1. Safety Precautions
- Ensure the product is used within the specified limits.
- Do not touch the terminals while power is supplied, as this may cause electric shock.
- Prevent metal pieces, wire clippings, or filings from entering the product to avoid electric shock, fire, or malfunction.
- Do not use the product in environments with flammable or explosive gases to prevent explosion hazards.
- Never disassemble, modify, or repair the product yourself. Internal parts should not be touched to avoid electric shock, fire, or malfunction.
- Be aware that output relays have a limited lifespan. Contact fusing or burning may occur if used beyond their life expectancy. Always consider application conditions and use relays within their rated load and electrical life expectancy. Relay lifespan varies with output load and switch conditions.
2. Specification
Mounting dimension
- Front Panel Dimension: DIN (48WmmX48Lmm)
- Cutout size: 45x45mm
Main Features
- Supports Multiple Thermocouples and Resistance Sensors (K, S, Wre, T, E, J, B, N, CU50, PT100).
- Wide Controlling Range: -50~1300°C (K sensor).
- High Accuracy of Displaying and Controlling: 0.1°C. Accuracy of Measurement: ±0.2%FS.
- PID and ON/OFF Control Mode with High Standard Self-adjusting Function.
- Multiple Outputs and Alarm Modes.
- Build-in Adjustable Digital Filter to Reduce Interference.
- Self-adjusting Function and Intelligent Control ensure long-term stability.
- High Luminance, 0.39" height LED display with an anti-glare panel.
- Built-in Switch Power Supply with a wide voltage range and low-power consumption.
2. Specification (Continued)
Attribute | Details |
---|---|
Units | Degree Celsius (<1000°C) |
Weight | Approx. 140g |
Power Supply Voltage | AC 100-240V ±10% 50/60Hz AC/DC 12-24V ±10% 50/60Hz DC 12-24V ±10% |
Operating voltage range | 85~110% Rated voltage |
Power Consumption | Approx. 5VA (100~240VAC) Approx. 4VA (12~24VAC) Approx. 3W (12~24VDC) |
Display Character | PV: 4 digital 9.9mm height Red LED Letters SV: 4 digital 8mm height Green LED Letters |
Display Accuracy | ±0.2%FS 0.1°C (<1000°C); 1°C (≥1000°C) |
Period of Sampling | 0.5S |
Temperature Compensation | 0-50°C |
Main Output |
Relay Contact Output (ITC-100R): AC250V 3A (Resistive load) ON/NC. Alarm 1 AC250V 3A (Resistive load) ON/NC. Voltage Pulses Output (ITC-100V): DC 12V, 30mA; Alarm 1 AC250V 3A (Resistive load) ON/NC |
Life Expectancy of Relay | Mechanical ≥10,000,000 operations Electrical ≥10,000,000 operations |
Storage Temperature | -25~65°C (no icy or condensation) |
Data Storage | 10 year |
Mounting Method | Flush mounting and screw terminals |
Environmental Conditions | -10~55°C (no icy or condensation), RH 35-85% Humidity |
3. Connection
3.1 Dimension (unit: mm)
Shell Diagram: A rectangular diagram showing dimensions: Height 89mm, Width 74mm, Depth (indicated by X) 48mm.
Mounting bracket Diagram: A diagram showing a bracket with dimensions: Length 49mm, Width (indicated by X) 56mm.
Panel Cutout Diagram: A diagram showing the required panel cutout dimensions: Minimum 60mm for width and height, with a cutout size of 45+0.6mm for width and 45+0.6mm for height.
- Push the instrument into the panel cutout and insert the mounting bracket from the back side. Ensure there are no gaps between the panel and the mounting bracket, then screw the cap down.
- Ensure the ambient temperature does not exceed the specified working temperature, especially when installing more than two instruments.
3.2 Connection
ITC-100V Connection Diagram: Shows terminals numbered 1 through 12. Terminal 1 (NC), 6 (NO), 11 (SSR Output). Terminal 3 (TC-), 8 (Output+). Terminal 4 (AL1), 9 (AL1). Terminal 5 (COM), 12 (Power). Terminal 10 (COM). Connections are shown to SSR and Power.
ITC-100R Connection Diagram: Shows terminals numbered 1 through 12. Terminal 1 (NC), 6 (NO), 11 (SSR Output). Terminal 3 (TC-), 8 (Output+). Terminal 4 (AL1), 9 (AL1). Terminal 5 (COM), 12 (Power). Terminal 10 (COM). Connections are shown to SSR and Power.
4. Front Panel and Operation
Front Panel Diagram Description: The front panel features a large LED display area showing 'TEMPERATURE' and two rows of numerical displays (PV and SV). Status indicator LEDs are labeled 'OUT', 'AL 1', 'AL 2', 'RUN', 'AT/RUN'. Below the display are control buttons: 'ITC', 'SET', and directional arrows: '◀' (Left/Shift), '▶' (Right/Move), '▲' (Up), '▼' (Down).
The buttons are numbered 1 through 7:
- ① PV: Process Value / Measured Value / Mode Value
- ② SV: Setting Value / Set Value / Mode Context Value
- ③ Status Display LED: OUT (Output pilot lamp), AL1 (Alarm1 pilot lamp), AL2 (Alarm2 pilot lamp), RUN (Manual pilot lamp).
- ④ Up Key: Increases value during setting; rapid increase when held.
- ⑤ Down Key: Decreases value during setting; rapid decrease when held.
- ⑥ Move Key: Switches to the next value/parameter position during setting.
- ⑦ SET Key: Press briefly to check PV/SV values. Press and hold for over 2 seconds to enter parameter setting mode.
5. Operation Process
5.1 Input Type (Table1)
Input Type | Input | Value | Measuring Range |
---|---|---|---|
Thermocouple | K | 0 | -50~1300°C |
S | 1 | -50~1700°C | |
Wr | 2 | -0~2300°C | |
T | 3 | -2000~350°C | |
E | 4 | 0~1000°C | |
J | 5 | 0~1000°C | |
B | 6 | 0~1800°C | |
N | 7 | 0~1300°C | |
Cu resistance | CU50 | 20 | -50~150°C |
Platinum resistance | PT100 | 21 | -200~600°C |
5.2 Alarm Function Setting (Table 2)
Alarm Output | Alarm Type | ALP Value |
---|---|---|
AL1 Output | Upper Alarm Limit | 0 |
Lower Alarm Limit | 0 | |
Maximum Deviation Alarm | 0 | |
Minimum Deviation Alarm | 0 | |
AL2 Output | Upper Alarm Limit | 1 |
Lower Alarm Limit | 2 | |
Maximum Deviation Alarm | 4 | |
Minimum Deviation Alarm | 8 |
5.3 Error Display (Fault Diagnosis)
SV Display | Explain | Remedy |
---|---|---|
orAL (orAL) | Input Sensor Selected Error | Input the correct value consistent with parameters of sensor. |
Signal Wire Connected Error | Correct the Connecting Signal Wire. | |
(orAL) | Sensor Fault | Check the sensor. |
6. Operating Instruction
- After power-on, the PV screen displays the current measured value and the SV screen displays the current set value, indicating normal status.
- If the PV/SV screen displays "orAL" alternately, it signifies that the input value is out of range (or sensor is open circuit) or the input setting is incorrect.
- When an alarm output is active, the SV screen displays characters related to the alarms: HiAL (Upper Alarm Limit), LoAL (Lower Alarm Limit), dHAL (Maximum Deviation Alarm), dLAL (Minimum Deviation Alarm).
- Checking Output Value: Press the [SET] key (no more than 1S). If the SV screen displays "A" (e.g., A100), the status is automatic control output. If the SV screen displays "M" (e.g., M100), the status is manual control output.
- Auto/Manual Switch: Press the [Left Arrow] key (no more than 1S) to switch between automatic and manual control status. In automatic control status, the RUN pilot lamp is off. In manual control status, the RUN pilot lamp is on. (Note: This function may be restricted if the setting function status is "2: No manual").
- Temperature Setting: When the SV screen displays the setting value, press the [Up Arrow] key or [Down Arrow] key to increase or decrease the setting value. Press the [Right Arrow] key to move the cursor to the digit to be updated. Holding down the [Up Arrow] or [Down Arrow] keys allows for rapid value adjustment.
- Start the Self-adjusting Function: For initial use, it is recommended to use the self-adjusting function to determine control parameters (M50, P, and T). This helps achieve ideal control. Keep pressing the [Left Arrow] key for more than 2 seconds. The SV screen will alternately display "AT" (Character: AT), indicating the instrument is in self-adjusting status. During this process, the instrument performs 2-5 oscillations to automatically determine PID control parameters (M50, P, and T). The instrument will return to PID automatic control status upon completion. To quit self-adjustment prematurely, press and hold the [Left Arrow] key for more than 2 seconds until the "AT" character disappears from the SV screen.
- Attention: To re-initiate self-adjustment after the first use, set the "CtrL" parameter to "2". Refer to "Parameter Setting and Defining" for more details. Control parameter values may vary with different setting temperatures; therefore, perform self-adjustment at the most common system setting temperature. If setting values change frequently, manual modulation might be necessary.
7. Parameter Setting and Defining
After power-on, press and hold the [SET] key for more than 2 seconds to enter setting mode. Use the [Up Arrow] or [Down Arrow] keys to set the value. After finishing, press the [SET] key to confirm and proceed to the next function setting. The PV/SV screen will return to normal display after setting.
Note: If modifications are made in setting mode, the instrument will automatically save the current value after more than 10 seconds of inactivity and return to normal status.
Function Setting Code | Name | Description | Setting Range | Unit | Remarks | Factory Default |
---|---|---|---|---|---|---|
HI AL | HIAL | Upper Alarm Limit | -1999~+9999 | 1°C | 9999 | |
LoAL | LOAL | Lower Alarm Limit | -1999~+9999 | 1°C | -1999 | |
dH AL | dHAL | Maximum Deviation Alarm | 0~9999 | 1°C | 9999 | |
dL AL | dLAL | Minimum Deviation Alarm | 0~9999 | 1°C | 9999 | |
dF | dF | Hysteresis | 0~200.0 | 0.1°C | 0.3 | |
CtrL | Ctrl | Control Output | 0: ON/OFF 1/3: PID 2: Self-adjustment |
3 | ||
" M50 | M50 | Integral | 0~9999 | 0.1°C | 0: Cancel | 1000 |
" P | P | Differential | 0~9999 | 0.01S/°C | 500 | |
" t | t | Hysteresis Time | 1~9999 | S | 120 | |
" CEI | Ctl | Control Period | 1~120 | S | 4 | |
" 5n | Sn | Input Sensor | 0~42 | Table 1 | 0 |
7. Parameter Setting and Defining (Continued)
Function Setting Code | Name | Description | Setting Range | Unit | Remarks | Factory Default |
---|---|---|---|---|---|---|
di P | dip | Decimal Point Position | 0~3 | 1 | ||
di L | diL | Input Lower Limit Value | -1999~+9999 | 1 Digital | 0 | |
di H | diH | Input Upper Limit Value | -1999~+9999 | 1 Digital | 1000 | |
SC | SC | Sensor Calibration | -199~+999 | 0 | ||
oP1 | OP1 | Output Mode | 0/2: Time Duty 1: 0-10mA |
0 | ||
OPL | Opl | Output Lower Limit | 0~220 | 1% | 0 | |
OPH | Oph | Output Upper Limit | 0~220 | 1% | 100 | |
ALP | ALP | Alarm Function | 0~31 | Table 2 | 0 | |
CF | CF | System Function | 2: Heater 3: Cooler |
2 | ||
Addr | Addr | Address | 0~63 | 1 | ||
bRud | Baud | Baud Rate | 0~4800 | Filter Effect | 9600 | |
dL | dl | Input Digital Filter | 0~20 | 0 | ||
run | run | Run Mode | 0: Manual 1: Automatoc 2: No Manual |
2 | ||
Loc | LOC | Lock Function | 0~999 | 40 | ||
EP1 ~ EP8 | 8 User-defined Parameters | Select any Parameter from this Table | Except LOC and EP1~EP8 | none |
User-defined Parameter
In the process of setting parameters, the display modes of the last eight parameters differ from the previous ones. The PV screen displays the prompt EP1 - EP8. The SV screen displays various prompts of technical parameters (e.g., HiAL, LoAL, dHAL, and so on). Press the [Up Arrow] or [Down Arrow] key. The technical parameters in the SV screen will be listed in proper order as in the table above. After that, press the [SET] key to confirm and enter the next setting. "none" needs to be set if the user does not need to use the user-defined parameter. Press the [SET] key to set these 8 user-defined parameters until all are set, and then return to normal status.
Datalock (LOC)
When the setting values of LOC are not "2", "40", or "808", the instrument only allows setting 0-8 self-defined parameters and LOC parameters themselves. User can set all parameters only when the LOC value is "2", "40", or "808". Details are as follows:
- Loc=0: Temperature setting value and EP1-EP8 can be revamped.
- Loc=1: Data cannot be revamped, only can be checked (Except LOC parameters).
- Loc=2, 40, 808: All parameters can be revamped.
8. Technical Assistance and Warranty
8.1 Technical Assistance
If you encounter any problems installing or using this thermostat, please carefully and thoroughly review the instruction manual. For assistance, please write to cs@ink-bird.com. Emails will be replied to within 24 hours from Monday through Saturday. You can also visit the Inkbird website at www.ink-bird.com to find answers to common technical questions.
8.2 Warranty
INKBIRD TECH. C.L. warrants this thermostat for one year from the date of purchase when operated under normal conditions by the original purchaser (not transferable), against defects caused by INKBIRD's workmanship or materials. This warranty is limited to the repair or replacement, at INKBIRD's discretion, of all or part of the thermostat. The original receipt is required for warranty purposes.
INKBIRD is not responsible for injury, property damage, or other consequential damages or damages of third parties arising directly from actual or alleged defects in workmanship of the product. There are no representations, warranties, or conditions, express or implied, statutory or otherwise, other than herein contained in the sale of goods act or any other statute.