Cooling Mode Performance
Rated Cooling | 42,000 BTU/hr |
Ambient Range | 5°F ~ 131°F |
SEER Rating | 22.0 BTU/W·h |
EER Rating | 12.0 BTU/W·h |
* 100% Capacity @ Indoor DB 80°F/WB 67°F
Heating Mode Performance
Rated Heating | 42,000 BTU/hr |
Ambient Range | -13°F ~ 86°F |
HSPF2 IV (V) | 9.5 (8.2) BTU/W·h |
COP (47°F) | 3.5 (W/W) |
*High Heat (47°F) = 42,000 BTU / Low Heat (17°F) = 29,400 BTU / COP (5°F) = 2.0
Electrical Information
Cooling | Heating | |
---|---|---|
Rated Input (W) | 3,550 | 3,260 |
Rated Current (A) | 15.9 | 14.6 |
Breaker Needed | 45A (Double-Pole) | |
Power Supply | 208~230V, 1Ph, 60Hz |
Piping and Refrigerant
Liquid Line (OD) | 1/4" (5) |
Suction Line (OD) | 3/8" (5) |
Refrigerant Precharge | R454b (Selectable Lineset) |
Vertical Run/Elevation Diff. | 50 ft. / 33 ft. |
Exterior Unit (Condenser) Specifications
Sound Level (dBA) | 65 |
Recommended Room Size | 1,000~1,600 Sq. ft. |
Minimum Room Size | 135 Sq. ft. |
Compressor | Twin-Rotary |
Dimensions (WDH) | 42"-1/4 x 18"-3/8 x 33"-1/2 |
Weight (lbs) | 174.2 |
Compatible Indoor Air Handler Units
CT009GLSILCFHG (9K) | CT012GLSILCFHG (12K) | |
CT018GLSILCFHG (18K) | CT024GLSILSFHG (24K) | |
Quantity | 5 (Up to 60,000 BTU) | |
Max Circuit Length | 80 ft. (9K) / 100 ft. (12K/18K/24K) | |
Max Vertical Run | 33 ft. (9K/12K/18K/24K) | |
Adjustment Charge | 0.11 oz x (L1+L2+L3+L4+L5-125 ft.) |
Visual Components
Image: A wall-mounted indoor unit with a Pioneer logo and grille.
Image: An outdoor condensing unit with a Pioneer logo and fan grille.
Image: An installation kit showing pipes and cables.
Image: A handheld remote controller.
Condenser Unit Dimensional Data (YN050GLSI24M5G)
Diagram showing the front and side views of the outdoor condensing unit with dimensions labeled A, B, C, D, E.
Model | A | B | C | D | E |
---|---|---|---|---|---|
YN050GLSI24M5G (42,000 BTU / 5-Zone) | 26" (660 mm) | 18-1/4" (462 mm) | 18-3/8" (468 mm) | 42-1/4" (1074 mm) | 33-5/8" (853 mm) |
Air Handler Dimensional Data
The following sections detail the dimensions for various compatible indoor air handler units.
CT009GLSILCFHG Air Handler
Diagrams showing the top, side, and ceiling installation view of the CT009GLSILCFHG air handler, including dimensions and required clearances for air outlet, air inlet, floor-to-panel, and inlet-to-ceiling.
Panel Thickness: 2-3/8 in (60 mm)
Dimensions (approximate from diagram):
- Overall Width/Depth: 25-5/8 in (650 mm)
- Air Handler Body Depth: 9-5/8 in (245 mm)
- Ceiling to Floor Clearance: ≥ 8 ft 2 in
- Inlet to Ceiling Clearance: ≥ 10-3/4 in
- Air Outlet to Wall Clearance: ≥ 39-3/8 in
CT012GLSILCFHG Air Handler
Diagrams showing the top, side, and ceiling installation view of the CT012GLSILCFHG air handler, including dimensions and required clearances.
Panel Thickness: 2-3/8 in (60 mm)
Dimensions (approximate from diagram):
- Overall Width/Depth: 25-5/8 in (650 mm)
- Air Handler Body Depth: 9-5/8 in (245 mm)
- Ceiling to Floor Clearance: ≥ 8 ft 2 in
- Inlet to Ceiling Clearance: ≥ 10-3/4 in
- Air Outlet to Wall Clearance: ≥ 39-3/8 in
CT018GLSILCFHG Air Handler
Diagrams showing the top, side, and ceiling installation view of the CT018GLSILCFHG air handler, including dimensions and required clearances.
Panel Thickness: 2-3/8 in (60 mm)
Dimensions (approximate from diagram):
- Overall Width/Depth: 25-5/8 in (650 mm)
- Air Handler Body Depth: 9-5/8 in (245 mm)
- Ceiling to Floor Clearance: ≥ 8 ft 2 in
- Inlet to Ceiling Clearance: ≥ 10-3/4 in
- Air Outlet to Wall Clearance: ≥ 39-3/8 in
CT024GLSILCFHG Air Handler
Diagrams showing the top, side, and ceiling installation view of the CT024GLSILCFHG air handler, including dimensions and required clearances.
Panel Thickness: 2-7/8 in (73 mm)
Dimensions (approximate from diagram):
- Overall Width/Depth: 37-3/8 in (950 mm)
- Air Handler Body Depth: 9-5/8 in (245 mm)
- Ceiling to Floor Clearance: ≥ 8 ft 2 in
- Inlet to Ceiling Clearance: ≥ 10-3/4 in
- Air Outlet to Wall Clearance: ≥ 39-3/8 in
Combination Data and Miscellaneous Information
Air Handler Specifications
Model | Airflow Rate (cfm) | Sound Level (dBA) | Auto Air Circulation | Dimensions (WDH) | Weight (lbs) |
---|---|---|---|---|---|
CT009GLSILCFHG | 329 (Turbo)/300 (Hi) / 270 (Med) / 217 (Lo)/194 (Mute) | 43 (Turbo)/41 (Hi) / 37 (Med) / 33 (Lo) / 32 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 22"-1/2 x 22"-1/2 x 9"-5/8 | 32.0 |
CT012GLSILCFHG | 360(Turbo)/320(Hi)/260(Med)/200(Lo)/190(Mute) | 45 (Turbo) / 43 (Hi) / 39 (Med) / 35 (Lo) / 32 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 22"-1/2 x 22"-1/2 x 9"-5/8 | 32.0 |
CT018GLSILCFHG | 441(Turbo)/394(Hi)/ 335(Med)/282(Lo)/253(Mute) | 48 (Turbo) / 46 (Hi) / 42 (Med) / 39 (Lo) / 37 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 22"-1/2 x 22"-1/2 x 9"-5/8 | 32.0 |
CT024GLSILCFHG | 836(Turbo)/765(Hi)/630(Med)/530(Lo)/482(Mute) | 51 (Turbo) / 48 (Hi) / 44 (Med) /40 (Lo)/37 (Mute) | 2-Way Louver (Up-Down + Left-Right) | 33"-1/8 x 33"-3/4 x 10"-3/4 | 51.8 |
Matching Table (# Circuits Utilized)
2-Circuits | (9000-24000) + (9000-24000) |
3-Circuits | (9000-24000) + (9000-24000) + (9000-18000) |
4-Circuits | (9000-24000) + (9000-18000) + (9000-12000) + (9000-12000) |
5-Circuits | (9000-24000) + (9000-18000) + (9000-12000) + (9000-12000) + (9000-12000) |
Piping Diameters
9000 BTU | 1/4" (Liquid) - 3/8" (Suction) |
12000 BTU | 1/4" (Liquid) - 3/8" (Suction) |
18000 BTU | 1/4" (Liquid) - 1/2" Adapter Required (Suction) |
24000 BTU | 1/4" (Liquid) - 5/8" Adapter Required (Suction) |
(All Necessary Adapters Provided with Condenser)
Note: If the total demand from the combined group of indoor units exceeds the rated capacity of the outdoor unit, the capacity of each indoor unit will be annotated accordingly. Each indoor unit operates at a random, self-regulated capacity based on the actual demand it measures from its zone (between 30% to 100% of its rated capacity) or turns Off as needed.
Warranty Information and Length
Image: A shield graphic with the number '10' indicating a 10-year warranty.
Complete warranty details are available with the vendor or online at pdhvac.com/support/warranty/. This high-quality system is eligible for up to 10 years limited warranty on the compressor, and 7 years on other internal parts. To qualify for this warranty, the system must be installed within 90 days by a registered technician. All other installations that are registered default to 5 years parts/compressor. Products unregistered qualify for only 1 year parts/compressor warranty.
Outstanding Features
- LED Display
- Energy Saving ?
- Ultra-Thin Design
- Dual Drain Options
- Customizable Timer
- Eco-Friendly Refrigerant
- Whisper-Quiet Operation
- Power Loss Memory Recovery
Available Accessories
Part Number | Description |
---|---|
IKT-LCVR4P-KIT | Decorative PVC Line Cover Kit |
IKT-LNBR-1/4-3/8 | BendAid Flexible Easy Bender Kit |
BRK-FRM-C-2P | Folding Mounting Bracket w/ Leveler |
IKT-UVL32UL-AG | UVC Bacterial Disinfection Kit |
IKT-SURPRK-DV2 | Ultimate Surge and Power Protection |