdoor air units, offering robust and highly configurable designs suitable for various projects. The systems are supported by Valent's extensive experience in high outdoor air applications, leading to high-performing solutions and valuable application expertise. Key design features include the use of quality components for increased unit longevity, injected foam casings for improved thermal performance, and pre-painted cabinets to reduce environmental wear and tear. Valent also provides dedicated support, aiming to reduce the need for post-sale service through quality products and offering product and selection support during the design process. End-of-line testing is conducted to reduce installation time.

Models shown include the Valent VX-352 and Valent VX-12.

Valent Units at a Glance

The following table provides a comparison of Valent VX, VXE, and VXC casing units across various specifications:

CategoryVX, VXE & VXC CASING
12112212312352
AIRFLOW
Minimum (cfm)5008002,2503,7503,900
Maximum (cfm)2,5006,5009,50016,00018,000
COOLING TYPE
Packaged, air cooled (Tons)35152530
4717.53040
510204050
612.5255060
71530-70
Chilled water (Circuits)11122
Air source heat pumpOptionOptionOptionNot availableNot available
No coolingOptionOptionOptionOptionOption
COOLING COMPONENTS
Inverter scroll compressorStandardStandardStandardStandardStandard
Modulating hot gas reheatOptionOptionOptionOptionOption
Lead EC modulating condensing fansStandardStandardStandardStandardStandard
All EC modulating condensing fansNot applicableOptionOptionOptionOption
INDIRECT GAS FURNACE
Minimum (MBh)75100300600600
Maximum (MBh)2003005001,2001,200
Turndown (NG)Up to 16:1Up to 16:1Up to 16:1Up to 16:1Up to 10:1
Turndown (LP)Up to 16:1Up to 16:1Up to 16:1Not availableUp to 6:1
ELECTRIC HEAT
Minimum (kW)415353550
Maximum (kW)6060120230200
Air source heat pumpNot availableOptionOptionNot availableNot available
Hot waterOptionOptionOptionOptionOption
Steam coilNot availableOptionOptionOptionOption
OTHER HEAT
Hot waterOptionOptionOptionOptionOption
Steam coilNot availableOptionOptionOptionOption

Notes for the table above:

Energy Recovery, Duct Connections, Controls, Construction, and Certification

The following table details features related to Energy Recovery, Duct Connections, Controls, Construction, and Certification for Valent units:

CategoryVX, VXE & VXC CASING
12112212312352
ENERGY RECOVERY
Full width wheel PolymerNot availableOptionOptionOptionOption
Full width wheel AluminumNot availableOptionOptionOptionOption
Enthalpy core PolymerNot availableOptionOptionNot availableNot available
Enthalpy core FiberNot availableOptionOptionNot availableNot available
DUCT CONNECTIONS
Bottom supply/ returnStandardStandardStandardStandardStandard
Side supplyOptionOptionOptionOptionOption
Side returndNot availableOptionOptionOptionOption
End returneOptionOptionOptionOptionOption
CONTROLS
Full controlsStandardStandardStandardStandardStandard
DamperOptionOptionOptionOptionOption
Heat-cool onlyStandardStandardStandardStandardStandard
Web user interfaceStandardStandardStandardStandardStandard
FanOptionOptionOptionOptionOption
CONSTRUCTION
Injected foam insulation2" double-wall R-132" double-wall R-132" double-wall R-132" double-wall R-132" double-wall R-13
ExteriorGray prepaintedGray prepaintedGray prepaintedGray prepaintedGray prepainted
InteriorGalvanizedGalvanizedGalvanizedGalvanizedGalvanized
CERTIFICATION
AHRI 1060N/ACompliantCompliantCompliantCompliant
ASHRAE 90.1-2019CompliantCompliantCompliantCompliantCompliant
DOE 2023CompliantCompliantCompliantCompliantCompliant

Additional Notes:

Dimensions and Weights

The following diagrams illustrate the unit configurations:

Diagram 1: Elevations with and without energy recovery wheel

Shows a side view of the unit with labels for Length (Ls), Width (W), and Height (H). It depicts variations with and without an energy recovery wheel, indicating different length dimensions (Lw, Lc) and a hood length (A).

Diagram 2: Elevations with enthalpy core heat exchangers

Shows a side view of the unit with labels for Length (Ls), Width (W), and Height (H). It depicts variations with enthalpy core heat exchangers, indicating different length dimensions (Lc) and a hood length (A), as well as a condenser width (B).

The table below provides detailed dimensions (inches) and weights (pounds) for various Valent unit models:

CASINGHeight (H)Width (W)Lengtha (Ls)Length with wheel (Lw)Length with core (Lc)Hood length (A)Condenser width (B)Nominal weight (pounds)
Bottom returnSide returnBottom returnSide returnVXVXEVXC
VX-1258.144.082.2cN/AN/AN/AN/A22.3N/A1,180N/AN/A
VX-11259.352.598.6a149.5a180.5N/A22.1/40.0e30.12,7003,4003,800
VX-21272.568.2109.0a163.2a197.3N/A27.1/38.0e30.14,5005,1005,675
VX-312101.398.0155.2d247.9276.9N/AN/A39.0bN/A6,5008,000N/A
VX-35299.596.0185.0263.0307.0308.0353.045.3/46.0eN/A7,95010,45012,000

Notes for the Dimensions and Weights table:


File Info : application/pdf, 4 Pages, 671.00KB

PDF preview unavailable. Download the PDF instead.

valent products datasheet

References

Adobe PDF Library 17.0

Related Documents

Preview Valent DOAS Products: Outdoor Air Experts
Explore Valent's range of Dedicated Outdoor Air Systems (DOAS) designed for robust performance, efficient operation, and dedicated support. Learn about their features, capacities, and applications.
Preview Valent DOAS Units: Technical Specifications and Features | VX Series
Comprehensive datasheet for Valent's Dedicated Outdoor Air Systems (DOAS) VX, VXE, and VXC series. Details airflow, cooling, heating, energy recovery, dimensions, weights, and certifications for 100% outdoor air solutions.
Preview Valent DOAS Products: Robust, Efficient, and Reliable Air Handling Units
Explore Valent's range of Dedicated Outdoor Air Systems (DOAS) units, featuring robust designs, efficient controls, and reliable performance for conditioning 100% outdoor air. Learn about cooling, heating, and energy recovery options, capacities, and product data.
Preview Valent Dedicated Outdoor Air Systems Datasheet
Datasheet for Valent Dedicated Outdoor Air Systems (DOAS) designed for 100% outdoor air applications, detailing features, specifications, and dimensions for various models.
Preview Valent VX/VXE Dedicated Outdoor Air Unit Installation, Operation, and Maintenance Manual
This manual details the installation, operation, and maintenance of Valent's VX/VXE Dedicated Outdoor Air Units. It covers product overview, safety, subassemblies, installation procedures, clearances, and electrical/gas connections for various models.
Preview Valent VX/VXE/VXC Dedicated Outdoor Air Unit Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Valent VX, VXE, and VXC Dedicated Outdoor Air Units. Covers safety information, product overview, subassemblies, installation procedures, service clearances, and technical specifications.
Preview Valent VX Dedicated Outdoor Air Systems for Contractors
Discover the Valent VX packaged dedicated outdoor air systems, designed for high outdoor air applications. Learn about simple start-ups, short lead times, affordable quality, robust design, and detailed specifications.
Preview Valent Energy Recovery for High Outdoor Air Applications
Valent offers advanced energy recovery solutions for high outdoor air applications, focusing on efficiency, IAQ, and low maintenance. Explore enthalpy wheels and enthalpy cores for optimized HVAC performance.