Uninterruptible Power Supply (UPS)
with Intrinsically Safe Output and 3.5 Ah Battery Backup
Environments: Mining • Tunnelling
Features
- Robust stainless steel housing
- Regulated output is current limited and has continuous short circuit protection
- 3.5 Ah back-up battery with automatic uninterrupted power transfer
- 12 V, 750 mA Ex ia Ma certified output
- Analogue output signal to show battery charge status
- Volt-free contact to show mains input status
Diagram: The TX6648 unit features a robust stainless steel housing. On the front panel, there is a timer reset button. The unit is divided into chambers: an Ex ia Terminal Chamber, a Mains Input Chamber, and a Battery Chamber. The Mains Input Chamber has terminals for 110V ac, 230V ac, or 24V ac input. The Ex ia output provides +V and OV terminals, along with terminals for Power Fail Relay (P1, P2, P3), Charge Condition Monitor Output (C1, C2, C3), and Timer Control Terminals (T1, T2). The unit also includes fixing holes and M25 Glanc entries.
Benefits
- Can remain on standby battery power in Ex ia Ma area conditions
- Available power can be remotely monitored via the battery charge analogue output signal
- AC mains failure can be remotely monitored via a volt-free output
- Spacious termination facilities to connect heavy-duty mining cables
- Sealed unit requires no user maintenance or examination
- Ex eq certification eliminates any maintenance costs of Ex d style enclosures
Functional Overview
The power supply converts an AC supply voltage into a stabilised and regulated intrinsically safe source, ideal for supplying power to approved sensors and electronic control devices in hazardous areas.
Diagram: The functional overview shows a diagram illustrating the power flow: Mains Input (1) goes to the power supply, which outputs an Intrinsically Safe Ex ia output (2). Terminals 3 and 4 are also indicated as part of the intrinsically safe output.
Technical Information
Parameter | Specification |
---|---|
Input Voltage | 110 V ac ± 10% or 230 Vac ± 10% - 50/60 Hz or 24 V ac +/- 10% |
Output Voltage | 12 V dc -0 V/+0.6 V |
Output Current | 750 mA |
Output Ripple/Noise | 150 mV max |
Line Regulation | <5% over the input voltage range |
Load Regulation | <5% over 0 to 90% of load current |
Voltage Limiting | <10% between 90% and 100% of load current. Over voltage detection with crowbar protection and short circuit protection. |
Current Limiting | Automatic current limiting of the intrinsically safe output also limits the current to less than the rupturing capacity of the output protection fuse. |
Max. Operating Temperature | -20°C to +40°C |
Storage Temperature | -20°C to +70°C |
Humidity | 0 to 95% RH, non-condensing |
Vibration Limits/Low Frequency | 0.25 mm peak, sinusoidal vibration in the range 10 Hz to 100 Hz in 3 perpendicular planes |
Medium Frequency | 2g peak, sinusoidal vibration in the range 10 Hz to 600 Hz in 3 perpendicular planes |
Mechanical Shock | 1000 shocks of 40g minimum in 3 perpendicular planes |
Housing Material | Stainless steel |
Weight | 16 kg |
Back-up Battery | Sealed lead-acid - 3.5 Ah |
Power Fail Indication | Automatic charge control to full capacity. Automatic uninterrupted output power transfer following input power failure. Relay contacts change state on power failure. Contact rating: 0.25 A at 30 V dc max. |
Charge Condition | Analogue output signal proportional to the charge level of the battery. Choice of 0.4 V to 2.0 V or 4 to 20 mA signals. |
Battery life | 6 years with normal usage |
Ex Certification | Group I - Please refer to user manual for full certification details |
Dimensions
Diagram: The dimensions show the unit with a height of 340mm, width of 386mm, and depth of 160mm. The Ex ia Chamber has dimensions of 160mm x 110mm x 67mm. The Battery Chamber is 160mm x 110mm x 110mm. The Mains Input Chamber is 160mm x 110mm x 58mm. There are 8 x Ø9.0 fixing holes and 2 x M25 Glanc entries.
Connections
Diagram: The connection diagram illustrates the following:
- Exi Output: +V, +V, -V, 0V, P1, P2, P3, C1, C2, C3, T1, T2
- Mains Input: 110V ac or 230V ac or 24V ac
- Output Specifications: +V = 12 V dc (intrinsically safe output), 0V = 0V (intrinsically safe output)
- Power Fail Relay: P1 = C, P2 = N/C, P3 = N/O
- Charge Condition Monitor Output: C1 = 0.4 to 2 V, C2 = 0 V, C3 = 4 to 20 mA
- Timer Control Terminals: T1, T2
- Remote Link: To Enable Timer Function
Battery Conserve Timer
The TX6648 Power supply is fitted with a Battery Conserve Timer. The timer is used to conserve battery power when used on mobile machinery where battery support will only be required for short intervals between long periods.
- The battery will be charged in the normal way when the main power is ON.
- The battery back-up output will be terminated 30 minutes after the main power is OFF.
- The battery back-up output may be re-instated at any time for a period of 30 minutes by operation of a pushbutton on the side of the power supply housing or a remote pushbutton connected to T1 and T2.
- The timer is disabled by fitting a link between T1 and T2.
Order Reference
ATEX & IECEx Certification
- 110 V ac supply: TX6648.35.105.101.1206.19
- 230 V ac supply: TX6648.35.106.101.1206.19
- 24 V ac supply: TX6648.35.103.101.1206.19
MASC Certification
- 110 V ac supply: TX6648.35.105.101.1206.05
- 230 V ac supply: TX6648.35.106.101.1206.05
- 24 V ac supply: TX6648.35.103.101.1206.05
Image: A small image of the TX6648 unit is displayed.
Disclaimer
The information provided in this document contains general descriptions and technical characteristics of the performance of the product. It is not intended as a substitute for and is not to be used for determining suitability or reliability of this product for specific user applications. It is the duty of any user or installer to perform the appropriate and complete risk assessment, evaluation and testing of the products with respect to the specific application or use. Trolex shall not be responsible or liable for misuse of the information contained herein. When instruments are used for applications with technical safety requirements, the relevant instructions must be followed.
All pertinent state, regional, and local safety regulations must be observed when installing and using this instrument. For reasons of safety and to help ensure compliance with documented system data, only Trolex or its affiliates should perform repairs to components.
Trolex Ltd. reserves the right to revise and update this documentation from time to time without obligation to provide notification of such revision or change. Revised documentation may be obtainable from Trolex.
Trolex Ltd. reserves the right, without notice, to make changes in equipment design or performance as progress in engineering, manufacturing or technology may warrant.
Trademark
© 2025 Trolex® Ltd.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Trolex.
Trolex is a registered trademark of Trolex Ltd. The use of all trademarks in this document is acknowledged.
Contact Information
At Trolex, we save lives. We believe that no person should risk their life to earn a living. Our aim is to become the world's leading name in health and safety technology, through pioneering products that provide real-world benefits to our customers, whenever workers operate in hazardous environments.
For more information about Trolex, please contact us at:
- Website: www.trolex.com
- Enquiries: sales@trolex.com
- Telephone: +44 (0) 161 483 1435
Trolex Ltd
Newby Road, Hazel Grove
Stockport, Cheshire
SK7 5DY, United Kingdom
Follow us: @TrolexUK [linkedin-icon] [twitter-icon] [facebook-icon]
Related Documents
![]() |
Trolex TX6649 Uninterruptible Power Supply (UPS) Datasheet Datasheet for the Trolex TX6649 Uninterruptible Power Supply (UPS) with Intrinsically Safe Output and 25 Ah Battery Backup, designed for hazardous environments like mining and tunnelling. |
![]() |
Trolex TX6831 Audio/Visual Alarm ATEX Certification Certification details for the Trolex TX6831 Audio/Visual Alarm, including IA Certificate, EU-Type Examination Certificate, and associated documentation for use in potentially explosive atmospheres. |
![]() |
Trolex TX8005 Air XD Particulate Monitor: IA and IECEx Certification This document provides the IA Certificate from Mining And Surface Certification (Pty) Ltd and the IECEx Certificate of Conformity for the Trolex TX8005 Air XD Particulate Monitor. It details the equipment's description, technical specifications, marking, safety conditions, and compliance with relevant SANS/IEC standards for use in explosive atmospheres. |
![]() |
Trolex TX6373 Toxic Gas Sensor/Transmitter: Installation and Operating Data Manual Comprehensive installation and operating data for the Trolex TX6373 Toxic Gas Sensor/Transmitter. Covers features, applications, technical specifications, calibration, maintenance, safety, and hazardous area compliance for industrial environments. |
![]() |
Trolex TX8005 Air XD Particulate Monitor IA Certificate and IECEx Certificate of Conformity This document contains the IA Certificate issued by MASC (Mining And Surface Certification Pty Ltd) and the IECEx Certificate of Conformity for the Trolex TX8005 Air XD Particulate Monitor. It details the equipment's specifications, safety conditions, and compliance with relevant standards for use in explosive atmospheres. |
![]() |
Trolex Connected Solutions Powered by Aethair: Real-Time Hazard Detection Trolex offers advanced connected cloud solutions for fixed hazard detection, integrating AIR XS silica monitors, AIR XD dust monitors, and SENTRO X gas detectors with the Aethair Environet platform for real-time data, enhanced workplace safety, and AI-driven insights. |
![]() |
Trolex TX91xx Trip Amplifiers EU-Type Examination Certificate This document contains the EU-Type Examination Certificate for Trolex TX91xx Programmable Trip Amplifiers, detailing compliance with ATEX directives and safety requirements. |
![]() |
Trolex TX9131-2-6-7-9 Programmable Trip Amplifier User Manual This user manual provides comprehensive installation and operating data for the Trolex TX9131-2-6-7-9 Programmable Trip Amplifier, covering its features, applications, technical specifications, and safety certifications. |