The OMRON NE1A-SCPU01 is a compact programmable safety circuit controller designed for industrial applications. It is certified by TÜV, CE, and cULus LISTED, meeting IEC/EN61508 (SIL3) and EN954-1 (Cat. 4) standards.
Key Features:
Image: A compact industrial safety network controller unit, dark gray with various input/output terminals, connectors, and indicator lights on the front panel. It has a rectangular shape with a textured surface, designed for DIN rail mounting.
Name | No. of I/O points | Model | ||
---|---|---|---|---|
Safety inputs | Test outputs | Safety outputs | ||
Safety Network Controller | 16 | 4 | 8 | NE1A-SCPU01 |
Certification body | Standard |
---|---|
TÜV Rheinland | EN954-1:1996, EN60204-1:1997, EN61000-6-2:2001, EN61000-6-4:2001, EN418:1992, IEC61508 part1-7/12.98-05.00, IEC61131-2/02.03, NFPA 79-2002, ANSI RIA15.06-1999, ANSI B11.19-2003 |
UL | UL1998, NFPA79, UL508, CSA22.2 No. 142, CSA22.2 No. 213, UL1604 |
Item | Specification |
---|---|
Communications power supply voltage | 11 to 25 VDC supplied via communications connector |
Unit power supply voltage (VO)* | 20.4 to 26.4 VDC (24 VDC -15%/+10%) |
I/O power supply voltage (V1, V2)* | |
Current consumption | Communications power supply: 24 VDC, 15 mA |
Internal circuit power supply: 24 VDC, 230 mA | |
Overvoltage category | II |
Noise immunity | Conforms to IEC61131-2. |
Vibration resistance | 10 to 57 Hz: 0.35 mm, 57 to 150 Hz: 50 m/s² |
Shock resistance | 150 m/s²: 11 ms |
Mounting method | 35-mm DIN Track (IEC 60715 TH35-7.5/TH35-15) |
Ambient operating temperature | -10 to 55°C |
Ambient operating humidity | 10% to 95% (with no condensation) |
Ambient storage temperature | -40 to 70°C |
Degree of protection | IEC60529 standard IP20 |
Serial interface | USB version 1.1 |
Weight | 460 g max. |
* VO-GO: Internal control circuit
V1-G1: For external input device, test output
V2-G2: For external output device
Input type | Sinking inputs (PNP) |
---|---|
ON voltage | 11 VDC min. between each terminal and ground |
OFF voltage | 5 VDC min. between each terminal and ground |
OFF current | 1 mA max. |
Input current | 4.5 mA |
Output type | Sourcing outputs (PNP) |
---|---|
Rated output current | 0.7 A max./output (See note.) |
ON residual voltage | 1.2 V max. between each output terminal and V |
Leakage current | 0.1 mA max. |
Note: The total current when T0 to T3 are simultaneously ON is 1.4 A.
Output type | Sourcing outputs (PNP) |
---|---|
Rated output current | 0.5 A max./output |
ON residual voltage | 1.2 V max. between each output terminal and V |
Leakage current | 0.1 mA max. |
Item | Specification | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Communications protocol | DeviceNet compliant | ||||||||||||||||
Connection form | Multi-drop system and T-branch system can be combined (for trunk line and branch lines) | ||||||||||||||||
Communications speed | 500/250/128 kbps | ||||||||||||||||
Communications media | Special cable, 5 conductors (2 for communications, 2 for power supply, 1 for shielding) | ||||||||||||||||
Communications distance |
Note: Figures in parentheses ( ) indicate values when a narrow cable is used. | ||||||||||||||||
Communications power supply | 11 to 25 VDC | ||||||||||||||||
No. of connectable nodes | 63 | ||||||||||||||||
Safety I/O communications | Safety Master function
| ||||||||||||||||
Standard I/O communications | Standard Slave function
| ||||||||||||||||
Message communications | Max. message length: 552 bytes |
The internal circuit diagram illustrates the connections within the NE1A-SCPU01, showing the flow from DeviceNet (V+, CAN H, DRAIN, CAN L, V-, D+, D-) through a non-insulated DC-DC converter and USB interface to the internal circuit. This circuit then branches to the Safety Input Circuit and an insulated DC-DC converter, which feeds into the Safety Output Circuit and Test Output Circuit. The outputs are connected to various terminals (V0, G0, V1, G1, T0, T3, V2, G2, IN0 to IN15, OUT0 to OUT7).
Terminal name | Description |
---|---|
V0 | Power supply terminal for internal circuit. The two V0 terminals are internally connected. |
G0 | Power supply terminal for internal circuit. The two G0 terminals are internally connected. |
V1 | Power supply terminal for external input device and test output. |
G1 | Power supply terminal for external input device and test output. |
V2 | Power supply terminal for external output device. |
G2 | Power supply terminal for external output device. |
IN0 to IN15 | Safety input terminal. |
T0 to T3 | Test output terminal. Connected to IN0 to IN15 safety inputs. Each test output terminal outputs a different test pulse pattern. Terminal T3 also supports a current monitoring function for the output signal. Example: Muting lamp. |
OUT0 to OUT7 | Safety output terminals. |
This diagram illustrates a typical emergency stop application circuit with manual reset. It shows connections from a 24 VDC power supply (E0, E1, E2) to the NE1A-SCPU01's V0 and G0 terminals. An emergency stop switch (S1) with positive opening mechanism is connected to terminals 11 and 12, and a reset switch (S2) is also included. Safety inputs (IN0-IN15) are shown connected, along with test outputs (T0-T3) and safety outputs (OUT0-OUT7). The circuit also includes contactors KM1 and KM2, with KM1-NC and KM2-NC connections, and a motor (M) controlled by KM1 and KM2. The diagram indicates the flow of signals and power within the safety system.
Color | Signal |
---|---|
Red | Power cable positive side (V+) |
White | Communications data high side (CAN H) |
Shield | |
Blue | Communications data low side (CAN L) |
Black | Power cable negative side (V-) |
Note: For details on communications specifications and wiring, refer to the DeviceNet Master Units Operation Manual (Cat. No.: W379).
All units are in millimeters unless otherwise indicated.
The NE1A-SCPU01 has a front view showing its terminals and indicators, with a width of 90.4 mm. The side view shows a depth of 131.4 mm and a height of 114.1 mm (overall height 111.1 mm, with a mounting height of 99 mm from the base). The top view provides an additional perspective of the unit's form factor.
Conversion Note: To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
⚠️ WARNING
This catalog serves as a guide for customers to select appropriate safety products. When choosing products, selecting the right ones for devices or equipment, and developing a safety-related system to fully utilize product functions, it is crucial to observe the following items.
Products listed in this catalog must be used properly concerning their location, performance, and functionality. The selection and use of these products should involve a risk assessment system early in the design development stage to identify potential dangers in equipment, optimizing safety product selection. A poorly designed risk assessment system can lead to incorrect safety product choices.
When developing a safety system for devices and equipment using safety products, efforts should be made to understand and conform to all relevant international and industrial standards.
Safety products have functions and mechanisms designed to ensure safety as defined by standards. These functions are intended to achieve their full potential within safety-related systems. Users must fully understand all functions and mechanisms to develop systems that ensure optimal usage.
Properly educated and trained engineers should be selected to develop safety-related systems and install safety products in devices and equipment.
Safety products should conform to pertinent laws, regulations, and standards. Ensure they are used in accordance with the laws, regulations, and standards of the country where the devices and equipment incorporating these products are distributed.
Carefully read the specifications and precautions in this catalog and the Operating Manual provided with the product to learn usage procedures that optimize product choice. Any deviation from precautions may lead to unexpected device or equipment failure not anticipated by safety-related systems or fire originating from equipment failure.
When transferring devices and equipment, ensure one copy of the Operating Manual is kept and another copy is packed with the device or equipment for the recipient's operational convenience.
OMRON is not responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the product.
Upon customer request, OMRON provides applicable third-party certification documents identifying ratings and limitations of use for the products. This information alone is insufficient for a complete determination of product suitability in combination with the end product, machine, system, or other application.
Examples of applications requiring particular attention (not an exhaustive list, nor implying suitability):
Users must know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Product specifications and accessories may change based on improvements. OMRON changes model numbers when published ratings or features change significantly. However, some specifications may change without notice. For specific applications, consult an OMRON representative to confirm actual specifications.
Dimensions and weights are nominal and not for manufacturing purposes, even when tolerances are shown.
Information in this catalog is believed accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors.
Performance data is a guide for determining suitability and does not constitute a warranty. It may represent OMRON's test conditions, and users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
OMRON is not responsible for user programming of a programmable product or its consequences.
This catalog must not be copied for sales or promotions without permission. It is protected by copyright and intended solely for use with the product. Users must notify OMRON before copying or reproducing this catalog for any other purpose. If copying or transmitting this catalog to another, copy and transmit it in its entirety.
![]() |
OMRON NE1A-SCPU01-V1 Safety Network Controller Instruction Manual Comprehensive instruction manual for the OMRON NE1A-SCPU01-V1 Safety Network Controller, covering installation, operation, safety precautions, specifications, and wiring diagrams for optimal performance and compliance. |
![]() |
OMRON NE1A-SCPU01-EIP Safety Network Controller: Installation & Operation Manual Comprehensive instruction manual for the OMRON NE1A-SCPU01-EIP Safety Network Controller, detailing installation, operation, safety precautions, and technical specifications for industrial automation. |
![]() |
OMRON NX Series Safety Network Controller: Flexible Production Line Safety Explore OMRON's NX Series Safety Network Controller for scalable, flexible, and efficient production line safety. Features EtherNet/IP, CIP Safety, EtherCAT, and Sysmac Studio for simplified design and maintenance. |
![]() |
Omron MC-S Series Coded Magnetic Safety Interlock Switches Detailed information on Omron MC-S Series safety interlock switches, including features, specifications, applications, and ordering information for compact coded magnetic safety interlock switches and control units. |
![]() |
Omron Industrial Automation Core Product Guide 2021: Integrated Solutions Explore Omron's Industrial Automation Core Product Guide 2021, featuring sensors, controllers, robotics, vision systems, and safety solutions. Learn about integrated, intelligent, and interactive automation from Omron Automation. |
![]() |
OMRON EJ1 Temperature Controller: Safety Precautions and Usage Guide Essential safety guidelines, installation instructions, and wiring specifications for the OMRON EJ1 Temperature Controller. Learn how to safely operate and install this industrial automation device. |
![]() |
OMRON F3SG-SR-K Safety Light Curtain: Instruction Sheet and Safety Guide Detailed instructions and safety guidelines for the OMRON F3SG-SR-K Safety Light Curtain, covering installation, wiring, LED indicators, and essential precautions for safe operation. |
![]() |
OMRON OS32C Safety Laser Scanner Quick Reference Guide Quick reference guide for the OMRON OS32C safety laser scanner, covering safety precautions, installation, wiring, testing, and troubleshooting. |