OUTLINE & MOUNTING FOR ASCO 300 SERIES AUTOMATIC TRANSFER SWITCHING EQUIPMENT (D2ATS/D2NTS) RATED 30-200 AMPERES, TYPE 1 ENCLOSURE

GENERAL NOTES

  • TYPE 1 WALL MOUNTED ENCLOSURE.
  • STANDARD FINISH – LIGHT GRAY, ANSI 61. OTHER FINISHES AVAILABLE CONSULT FACTORY.
  • KEY LOCKABLE HANDLE.
  • REMOVABLE SINGLE DOOR
  • TERMINALS – SCREW TYPE LUGS FOR EXTERNAL POWER CONNECTIONS.
  • [CG] = CENTER OF GRAVITY.
  • THREE POLE SWITCH WITH SOLID NEUTRAL SHOWN FOR REFERENCE.
  • NEUTRAL CONFIGURATIONS:
    • AN OPTIONAL FULL RATED NEUTRAL CONFIGURATION FOR EACH SOURCE AND THE LOAD MAY BE PROVIDED. WHEN EQUIPPED IT IS IN ONE OF THE FOLLOWING FORMATS AS SPECIFIED BY THE CATALOG NUMBER NO. NEUTRAL TYPE:
      • (A) SOLID (COPPER BUS) NEUTRAL
      • (B) SWITCHED NEUTRAL POLE
      • (C) OVERLAPPING NEUTRAL POLE (SEE NOTICE)

DIAGRAM DESCRIPTIONS

Top View (Typical Top & Bottom): Shows the top of the enclosure. Dimensions include 177.8mm [7.00] width and 144.2mm [5.68] depth. Features .75-.50 combination pilot knock-outs located at the top and bottom.

Front View Without Door: Displays the front of the enclosure with the door removed. Overall dimensions are 457.2mm [18.00] width and 787.4mm [31.00] height. Key internal components are visible: the switch mechanism with terminals labeled NORMAL and EMERGENCY, and an OPTIONAL SOLID NEUTRAL connection. Dimensions for the internal switch area are 279.4mm [11.00] height. Mounting holes are indicated by (4) .37-DIA. EXTERNAL DIMPLED MOUNTING HOLES.

Front View With Door: Shows the front of the enclosure with the door closed. Overall dimensions are 469.9mm [18.50] width (outside) and 800.1mm [31.50] height (outside). Features a key lockable handle. A control indicator is present. The Center of Gravity [CG] symbol is also shown.

Right Side View: Illustrates the side profile of the enclosure. Dimensions include 339.7mm [13.37] width (outside) and 400.1mm [15.75] height. Ground lug mounting studs are indicated. The overall depth is 190.5mm [7.50].

NOTICE

When an overlapping switched neutral assembly is provided, the normal and emergency source neutral terminations are physically reversed from those of the normal and emergency source phase terminations. Locate the neutral termination markings and review the wiring diagram before connecting the neutral conductors.

POWER CONNECTIONS

RANGE OF AL-Cu CONDUCTOR SIZES ISO CROSS SECTION (mm²) (USE STRANDED TYPE CONDUCTORS)

SWITCH RATING (AMPS)CONDUCTOR SIZE RANGERECOMMENDED TIGHTENING TORQUE
30-200*ONE 2-511,3 Nm
200*-COPPER WIRE ONLYOR ONE 6-12022,6 Nm

PROJECT INFORMATION

PROJECT NAME: COMPOSITE OUTLINE

PRODUCT: 300 SERIES, D2ATS/D2NTS RATED 30-200 AMPERES, 30-200 AMPS TYPE 1 IEC/CE

MANUFACTURER: ASCO POWER TECHNOLOGIES, L.P., FLORHAM PARK, NEW JERSEY 07932 U.S.A.

DRAWING NUMBER: 978723-A

DRAWN BY: VOM, DATE: 12/30/15

CHECKED BY: EL, DATE: 12/30/15

APPROVAL: BK, DATE: 12/30/15

REVISION: ISSUE, ECN NO.: 258699, VOM: EL, DATE: 12/30/15

COMPUTER GENERATED DRAWING

MANUFACTURING TOLERANCES: TO BE IN ACCORDANCE WITH ASCO PROCEDURE MP-1-003. FOR PLASTIC PARTS SEE MP-1-055.

THIRD ANGLE PROJECTION

Property of ASCO Power Technologies. Use permitted for our work only. All rights of design or invention are reserved.

PDF preview unavailable. Download the PDF instead.

files?p enDocType=Technical Drawing&p File Name=978723-A - &p Doc Ref=ASC-TS-OD-978723-A AutoCAD 2013 - English 2013 (19.0s (LMS Tech)) pdfplot11.hdi 11.0.204.0

Related Documents

Preview ASCO 300 Series Transfer Switches Outline Drawing - 30-200 Amperes, Type 1 Enclosure
Detailed outline drawing for ASCO 300 Series Transfer Switches (D3ATS/D3NTS) rated 30-200 Amperes, Type 1 enclosure, including physical dimensions, general notes, and technical specifications.
Preview ASCO 300 Series Transfer Switches (E3ATS/E3NTS) 260 & 400 Amperes Outline
Outline drawing and dimensional data for ASCO 300 Series E3ATS/E3NTS automatic transfer switches, rated for 260 and 400 amperes, open type. Includes general notes, cabling notes, and mounting dimensions.
Preview ASCO 300 Series Transfer Switches: Outline and Specifications (1000-2000 Amp)
Detailed composite outline and technical specifications for ASCO 300 Series automatic transfer switches, covering 1000 to 2000 Amp models. Includes dimensions, general notes, and cabling information for electrical installations.
Preview ASCO 300 Series G3MGDQ Transfer Switch Wiring Diagrams and Specifications
Detailed wiring diagrams, connection schematics, and accessory specifications for ASCO 300 Series manually operated transfer switches (Type G3MGDQ), rated for 1000-3000 Amperes. Includes information on field connections, power poles, optional accessories, and wire run listings.
Preview ASCO Series 300 Automatic Transfer Switch Wiring Diagrams and Technical Data
Comprehensive technical document detailing wiring diagrams, control schematics, physical layout, and operator controls for ASCO Series 300 Automatic Transfer Switches (ATS) with Group 1 Controls, available in 600, 800, 1000, and 1200 Ampere ratings. Includes wire run lists and accessory information.
Preview ASCO Series 300 Automatic Transfer Switch Wiring Diagrams - 600 Amperes
Detailed wiring diagrams and technical specifications for the ASCO Series 300 Automatic Transfer Switch, rated for 600 Amperes with Group 1 Controls. Includes control features, circuit schematics, and wire listings.
Preview ASCO Series 300 ATS Wiring Diagrams and Technical Specifications
Detailed wiring diagrams, control features, and physical layout for ASCO Series 300 Automatic Transfer Switches (ATS), 'G' Frame, Group 1 Controls, 1600-3000 Amperes.
Preview ASCO 300 Series Transfer Switches Wiring Diagram for 600 Amperes with Group G Controls
This document provides detailed wiring diagrams and technical specifications for ASCO 300 Series Transfer Switches, specifically the J3ATS and J3NTS models rated at 600 Amperes, featuring Group G controls. It covers general information, feature descriptions, wiring for various circuits including main power, operator, normal and emergency sources, load terminals, and control signals. The document also details optional accessories like the relay expansion module (18RX), uninterruptible power supply (1UP), and load current metering (23GB), along with their wiring configurations. It includes explanations of catalog number codes, physical diagrams, and wire run listings for comprehensive installation and maintenance guidance.