Introduction
Thank you for purchasing the OMRON NE1A-SCPU01-V1 Safety Network Controller. This manual provides essential precautions for its installation and operation.
- Only qualified personnel trained in professional electrical techniques should handle the NE1A-SCPU01-V1.
- Before operating, read this manual thoroughly to acquire sufficient knowledge of the NE1A-SCPU01-V1.
- For safe and correct use, also refer to the following manuals:
- Safety Network Controller OPERATION MANUAL (Cat. No. Z906-E1)
- SYSTEM CONFIGURATION MANUAL (Cat. No. Z905-E1)
- DeviceNet™ OPERATION MANUAL (Cat. No. W267-E1)
- Keep this manual for future reference.
OMRON Corporation © OMRON Corporation 2005-2021 All Rights Reserved. Instructions in EU languages and a signed EU Declaration of Conformity are available on the OMRON website: http://www.ia.omron.com/support/models/.
Declaration of Conformity
OMRON declares that the NE1A-SCPU01-V1 is in conformity with the requirements of the following EU Directives and UK Legislations:
- EU: Machinery Directive 2006/42/EC, EMC Directive 2014/30/EU, RoHS Directive 2011/65/EU
- UK: 2008 No 1597 Machinery (Safety), 2016 No 1091 EMC, 2012 No 3032 RoHS
Safety Standards
The NE1A-SCPU01-V1 is designed and manufactured in accordance with the following standards:
- EN ISO13849-1:2015 Cat.4 PL e
- IEC61326-3-1
- EN ISO13850
- IEC61508 parts 1-7 SIL3
- EN61131-2
- UL508
- ANSI/ISA 12.12.01
- EN ISO13849-2
- EN62061
- EN60204-1
- NFPA 79
- ANSI RIA 15.06
- ANSI B11.19
- CSA C22.2 No.142, No.213
- ANSI/UL1998
⚠ WARNING: Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage.
Precautions for Safe Use
Handle with care
Do not drop the NE1A-SCPU01-V1 or subject it to excessive vibration or mechanical shocks. The NE1A-SCPU01-V1 may be damaged and may not function properly.
Installation and storage environment
Do not use or store the NE1A-SCPU01-V1 in any of the following locations:
- Locations subject to direct sunlight.
- Locations subject to temperatures or humidity outside the range specified in the specifications.
- Locations subject to condensation as the result of severe changes in temperature.
- Locations subject to corrosive or flammable gases.
- Locations subject to dust (especially iron dust) or salts.
- Locations subject to water, oil, or chemicals.
- Locations subject to shock or vibration.
Take appropriate and sufficient countermeasures when installing systems in the following locations. Inappropriate and insufficient measures may result in malfunction:
- Locations subject to static electricity or other forms of noise.
- Locations subject to strong electromagnetic fields.
- Locations subject to possible exposure to radioactivity.
- Locations close to power supplies.
Installation/Mounting
- Use the NE1A-SCPU01-V1 within an enclosure with IP54 protection or higher of IEC/EN 60529.
- Use DIN rail (TH35-7.5 according to IEC60715) for placing the NE1A-SCPU01-V1 into the control board.
- Mount the NE1A-SCPU01-V1 to DIN rails with attachments (TYPE PFP-M, not incorporated to this product), to prevent it from dropping out of rails due to vibration etc.
- Spacing should be available around the NE1A-SCPU01-V1 at least 50mm from its top and bottom surfaces for ventilation and wiring.
- This is a class A product. In residential areas it may cause radio interference, in which case the user may be required to take adequate measures to reduce interference.
Installation/Wiring
Use the following to wire external I/O devices to the NE1A-SCPU01-V1:
- Solid wire: 0.2 to 2.5 mm² (AWG24 to 12)
- Standard (Flexible) wire: 0.34 to 1.5 mm² (AWG22 to 16)
- Disconnect the NE1A-SCPU01-V1 from power supply when wiring. Devices connected to the NE1A-SCPU01-V1 may operate unexpectedly.
- Apply properly specified voltages to the NE1A-SCPU01-V1 inputs. Applying inappropriate DC voltage and any AC voltages causes the NE1A-SCPU01-V1 to fail.
- Be sure to separate the communication cable and the I/O cable from the high-voltage/current lines.
- Be cautious not to have fingers caught when attaching connectors to the plugs on the NE1A-SCPU01-V1.
- Mount screw of DeviceNet Connector and I/O Connector correctly (0.25-0.3 N•m).
- Incorrect wiring may lead to loss of safety function. Wire conductors correctly and verify the operation of the NE1A-SCPU01-V1 before commissioning the system in which the NE1A-SCPU01-V1 is incorporated.
- After wiring is completed, be sure to remove label for wire clipping prevention on the NE1A-SCPU01-V1 to enable heat to escape for proper cooling.
Power Supply Selection
Use a DC power supply satisfying the requirements below:
- Secondary circuits of the DC power supply are isolated from its primary circuit by double insulations or reinforced insulations.
- DC power supply satisfies the requirement for class 2 circuits or limited voltage/current circuit stated in UL 508.
- 20ms or over of the output hold time.
- DC power supply that satisfies the requirements for SELV given in IEC/EN60950-1 or EN 50178.
Periodical Inspection and Maintenance
- Disconnect the NE1A-SCPU01-V1 from power supply when replacing. Devices connected to the NE1A-SCPU01-V1 may operate unexpectedly.
- Do not dismantle, repair, or modify the NE1A-SCPU01-V1. It may lead to loss of its safety functions.
Disposal
- Be cautious not to be injured when dismantling the NE1A-SCPU01-V1.
The above-mentioned is a part of directions. Please use it after reading the operation manual.
Additional Precautions According to ANSI/ISA 12.12.01
- This equipment is suitable for use in Class I, Div.2, Group A, B, C, D or Non-Hazardous Locations Only.
- WARNING: Explosion Hazard - Substitution of Components may Impair Suitability for Class I, Div.2.
- WARNING: Explosion Hazard - Do not Disconnect Equipment Unless Power Has Been Switched off or the Area Is Known to Be Non-Hazardous.
- This device is open-type and is required to be installed in an enclosure suitable for the environment and can only be accessed with the use of a tool or key.
- WARNING: Explosion Hazard - Do not connect USB Connector Unless Power Has Been Switched Off Or The Area Is Known To Be Non-Hazardous.
Alert Statements
⚠ WARNING: Serious injury may possibly occur due to loss of required safety functions. Do not use test outputs of the NE1A-SCPU01-V1 as any safety outputs.
⚠ WARNING: Serious injury may possibly occur due to loss of required safety functions. Do not use DeviceNet standard I/O data or Explicit message data as any safety data.
⚠ WARNING: Serious injury may possibly occur due to loss of required safety functions. Do not use LEDs on the NE1A-SCPU01-V1 for safety operations.
⚠ WARNING: Serious injury may possibly occur due to breakdown of outputs. Do not connect loads beyond the rated value to the safety outputs and the test outputs.
⚠ WARNING: Serious injury may possibly occur due to loss of required safety functions. Wire the NE1A-SCPU01-V1 properly so that 24VDC line do NOT touch the outputs accidentally or unintentionally.
⚠ WARNING: Serious injury may possibly occur due to loss of required safety functions. Ground the 0V line of the power supply for external output devices so that the devices do Not turn ON when the safety output line or the test output line is grounded.
⚠ WARNING: Serious injury may possibly occur due to loss of required safety functions. Use appropriate components or devices according to the requirements given in the following table.
Controlling Devices | Requirements |
---|---|
Emergency stop switch | Use approved devices with Direct Opening Mechanism complying with IEC/EN 60947-5-1. |
Door interlocking switch, Limit switch | Use approved devices with Direct Opening Mechanism complying with IEC/EN 60947-5-1 and capable of switching micro loads of 24VDC, 4mA. |
Safety sensor | Use approved sensors complying with the relevant product standards, regulations, and rules in the country where it is used. |
Relay with forcibly guided contacts | Use approved devices with forcibly guided contacts complying with IEC61810-3. For feedback purpose, use devices with contacts capable of switching micro loads of 24VDC, 4mA. |
Contactor | Use contactors with forcibly guided mechanism and monitor its auxiliary NC contact to detect failures of contactor. For feedback purpose, use devices with contacts capable of switching micro loads of 24VDC, 4mA. |
Other devices | Evaluate whether devices used are appropriate to satisfy the requirements of safety category level. |
Part Names and Functions / Dimensions
Overview of NE1A-SCPU01-V1 Components
The NE1A-SCPU01-V1 features various components including removable I/O and power terminals, a USB port, and a DeviceNet connector. It also includes a Node Address Switch and a Baud Rate Switch for configuration. Visual indicators include LEDs for Module Status (MS), Network Status (NS), Configuration Lock (LOCK), USB Communication (COMM), Input/Output status (IN/OUT), and a 7-segment LED display.
Indicators
LED Designation | LED Color | Status | Description |
---|---|---|---|
MS (Module Status) | Green | Lit | In Executing |
Flashing | In Idle | ||
Red | Lit | In Critical fault | |
Flashing | In Recoverable fault | ||
Green/Red | Flashing | In Self Testing, Waiting for TUNID, or Configuring | |
NS (Network Status) | Not lit | No power | |
Green | Lit | Online connection established | |
Flashing | Online but connection not established | ||
Red | Lit | Critical link failure | |
Flashing | Connection time-out | ||
Green/Red | Flashing | In Waiting for TUNID | |
LOCK (Configuration Lock) | Not lit | Not online / Not powered | |
Yellow | Lit | Locked Valid Configuration | |
Flashing | Unlocked Valid Configuration | ||
COMM (USB) | Not lit | Invalid Configuration | |
Yellow | Flashing | Communicating | |
Not lit | Not communicating | ||
IN 0, 1, 2...15 / OUT 0, 1, 2...7 (I/O status) | Yellow | Lit | Input/Output signal ON |
Not lit | Input/Output signal OFF | ||
Red | Lit | Failure detected in the Input/Output circuit / Discrepancy error has occurred in I/O set for dual channel mode | |
Flashing | Failure detected in the associated I/O circuit in case of dual channel configuration |
7-Segment LEDs
- At normal state, the 7-Segment LED displays the node address of the NE1A-SCPU01-V1 itself in decimal number (00-63). The node address, depending on the operational state of the NE1A-SCPU01-V1, turns "ON" or "Flashing".
- If in fault status, error code and error occurrence node address are displayed alternately in the order of node address.
- In "standalone mode", "nd" is displayed in the normal condition.
Rotary Switch
- Node Address is settable by a 2-digit 10-position Rotary Switch.
- Node Address range is from 0 to 63. (Default: 63)
- If set from 64 to 99, Node Address is settable by Configuration tool.
Dip Switch
Baud Rate | Switch | |||
---|---|---|---|---|
1 | 2 | 3 | 4 | |
125Kbit/s (default) | OFF | OFF | OFF | OFF |
250Kbit/s | ON | OFF | OFF | OFF |
500Kbit/s | OFF | ON | OFF | OFF |
ON | ON | OFF | OFF | |
Software setting | OFF | OFF | ON | OFF |
ON | OFF | ON | OFF | |
ON | ON | OFF | ON | |
ON | ON | ON | OFF | |
Auto Baud Rate Detection | X | X | X | ON |
X: Don't care |
Internal Circuitry and Wiring
Terminal Designations and Functions
Terminal Designations | Descriptions |
---|---|
V0 | Power terminal for internal circuit (Logic). |
G0 | Power terminal for internal circuit (Logic). |
V1 | Power terminal for external input devices and test outputs. |
G1 | Power terminal for external input devices and test outputs. |
V2 | Power terminal for external output devices e.g. safety outputs. |
G2 | Power terminal for external output devices e.g. safety outputs. |
IN0 through IN15 | Terminal for Safety input signals. |
T0 through T3 | Test output terminal for use in conjunction with IN0 through IN15 safety inputs. Each test output provides a unique set of test pulse patterns. T3 also supports current monitoring of the output signal for e.g. muting applications. |
OUT0 through OUT7 | Terminal for Safety outputs |
- The maximum terminal temperature is 80 °C.
- Use SELV Power Source for the DC main power source.
Specifications
Environmental Specifications
Item | Specifications |
---|---|
DeviceNet supply voltage | 11 to 25VDC (Supplied from communications power supply) |
Device supply voltage V0, V1, V2 1) | 20.4 to 26.4VDC (24VDC, -15% to +10%) |
DeviceNet current consumption | 15mA at 24VDC |
Current consumption V0 (internal logic circuit) | 230mA at 24VDC |
EMC | Conform to IEC61131-2 |
Operating Temperature | -10 to +55°C |
Storage Temperature | -40 to +70°C |
Relative Humidity | 10 to 95% non-condensing |
Vibration resistance | 0.35 mm at 10 to 57Hz, 50m/s² at 57 to 150Hz |
Shock resistance | 150m/s²: 11ms |
Protection degree | IP20 |
Over Voltage Category | II (per IEC61131-2: 4.4.2) |
Pollution Degree | 2 |
Altitude | Max. 2000m |
Weight | 460g |
1) V0-G0: for internal logic circuit, V1-G1: for external input devices and test outputs, V2-G2: for external output devices |
Safety Input Specifications
Item | Specifications |
---|---|
Inputs type | Current sinking |
ON voltage | 11VDC min. |
OFF voltage | 5VDC max. |
OFF current | 1mA max. |
Input current | 4.5mA |
Test Output Specifications
Item | Specifications |
---|---|
Outputs type | Current sourcing |
Rated output current | 0.7A max./channel 2) |
Residual voltage | 1.2V max. |
Leakage current | 0.1mA max. |
2) T0-T3 total current at the same time: 1.4A |
Safety Output Specifications
Item | Specifications |
---|---|
Outputs type | Current sourcing |
Rated output current | 0.5A max./channel |
Residual voltage | 1.2V max. |
Leakage current | 0.1mA max. |
In case that a safety output is configured as "Safety Pulse Test", while this output is in an ON state, the pulsed off signal (pulse width: 580µs) is output continuously for fault diagnosis. Confirm response time of device connected to safety outputs so the device does not malfunction due to this off pulse.
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Contact Information
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
Contact: www.ia.omron.com
Regional Headquarters
- OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, 2132 JD Hoofddorp, The Netherlands
Tel: (31)2356-81-300
Fax: (31)2356-81-388 - OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200, Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900
Fax: (1) 847-843-7787 - OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road #05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967
Tel: (65) 6835-3011
Fax: (65) 6835-2711 - OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower, 200 Yin Cheng Zhong Road, Pu Dong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222
Fax: (86) 21-5037-2200
Note: Specifications subject to change without notice.