Valent Dedicated Outdoor Air Systems

Designed for 100% Outdoor Air

Introduction

Valent was one of the first to specialize in high outdoor air units, which have unique design challenges like managing high humidity loads. Valent's DOAS designs are highly configurable to fit almost any project.

Valent DOAS Units at a Glance

Key Features

Specifications Overview

Category VX, VXE & VXC CASING
12 112 212 312 412
AIRFLOW
Minimum (cfm) 500 800 2,250 3,750 8,000
Maximum (cfm) 2,500 6,500 12,500 18,000 29,200
COOLING TYPE
Packaged, air cooled (Tons) 3, 4, 5, 6, 7 5, 7, 10, 12.5, 15 15, 17.5, 20, 25, 30 25, 30, 40, 50, 60 50, 60, 70, 80, 90
COOLING COMPONENTS
Chilled water (Circuits) 1 1 1 2 2
Air source heat pump Coming soon Option Option Not available Not available
No cooling Option Option Option Option Option
Lead inverter scroll compressor Standard Standard Standard Standard Standard
Modulating hot gas reheat Option Option Option Option Option
Lead EC modulating condensing fans Standard Standard Standard Standard Standard
All EC modulating condensing fans Not applicable Option Option Option Option
INDIRECT GAS FURNACE
Minimum (MBh) 75 100 300 600 800
Maximum (MBh) 200 300 600 1,200 2,000
Turndown (NG) Up to 16:1 Up to 16:1 Up to 16:1 Up to 16:1 Up to 10:1
Turndown (LP) Up to 16:1 Up to 16:1 Up to 16:1 Up to 16:15 Up to 50:1
ELECTRIC HEAT
Minimum (kW) 5 15 35 40 80
Maximum (kW) 60 60 120 230 230
Air source heat pump Coming soon Option Option Not available Not available
Hot water Option Option Option Option Coming soon
Steam coil Not available Option Option Option Not available
OTHER HEAT
ENERGY RECOVERY
Full width wheel Polymer Option Option Option Option Coming soon
Full width wheel Aluminum Not available Option Option Option Coming soon
Enthalpy core Polymer Not available Option Not available Not available Not available
Enthalpy core Fiber Not available Option Not available Not available Not available
DUCT CONNECTIONS
Bottom supply/return Standard Standard Standard Standard Standard
Side supply Option Option Option Option Option
Side return Not available Option Option Option Option
End return Option Option Option Option Option
CONTROLS
Full controls Standard Standard Standard Standard Standard
Heat-cool only Option Optiond Optiond Option Option
Web user interface Standard Standard Standard Standard Standard
MONITORING
Damper Option Option Option Option Option
Fan Option Option Option Option Option
CONSTRUCTION
Injected foam insulation 2" double-wall R-13 2" double-wall R-13 2" double-wall R-13 2" double-wall R-13 2" double-wall R-13
Exterior Gray prepainted Gray prepainted Gray prepainted Gray prepainted Gray prepainted
Interior Galvanized Galvanized Galvanized Galvanized Galvanized
CERTIFICATION
AHRI 1060 Compliant Compliant Compliant Compliant Compliant
ASHRAE 90.1-2019 Compliant Compliant Compliant Compliant Compliant
DOE 2023 Compliant Compliant Compliant Compliant Compliant

Refer to Valent CAPS® selection software or the Valent Mechanical IOMs for additional detail.

a Based on packaged DX cooling, indirect gas heating, 100% outdoor air, 1.5 in. wg supply external and 0.5 in. wg return air static pressure. Airflows will vary based on unit configuration.

b LP furnaces available on 600 and 800 mbh furnaces only.

c Max kW is dependent on unit voltage.

d Not available with the fiber core.

Dimensions and Weights

Diagrams illustrating unit elevations with and without energy recovery wheels, and with enthalpy core heat exchangers are available in the original document.

CASING Height (in) Width (in) Lengtha (in) Length with wheel (in) Length with core (in) Hood length (in) Condenser width (in) Nominal weight (lbs)
Lw Ls Lw Ls VX VXE VXC
VX-12 58.1 44.0 82.2b 125.0 N/A N/A N/A 22.3 N/A 1,180 1,780 N/A
VX-112 59.3 52.5 98.6a 149.5a 180.5 180.5 N/A 22.1/40.0b 30.1 2,700 3,400 3,800
VX-212 72.5 68.2 109.0a 163.2a 197.3 197.3 N/A 27.1/38.0b 30.1 4,500 5,100 5,675
VX-312 101.3 98.0 155.2d 247.9 276.9 N/A N/A 39.0b N/A 7,750 9,600 N/A
VX-412 101.8 100.9 283.6/249.4e N/A N/A N/A N/A 36.25 N/A 11,600g N/A N/A

a Powered exhaust units with no energy recovery, whether bottom or side return, have the same length as the wheel units with bottom return. This applies to the VX-112 and VX-212.

b If the VXE-312 has an exhaust fan, the exhaust blower bump-out will have a length of 48.4 inches.

c If the VX-12 has an indirect gas furnace, the furnace bump-out will have a length of 13.3 inches.

d If the VX-312 has powered exhaust but no energy recovery, the length will be 203.6 inches for bottom return and 222.7 inches for side return.

e Longer dimension reflects VXC hood length.

f Longer dimension reflects 90-100 ton configurations, shorter dimension reflects 50-80 ton configurations. Units without cooling will have a length of 155 inches.

g If the VX-412 is configured without cooling, the nominal weight will be 6,300 pounds. VX-412 50-80 ton configurations will have a nominal weight of 10,325 pounds.

PDF preview unavailable. Download the PDF instead.

valent products datasheet ?sfvrsn=9a9908c0 22 Adobe PDF Library 17.0

Related Documents

Preview Valent DOAS Units: Technical Specifications and Features | VX Series
Comprehensive datasheet for Valent's Dedicated Outdoor Air Systems (DOAS) VX, VXE, and VXC series. Details airflow, cooling, heating, energy recovery, dimensions, weights, and certifications for 100% outdoor air solutions.
Preview Valent DOAS Products: Outdoor Air Experts
Explore Valent's range of Dedicated Outdoor Air Systems (DOAS) designed for robust performance, efficient operation, and dedicated support. Learn about their features, capacities, and applications.
Preview Valent VX/VXE Dedicated Outdoor Air Unit Installation, Operation, and Maintenance Manual
This manual details the installation, operation, and maintenance of Valent's VX/VXE Dedicated Outdoor Air Units. It covers product overview, safety, subassemblies, installation procedures, clearances, and electrical/gas connections for various models.
Preview Valent VX Dedicated Outdoor Air Systems for Contractors
Discover the Valent VX packaged dedicated outdoor air systems, designed for high outdoor air applications. Learn about simple start-ups, short lead times, affordable quality, robust design, and detailed specifications.
Preview Valent Dedicated Outdoor Air Systems Datasheet
Datasheet detailing Valent's Dedicated Outdoor Air Systems (DOAS), including model specifications, features, and dimensions for VX, VXE, and VXC casings.
Preview Valent DOAS Products: Robust, Efficient, and Reliable Air Handling Units
Explore Valent's range of Dedicated Outdoor Air Systems (DOAS) units, featuring robust designs, efficient controls, and reliable performance for conditioning 100% outdoor air. Learn about cooling, heating, and energy recovery options, capacities, and product data.
Preview Valent VX/VXE/VXC Dedicated Outdoor Air Unit Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Valent VX, VXE, and VXC Dedicated Outdoor Air Units. Covers safety information, product overview, subassemblies, installation procedures, service clearances, and technical specifications.
Preview Valent DOAS Microprocessor Controller Reference Guide
A comprehensive reference guide for the Valent DOAS Microprocessor Controller, detailing its features, operation, and control sequences for dedicated outdoor air systems.