Frico Elztrip EZ200

Original Instructions

Introduction and Ecodesign Regulation

The Ecodesign Regulation (EU) 2015/1188 concerning local space heaters does not apply to all application areas. It applies when an installation is intended to provide thermal comfort for people in the premises. The regulation does not apply to heating installations of a more technical nature (e.g., in engineering/utility rooms, production processes, frost protection) or to installations in vehicles, offshore, or outdoors.

Frico products can be used as both local space heaters and for technical heating purposes. The installer is responsible for assessing whether the Ecodesign Regulation applies. Control solutions for installations not covered by the regulation are listed separately.

Application

The Elztrip EZ200 is a radiant cassette with a sleek design that integrates well with electrical equipment. It is suitable for integral or supplementary heating, and for protection against cold drafts near windows in locations such as department stores, multi-purpose halls, and assembly workshops. The recommended installation heights are indicated in the introductory pages. The product has an IP44 protection rating.

Operation

When in operation, the cassettes reach temperatures of approximately 320°C and emit heat via radiation to cooler surfaces. The maximum ambient temperature is +30°C.

Mounting

The Elztrip can be suspended, mounted horizontally on ceilings, on support rails, or on cables. Standard fixings are supplied within the connection box. For suspended mounting, four suspensions per cassette are required. The distance between panels should not exceed the height between the panel and the floor (distance 'a' must be less than height 'H'). Consult introductory pages for minimum distances.

Mounting Steps:

  1. Determine the cassette's position on the ceiling.
  2. Bend the bracket tabs to approximately 90° (refer to Fig. 1.1, 1.2).
  3. Mount the brackets with the specified spacing (refer to page 4 illustration) onto the ceiling or a cable (Fig. 1.3). For cable mounting, install the bracket at the top of the cable.
  4. Mount the unit according to Fig. 1.4, starting from one end and then assembling the other.
  5. Ensure all screws are tightened correctly.
  6. For cable mounting, use clips to prevent the cassette from sliding.

Diagram Description (Fig. 1. Mounting): Shows the mounting brackets and how they attach to the unit and a surface (ceiling or cable). It illustrates the bending of brackets and the attachment of wires/cables.

Positioning and Minimum Distances

Proper positioning ensures optimal heat distribution. The diagram (Fig. 2) illustrates the relationship between mounting height (H), distance from the wall (a), and recommended clearance (Δh = 1.5 - 2 m). The effective heating range is typically 3-10 meters.

Minimum distances to flammable materials are crucial for safety. The diagram (Fig. 3) details these clearances (B, C, D, E) as specified in the table.

Diagram Description (Fig. 2. Positioning): Illustrates the recommended height and horizontal clearance for mounting the Elztrip unit, showing the heat distribution cone.

Diagram Description (Fig. 3. Minimum distances): Shows a side view of the unit with dimensions indicating required clearances from flammable materials.

Technical Specifications

Item NumberTypeHeat Output [W]Voltage [V]Amperage [A]Max. Surface Temp. [°C]Dimensions LxHxW [mm]Weight [kg]
11066EZ208800230V~3.5320683x64x2824.9
11067EZ2121200230V~5.2320923x64x2826.8
11068EZ2171700230V~7.43201221x64x2828.8
11069EZ2222200230V~9.63201520x64x28210.7
11724EZ20831800400V2~2.0320683x64x2824.9
11725EZ212311200400V2~3.0320923x64x2826.8
11726EZ217311700400V2~4.33201221x64x2828.8
11727EZ222312200400V2~5.53201520x64x28210.7

Controls

The Elztrip EZ200 can be controlled using various accessories. The following tables list available controls and their specifications.

Controls for standard installations:

Item NumberTypeHxWxD [mm]
92790TAP16R87x87x53
205540TEP4487x87x55
93012RB3155x87x43
93044RTX5482x88x25
205550SKG30115x85x40
211780PDK65102x70x50

Controls for installations not covered by the Ecodesign Regulation (EU) 2015/1188:

Item NumberTypeHxWxD [mm]
5999KRT1900165x57x60
10214KRTV19165x57x60

Wiring Diagrams

The document includes various wiring diagrams illustrating different control configurations for the Elztrip EZ200 units. These diagrams show how to connect the heating cassettes with thermostats, relay boxes, black bulb sensors, and presence detectors for both 230V and 400V systems. They also detail connections for installations not covered by the Ecodesign Regulation, using thermostats and contactors.

Diagram Types Illustrated:

Safety and Maintenance

Safety Precautions:

Maintenance:

Residual Current Circuit Breaker (RCD) Issues: If an RCD trips, it may be due to humidity in the heating element, especially after prolonged storage in a damp environment. This is not a fault. It can be remedied by temporarily connecting the appliance to mains power via a socket without an RCD to dry the element. This may take several hours to days. Periodic short operation is recommended to prevent this.

End of Life: This product contains necessary but potentially environmentally hazardous substances. It must not be disposed of with household waste but taken to an approved collection point for recycling.

Models: EZ200 Cassette Radiant Elztrip, EZ200, Cassette Radiant Elztrip, Radiant Elztrip, Elztrip

File Info : application/pdf, 17 Pages, 1.39MB

PDF preview unavailable. Download the PDF instead.

MA FRICO EZ200 FR 180919 20190426 193930959 ?ts=1675419023708

References

Adobe InDesign 18.0 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Frico Elztrip EZ200 Radiant Heater: Installation and Operating Instructions
Comprehensive guide to installing and operating the Frico Elztrip EZ200 radiant heater, including technical specifications, safety guidelines, control options, and wiring diagrams.
Preview Frico Elztrip EZ200: Installation and Operation Manual
Comprehensive guide to the Frico Elztrip EZ200 local space heater, covering installation, operation, technical specifications, and safety guidelines.
Preview Frico Elztrip EZ100 Radiant Heater: Installation, Operation, and Safety Guide
Comprehensive guide for the Frico Elztrip EZ100 radiant heater, covering its features, installation procedures, operational guidelines, safety precautions, and technical specifications. Includes information on Ecodesign regulation compliance.
Preview Frico Elztrip EZ300 Radiant Heater: Installation and Operating Instructions
Comprehensive guide for the Frico Elztrip EZ300 radiant heater, covering installation, operation, safety, technical specifications, and control options. Includes details on Ecodesign regulations and mounting procedures.
Preview Frico Thermozone AD 200 A/E/W Air Curtains - Technical Specifications and Installation Guide
Detailed information on Frico Thermozone AD 200 A/E/W air curtains, including technical specifications, installation instructions, control options, and performance data for ambient, electric, and water-heated models.
Preview Frico Infrasmart IHS20W/B/S24 Infrared Heater User Manual
User and safety instructions for the Frico Infrasmart IHS20W/B/S24 infrared heater, detailing installation, operation, safety precautions, and technical specifications.
Preview Frico IH Infrared Heater: Installation, Operation, and Safety Guide
Comprehensive guide for Frico IH series infrared heaters (IHW and IHF models), covering dimensions, mounting, installation, technical specifications, wiring diagrams, maintenance, and safety instructions. Features detailed descriptions of diagrams and multilingual content translated into English.
Preview FRICO Heating Products Price List - Air Curtains, Heaters, Controls
Official price list from FRICO (Systemair) for heating products as of September 17, 2025. Features air curtains, heaters, fan heaters, convectors, radiators, and control systems with item numbers and descriptions.