EG4® 6000XP Monitor System Working Modes
This guide will assist the user in configuring and customizing the integrated working modes of the 6000XP off-grid inverter.
1. Operating Mode Description
The EG4 6000XP inverter offers several preset working modes for extensive system customization. This guide helps users set the station's needs based on factors like time of day.
Working Mode Definitions:
- Off-Grid Mode: The system operates on a pre-set priority. The inverter draws power from solar arrays for loads. If solar power is insufficient, it draws from the battery bank. As a last resort, it switches to bypass mode to power loads from AC input.
- Bypass Mode: Grid power handles the load demand, while solar energy charges the battery.
- Power Backup Mode: The battery discharges its stored energy only during a grid power outage.
- AC Charge Mode: During AC charge time, if solar power is insufficient, grid power supplements battery charging.
2. Off-Grid Mode
Source Priority: Solar > Battery > Utility Grid (SBU)
If solar power exceeds the load, solar powers the load first, and excess solar charges the battery. If solar power is less than the load, solar and battery power the load together. The system discharges the battery until it reaches the EOD Voltage/SOC.
2.1 Configuration via App & Web
- AC Charge Time: Configurable for three stages (e.g., 00:00-00:00).
- AC Charge Start Time 1: [0, 23] : [0, 59]
- AC Charge End Time 1: [0, 23] : [0, 59]
- AC Charge Start Time 2: [0, 23] : [0, 59]
- AC Charge End Time 2: [0, 23] : [0, 59]
- AC Charge Start Time 3: [0, 23] : [0, 59]
- AC Charge End Time 3: [0, 23] : [0, 59]
- AC Charge Based On: Disable.
- On-Grid EOD SOC/Voltage: Set the desired level point for Grid/Utility takeover from the battery.
- On Grid EOD Voltage(V): [40, 58]
- On Grid EOD SOC(%): [10, 90]
- Off-Grid Cut-off SOC/Voltage: Set to be less than On-Grid EOD.
- Discharge Cut-off Voltage(V): [40, 56]
- Discharge Cut-off SOC(%): [0, 90]
2.2 Configuration via LCD
- Setting 11 (Off-Grid Cut-off SOC/Voltage): Set < On-Grid EOD.
- Setting 12 (On-Grid EOD SOC/Voltage): Set the desired level point for Grid/Utility takeover from the battery.
- Setting 14 (AC Charge): Disable.
- Setting 15 (AC First Time): 00:00-00:00 (all 3 stages should be the same).
CutOFF: Cut off Voltage/SOC
This setting allows the user to set the cutoff Voltage or SOC based on the selection made in Setting 10, TEOd.
- Cutoff Voltage: Range 40.0V - On-Grid EOD Voltage. Default: 42V.
- Cutoff SOC: Range 0% - On-Grid EOD SOC%. Default: 15%.
EOD: Battery Discharge Cutoff
This setting allows the user to set the End of Discharge Voltage and SOC parameters.
- End of Discharge Cutoff Voltage: Range: Cutoff Voltage – 58V. Default: 42V.
- End of Discharge Cutoff SOC: Range: Cutoff SOC – 90%. Default: 15%.
3. Bypass Mode
Source Priority: Utility Grid > Solar > Battery (USB)
Bypass Mode: Grid AC powers the load, and solar charges the battery. Power Backup Mode: Battery discharges only when grid power is out.
3.1 Configuration via App & Web
- AC Charge Time: 00:00-23:59 (or as required. If Time 1 is 00:00-23:59, the feature is enabled all day).
- AC Charge Start Time 1: [0, 23] : [0, 59]
- AC Charge End Time 1: [0, 23] : [0, 59]
- AC Charge Start Time 2: [0, 23] : [0, 59]
- AC Charge End Time 2: [0, 23] : [0, 59]
- AC Charge Start Time 3: [0, 23] : [0, 59]
- AC Charge End Time 3: [0, 23] : [0, 59]
- AC Charge Based On: Disable.
- On-Grid EOD SOC/Voltage: Set the desired level point for Grid/Utility takeover from the battery.
- On Grid EOD Voltage(V): [40, 58]
- On Grid EOD SOC(%): [10, 90]
- Off-Grid Cut-off SOC/Voltage: Set < On-Grid EOD.
- Discharge Cut-off Voltage(V): [40, 56]
- Discharge Cut-off SOC(%): [0, 90]
3.2 Configuration via LCD
- Setting 11 (Off-Grid Cut-off SOC/Voltage): Set < On-Grid EOD.
- Setting 12 (On-Grid EOD SOC/Voltage): Set the desired level point for Grid/Utility takeover from the battery.
- Setting 14 (AC Charge): Disable.
- Setting 15 (AC First Time): 00:00-23:59 (or as required. If Time 1 is 00:00-23:59, the feature is enabled all day).
AC Input Load Timer Settings
This setting allows the user to set the Start/End times for the Grid/Utility to supply power to the load.
- Start Time1-3: Range: 00:00 – 23:59. Default: 00:00 - 00:00.
- End Time1-3: Range: 00:00 – 23:59. Default: 00:00 - 00:00.
4. AC Charge (and Bypass) Mode
Source Priority: Utility Grid > Solar > Battery (USB)
AC Charge Mode: Grid AC charges the battery during AC charge time if solar power is insufficient. Bypass Mode: Grid AC powers the load, and solar charges the battery. Power Backup Mode: Battery discharges only when grid power is out.
4.1 Configuration via App & Web
- AC Charge Based On: Set according to time or battery Voltage or SOC. Options include: Disable, Time (According to), Battery Voltage (According to), Battery SOC (According to), Battery Voltage and Time (According to), Battery SOC and Time (According to).
- If according to time, AC Charge Time: 00:00 – 23:59 (or as required. If Time 1 is 00:00 - 23:59, the feature is enabled all day).
- AC Charge Start Time 1: [0, 23] : [0, 59]
- AC Charge End Time 1: [0, 23] : [0, 59]
- AC Charge Start Time 2: [0, 23] : [0, 59]
- AC Charge End Time 2: [0, 23] : [0, 59]
- AC Charge Start Time 3: [0, 23] : [0, 59]
- AC Charge End Time 3: [0, 23] : [0, 59]
- If according to battery Voltage or SOC: Set start and end Voltage or SOC.
- AC Charge Start Battery Voltage(V): [38.4, 57]
- AC Charge Start Battery SOC(%): [1, 90]
- AC Charge End Battery Voltage(V): [48, 59]
- AC Charge End Battery SOC(%): [20, 100]
- On-Grid EOD SOC/Voltage: Set the desired level point for Grid/Utility takeover from the battery.
- On Grid EOD Voltage(V): [40, 58]
- On Grid EOD SOC(%): [10, 90]
- Off-Grid Cut-off SOC/Voltage: Set < On-Grid EOD.
- Discharge Cut-off Voltage(V): [40, 56]
- Discharge Cut-off SOC(%): [0, 90]
4.2 Configuration via LCD
- Setting 11 (Off-Grid Cut-off SOC/Voltage): Set < On-Grid EOD.
- Setting 12 (On-Grid EOD SOC/Voltage): Set the desired level point for Grid/Utility takeover from the battery.
- If according to battery voltage or SOC: Set start and end voltage or SOC.
- If according to time, AC Charge Time: 00:00 – 23:59 (or as required. If Time 1 is 00:00 - 23:59, the feature is enabled all day).
- Setting 14 (AC Charge): Set according to time or battery voltage or SOC.
AC Charge Control Settings for Voltage and SOC:
- Voltage: Start Voltage: 35.4V – 52V, End Voltage: 48V - 59V.
- SOC: Start SOC: 1-90%, End SOC: 20 – 100%.
AC Charge Control Settings for Start/End Times:
- Start Time1-3: Range: 00:00 – 23:59. Default: 00:00 - 00:00.
- End Time1-3: Range: 00:00 – 23:59. Default: 00:00 - 00:00.