Pioneer YN050GLSI24M5G Quint (5) Circuit Ductless Inverter Heat Pump Set

Submittal Sheet For: YN050GLSI24M5G / (5x) CT0xxGLSILCFHG

System Full Set Model: YN050GLSI24M5G

AHRI Reference Number: 217048768

Cooling Mode Performance

Rated Cooling42,000 BTU/hr
Ambient Range5°F ~ 131°F
SEER Rating22.0 BTU/W·h
EER Rating12.0 BTU/W·h

* 100% Capacity @ Indoor DB 80°F/WB 67°F

Heating Mode Performance

Rated Heating42,000 BTU/hr
Ambient Range-13°F ~ 86°F
HSPF2 IV (V)9.5 (8.2) BTU/W·h
COP (47°F)3.5 (W/W)

*High Heat (47°F) = 42,000 BTU / Low Heat (17°F) = 29,400 BTU / COP (5°F) = 2.0

Electrical Information

CoolingHeating
Rated Input (W)3,5503,260
Rated Current (A)15.914.6
Breaker Needed45A (Double-Pole)
Power Supply208~230V, 1Ph, 60Hz

Piping and Refrigerant

Liquid Line (OD)1/4" (5)
Suction Line (OD)3/8" (5)
Refrigerant PrechargeR454b (Selectable Lineset)
Vertical Run/Elevation Diff.50 ft. / 33 ft.

Exterior Unit (Condenser) Specifications

Sound Level (dBA)65
Recommended Room Size1,000~1,600 Sq. ft.
Minimum Room Size135 Sq. ft.
CompressorTwin-Rotary
Dimensions (WDH)42"-1/4 x 18"-3/8 x 33"-1/2
Weight (lbs)174.2

Compatible Indoor Air Handler Units

CT009GLSILCFHG (9K)CT012GLSILCFHG (12K)
CT018GLSILCFHG (18K)CT024GLSILSFHG (24K)
Quantity5 (Up to 60,000 BTU)
Max Circuit Length80 ft. (9K) / 100 ft. (12K/18K/24K)
Max Vertical Run33 ft. (9K/12K/18K/24K)
Adjustment Charge0.11 oz x (L1+L2+L3+L4+L5-125 ft.)

Visual Components

Image: A wall-mounted indoor unit with a Pioneer logo and grille.

Image: An outdoor condensing unit with a Pioneer logo and fan grille.

Image: An installation kit showing pipes and cables.

Image: A handheld remote controller.

Condenser Unit Dimensional Data (YN050GLSI24M5G)

Diagram showing the front and side views of the outdoor condensing unit with dimensions labeled A, B, C, D, E.

ModelABCDE
YN050GLSI24M5G (42,000 BTU / 5-Zone)26" (660 mm)18-1/4" (462 mm)18-3/8" (468 mm)42-1/4" (1074 mm)33-5/8" (853 mm)

Air Handler Dimensional Data

The following sections detail the dimensions for various compatible indoor air handler units.

CT009GLSILCFHG Air Handler

Diagrams showing the top, side, and ceiling installation view of the CT009GLSILCFHG air handler, including dimensions and required clearances for air outlet, air inlet, floor-to-panel, and inlet-to-ceiling.

Panel Thickness: 2-3/8 in (60 mm)

Dimensions (approximate from diagram):

  • Overall Width/Depth: 25-5/8 in (650 mm)
  • Air Handler Body Depth: 9-5/8 in (245 mm)
  • Ceiling to Floor Clearance: ≥ 8 ft 2 in
  • Inlet to Ceiling Clearance: ≥ 10-3/4 in
  • Air Outlet to Wall Clearance: ≥ 39-3/8 in

CT012GLSILCFHG Air Handler

Diagrams showing the top, side, and ceiling installation view of the CT012GLSILCFHG air handler, including dimensions and required clearances.

Panel Thickness: 2-3/8 in (60 mm)

Dimensions (approximate from diagram):

  • Overall Width/Depth: 25-5/8 in (650 mm)
  • Air Handler Body Depth: 9-5/8 in (245 mm)
  • Ceiling to Floor Clearance: ≥ 8 ft 2 in
  • Inlet to Ceiling Clearance: ≥ 10-3/4 in
  • Air Outlet to Wall Clearance: ≥ 39-3/8 in

CT018GLSILCFHG Air Handler

Diagrams showing the top, side, and ceiling installation view of the CT018GLSILCFHG air handler, including dimensions and required clearances.

Panel Thickness: 2-3/8 in (60 mm)

Dimensions (approximate from diagram):

  • Overall Width/Depth: 25-5/8 in (650 mm)
  • Air Handler Body Depth: 9-5/8 in (245 mm)
  • Ceiling to Floor Clearance: ≥ 8 ft 2 in
  • Inlet to Ceiling Clearance: ≥ 10-3/4 in
  • Air Outlet to Wall Clearance: ≥ 39-3/8 in

CT024GLSILCFHG Air Handler

Diagrams showing the top, side, and ceiling installation view of the CT024GLSILCFHG air handler, including dimensions and required clearances.

Panel Thickness: 2-7/8 in (73 mm)

Dimensions (approximate from diagram):

  • Overall Width/Depth: 37-3/8 in (950 mm)
  • Air Handler Body Depth: 9-5/8 in (245 mm)
  • Ceiling to Floor Clearance: ≥ 8 ft 2 in
  • Inlet to Ceiling Clearance: ≥ 10-3/4 in
  • Air Outlet to Wall Clearance: ≥ 39-3/8 in

Combination Data and Miscellaneous Information

Air Handler Specifications

ModelAirflow Rate (cfm)Sound Level (dBA)Auto Air CirculationDimensions (WDH)Weight (lbs)
CT009GLSILCFHG329 (Turbo)/300 (Hi) / 270 (Med) / 217 (Lo)/194 (Mute)43 (Turbo)/41 (Hi) / 37 (Med) / 33 (Lo) / 32 (Mute)2-Way Louver (Up-Down + Left-Right)22"-1/2 x 22"-1/2 x 9"-5/832.0
CT012GLSILCFHG360(Turbo)/320(Hi)/260(Med)/200(Lo)/190(Mute)45 (Turbo) / 43 (Hi) / 39 (Med) / 35 (Lo) / 32 (Mute)2-Way Louver (Up-Down + Left-Right)22"-1/2 x 22"-1/2 x 9"-5/832.0
CT018GLSILCFHG441(Turbo)/394(Hi)/ 335(Med)/282(Lo)/253(Mute)48 (Turbo) / 46 (Hi) / 42 (Med) / 39 (Lo) / 37 (Mute)2-Way Louver (Up-Down + Left-Right)22"-1/2 x 22"-1/2 x 9"-5/832.0
CT024GLSILCFHG836(Turbo)/765(Hi)/630(Med)/530(Lo)/482(Mute)51 (Turbo) / 48 (Hi) / 44 (Med) /40 (Lo)/37 (Mute)2-Way Louver (Up-Down + Left-Right)33"-1/8 x 33"-3/4 x 10"-3/451.8

Matching Table (# Circuits Utilized)

2-Circuits(9000-24000) + (9000-24000)
3-Circuits(9000-24000) + (9000-24000) + (9000-18000)
4-Circuits(9000-24000) + (9000-18000) + (9000-12000) + (9000-12000)
5-Circuits(9000-24000) + (9000-18000) + (9000-12000) + (9000-12000) + (9000-12000)

Piping Diameters

9000 BTU1/4" (Liquid) - 3/8" (Suction)
12000 BTU1/4" (Liquid) - 3/8" (Suction)
18000 BTU1/4" (Liquid) - 1/2" Adapter Required (Suction)
24000 BTU1/4" (Liquid) - 5/8" Adapter Required (Suction)

(All Necessary Adapters Provided with Condenser)

Note: If the total demand from the combined group of indoor units exceeds the rated capacity of the outdoor unit, the capacity of each indoor unit will be annotated accordingly. Each indoor unit operates at a random, self-regulated capacity based on the actual demand it measures from its zone (between 30% to 100% of its rated capacity) or turns Off as needed.

Warranty Information and Length

Image: A shield graphic with the number '10' indicating a 10-year warranty.

Complete warranty details are available with the vendor or online at pdhvac.com/support/warranty/. This high-quality system is eligible for up to 10 years limited warranty on the compressor, and 7 years on other internal parts. To qualify for this warranty, the system must be installed within 90 days by a registered technician. All other installations that are registered default to 5 years parts/compressor. Products unregistered qualify for only 1 year parts/compressor warranty.

Outstanding Features

  • LED Display
  • Energy Saving ?
  • Ultra-Thin Design
  • Dual Drain Options
  • Customizable Timer
  • Eco-Friendly Refrigerant
  • Whisper-Quiet Operation
  • Power Loss Memory Recovery

Available Accessories

Part NumberDescription
IKT-LCVR4P-KITDecorative PVC Line Cover Kit
IKT-LNBR-1/4-3/8BendAid Flexible Easy Bender Kit
BRK-FRM-C-2PFolding Mounting Bracket w/ Leveler
IKT-UVL32UL-AGUVC Bacterial Disinfection Kit
IKT-SURPRK-DV2Ultimate Surge and Power Protection

PDF preview unavailable. Download the PDF instead.

YN050GLSI24M5G CT SubmittalSheet Adobe PDF library 17.00

Related Documents

Preview Pioneer Multi-Zone Free-Match Air Conditioner Parts Diagrams
Comprehensive parts catalog for Pioneer Multi-Zone Free-Match ductless, ducted, or both residential and light-commercial air conditioning and heat pump systems. Features detailed parts lists for various outdoor and indoor unit models.
Preview Pioneer Multi Inverter Air Conditioner Disassembly Manual - Indoor and Outdoor Units
Detailed disassembly instructions for Pioneer Multi Inverter Air Conditioner indoor and outdoor units, covering various models including Ceiling Cassette, Ductable Concealed, Floor-Ceiling Flex, and Wall Mounted types. Includes step-by-step guides for technicians.
Preview Pioneer Quad-Zone Ductless Inverter Heat Pump Set Submittal Sheet YN040GLSI24M4G
This document provides detailed specifications, performance data, dimensional information, and compatibility details for the Pioneer Quad-Zone Ductless Inverter Heat Pump Set, model YN040GLSI24M4G, which supports multiple indoor air handler units.
Preview Pioneer YN050GLSI24M5G Ductless Inverter Heat Pump Set Specifications
Detailed submittal sheet for the Pioneer YN050GLSI24M5G Quint (5) Circuit Ductless Inverter Heat Pump Set, including cooling and heating performance, electrical information, exterior unit specifications, and compatible indoor air handler units.
Preview Pioneer YN040GLSI24M4G Quad-Zone Ductless Inverter Heat Pump Submittal Sheet
Technical specifications and dimensional data for the Pioneer YN040GLSI24M4G Quad-Zone Ductless Inverter Heat Pump Set, including indoor and outdoor unit details, performance ratings, and compatibility.
Preview Pioneer Quantum Ultra 12,000 BTU Ductless Heat Pump System Submittal Sheet
Submittal sheet for the Pioneer Quantum Ultra 12,000 BTU 23 SEER2 wall-mounted ductless inverter heat pump system. Details cooling and heating performance, electrical specifications, unit dimensions, piping, refrigerant, warranty, features, and accessories from Parker Davis HVAC International.
Preview Pioneer Inverter Air Conditioner Indoor/Outdoor Unit Disassembly Manual
Detailed disassembly instructions for Pioneer Inverter Air Conditioner Indoor (Cassette) and Outdoor (ODU) units, covering models CYT, CT, and YN series.
Preview Pioneer Quint-Zone Ductless Inverter Heat Pump System Specifications
Comprehensive submittal sheet detailing the Pioneer Quint-Zone (5) Circuit Ductless Inverter Heat Pump Set (YN050GLSI24M5G / WT0xxGLSI24HLG), covering performance, electrical, piping, dimensional data, compatibility, and warranty information.